i950

i950-C0.37/230-2 i950-C0.37/230-2 Description
Lenze logo Order code / SKU
On request
  • Rated power 0.37 kW/0.5 HP
  • Output current 2.4 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 1/N(3)/PE 230/240 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter not integrated
i950-C0.55/230-2 i950-C0.55/230-2 Description
Lenze logo Order code / SKU
On request
  • Rated power 0.55 kW/0.75 HP
  • Output current 3.2 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 1/N(3)/PE 230/240 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter not integrated
i950-C0.55/400-3 i950-C0.55/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 0.55 kW/0.75 HP
  • Output current 1.8/1.6 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C0.75/230-2 i950-C0.75/230-2 Description
Lenze logo Order code / SKU
On request
  • Rated power 0.75 kW/1 HP
  • Output current 4.2 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 1/N(3)/PE 230/240 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter not integrated
i950-C0.75/400-3 i950-C0.75/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 0.75 kW/1 HP
  • Output current 2.4/2.1 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C1.5/230-2 i950-C1.5/230-2 Description
Lenze logo Order code / SKU
On request
  • Rated power 1.5 kW/2 HP
  • Output current 7 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 1/N(3)/PE 230/240 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter not integrated
i950-C2.2/230-3 i950-C2.2/230-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 2.2 kW/3 HP
  • Output current 9.6 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 230/240 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter not integrated
i950-C2.2/400-3 i950-C2.2/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 2.2 kW/3 HP
  • Output current 5.6/4.8 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C4/230-3 i950-C4/230-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 4 kW/5 HP
  • Output current 16.5 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 230/240 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter not integrated
i950-C4/400-3 i950-C4/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 4 kW/5 HP
  • Output current 9.5/8.2 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C5.5/230-3 i950-C5.5/230-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 5.5 kW/7.5 HP
  • Output current 23 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 230/240 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter not integrated
i950-C7.5/400-3 i950-C7.5/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 7.5 kW/10 HP
  • Output current 16.5/14 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C11/400-3 i950-C11/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 11 kW/15 HP
  • Output current 23.5/21 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C15/400-3 i950-C15/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 15 kW/20 HP
  • Output current 32/27 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C22/400-3 i950-C22/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 22 kW/30 HP
  • Output current 47/40.4 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C30/400-3 i950-C30/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 30 kW/40 HP
  • Output current 61/52 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C45/400-3 i950-C45/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 45 kW/60 HP
  • Output current 89/77 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C55/400-3 i950-C55/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 55 kW/75 HP
  • Output current 110/96 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C75/400-3 i950-C75/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 75 kW/100 HP
  • Output current 150/124 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C90/400-3 i950-C90/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 90 kW/125 HP
  • Output current 180/156 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C110/400-3 i950-C110/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 110 kW/150 HP
  • Output current 212/180 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
Showing 51–75 of 563
  • Fault message ID
    537526045
    0x2009FF1D Description

    No HIPERFACE® absolute value encoder as load encoder/master encoder connected - command cannot be

    Cause

    An attempt was made to read out HIPERFACE® data although no HIPERFACE® encoder is connected. No HIPERFACE® encoder is selected in 0x2C50.

    Remedy

    Connect HIPERFACE® encoder. A HIPERFACE® encoder must be selected in 0x2C50.

    Severity/response

    Warning

  • Fault message ID
    537526046
    0x2009FF1E Description

    FIQ runtime error

    Cause

    The monitoring of the FIQ by the FPGA has triggered.

    Remedy

    Connect an encoder with a supported type code.

    Severity/response

    Fault

  • Fault message ID
    537526048
    0x2009FF20 Description

    Brand protection - check failed

    Cause

    The review of brand protection has failed.

    Remedy

    Enter correct pin. Replace device with OEM device and reprogram pin.

    Severity/response

    Warning

  • Fault message ID
    537526049
    0x2009FF21 Description

    Time-out holding brake feedforward control

    Cause

    The specified feedforward control torque could not be built up within one second.

    Remedy
    • 0x2820:009 (Starting torque source) = [0] (Last torque saved): - The load to be braked is too large. - Control the stored torque. 40x2820:021
    • 0x2820:009 (Starting torque source) = [1] (Torque in 0x2820:010): - The set torque is too high. - Reduce torque.
    Severity/response

    Fault

  • Fault message ID
    537526050
    0x2009FF22 Description

    Velocity error

    Cause

    The speed error exceeds the limit from 0x2D51:001 for a time duration > 0x2D51:002.

    Remedy

    Increase timeout in 0x2D51:002. Increase limit in 0x2D51:001. Increase gain of the speed controller. Increase torque limit and/or current limit.

    Severity/response

    Fault

  • Fault message ID
    537526051
    0x2009FF23 Description

    Position error

    Cause

    The following error exceeds the limit from 0x2D51:004 for a time duration > 0x2D51:005.

    Remedy

    Increase timeout in 0x2D51:005. Increase limit in 0x2D51:004. Increase gain of the position controller.

    Severity/response

    Fault

  • Fault message ID
    537526054
    0x2009FF26 Description

    Cable check - Motor movement too large

    Cause

    Phases in the motor cable reversed. The axis was moved manually. Motor parameters are set incorrectly. For synchronous motors: The pole position is set incorrectly. For motors with holding brake: The brake was opened prematurely by an external source.

