6AG1334-0KE00-7AB0
SIPLUS S7-300 SM 334 4 AI 2 AO based on 6ES7334-0KE00-0AB0 with conformal coating, -25…+70 °C, analog module isolated, 4 AI/2 AO, 12 bit, 0-10 V for Pt100 (climatic range -120-155 degrees) and 10 kOhm measuring range, 1x 20-pole
Siemens spare part — S7-300 product cancellation (PM410, 1 October 2025); available as a spare part until 2033.
Categorie de produs
Module analogiceProducător
SIEMENSSerie de produse
S7-300| General information | |
|---|---|
| based on | 6ES7334-0KE00-0AB0 |
| Supply voltage | |
| Load voltage L+ | |
| Rated value (DC) | 24 V |