    Remedy

    Check motor cabling. Avoid manual movement. Check number of pole pairs and motor type. Carry out the pole position identification Do not open the brake until you have checked the wiring.

    Severity/response

    Fault

  • Fault message ID
    537526055
    0x2009FF27 Description

    Cable check - Wrong motor angle detected

    Cause

    The determined angle between rotor and resolver differs from the setting in 0x2C03:002. The determined angle between rotor and encoder differs from the setting in 0x2C03:004.

    Remedy

    Check encoder cabling. Check motor cabling. If appropriate, Carry out the pole position identification

    Severity/response

    Fault

  • Fault message ID
    537526062
    0x2009FF2E Description

    Connected motor encoder is not supported

    Severity/response

    Fault

  • Fault message ID
    537526063
    0x2009FF2F Description

    Connected load encoder/master encoder is not supported

    Severity/response

    Fault

  • Fault message ID
    537526076
    0x2009FF3C Description

    Backup created via device command

    Cause

    Backup created via device command

    Remedy

    For information only. No remedy necessary.

    Severity/response

    Information

  • Fault message ID
    537526077
    0x2009FF3D Description

    Backup restored via device command

    Cause

    Backup restored via device command

    Remedy

    For information only. No remedy necessary.

    Severity/response

    Information

  • Fault message ID
    537526080
    0x2009FF40 Description

    Error - Brake transistor

    Cause

    The short-circuit monitoring of the brake transistor has triggered.

    Remedy

    Use brake resistor with a greater resistance value. Use external brake chopper. Use regenerative module.

    Severity/response

    Fault

  • Fault message ID
    537526081
    0x2009FF41 Description

    Error - Charging circuit

    Cause

    The monitoring of the charge relay has responded.

    Remedy

    Acknowledge error. If the error persists, contact the manufacturer.

    Severity/response

    Fault

  • Fault message ID
    537526082
    0x2009FF42 Description

    Mains phase failure

    Cause

    The mains phase monitoring has triggered.

    Remedy

    Check mains connection.

    Severity/response

    Fault

  • Fault message ID
    537526083
    0x2009FF43 Description

    Motor encoder requires restart of the device

    Severity/response

    Fault

  • Fault message ID
    537526084
    0x2009FF44 Description

    Load encoder requires restart of the device

    Severity/response

    Fault

  • Fault message ID
    537526096
    0x2009FF50 Description

    General error (see manual)

    Cause

    An error has been triggered in the technology application, the PLC or in the network, which requires a direct error response from the drive.

    Remedy

    1. Search logbook for the triggering error in the other component. 2. Eliminate the triggering error. The error message can now be acknowledged. If this is not possible, contact the manufacturer.

    Severity/response

    Fault

  • Fault message ID
    537526097
    0x2009FF51 Description

    Internal communication to PLC failed

    Cause

    The internal communication between the application and the base firmware is disturbed.

    Remedy

    Restart device.

    Severity/response

    Fault

  • Fault message ID
    537526110
    0x2009FF5E Description

    Invalid module combination in slot A and slot B

    Cause

    The modules in slot A and slot B cannot be combined.

    Remedy

    Remove a module. Plug a valid module combination.

    Severity/response

    Fault

    • The event can only be reset by mains switching.
  • Fault message ID
    8992
    0x2320 Description
    Short circuit or earth leakage at the motor end
    Keypad display
    Earth leak
    Cause
    • Short circuit/earth fault of motor cable
    • Capacitive charging current of the motor cable too high.
    Remedy
    • Check motor cable.
    • Check length of the motor cable.
    • Use shorter or lower-capacitance motor cable.
    Severity/response

    Fault

    • The inverter is disabled immediately. The motor has no torque (is coasting).
    • The event can only be reset after a blocking time.
  • Fault message ID
    9024
    0x2340 Description
    Short circuit at the motor end
    Keypad display
    Motor shorted
    Cause

    Short circuit of motor cable

    Remedy

    Check motor cable for short circuit.

    Severity/response

    Fault

    • The inverter is disabled immediately. The motor has no torque (is coasting).
    • The event can only be reset after a blocking time.
  • Fault message ID
    9090
    0x2382 Description
    Fault - Device utilization (ixt) too high
    Keypad display
    Ixt error
    Cause

    Device utilisation (ixt) too high by frequent and too long acceleration processes.

    Remedy

    Check drive sizing. 

    • Reduce the maximum current of the inverter 0x6073 (P324.00). 
    • In case of high mass inertias, reduce maximum current of the inverter 0x6073 (P324.00) to 150 %.
    Severity/response

    Fault (configurable)

    • The event can only be reset after a blocking time.
  • Fault message ID
    9091
    0x2383 Description

    Warning - Device utilization (ixt) too high

    Keypad display
    Ixt warning
    Cause

    Device utilisation (ixt) too high by frequent and too long acceleration processes.

    Remedy

    Check drive dimensioning.

    Severity/response

    Warning

  • Fault message ID
    9095
    0x2387 Description

    Clamp responded too often

    Keypad display
    Clamp timeout
    Cause

    Maximum current of the axis (display in 0x2DDF:002) has been reached too often in succession.

    Remedy
    • Select a flatter speed ramp.
    • Reduce the load.
    • Set Imax controller more dynamically.
    Severity/response

    Fault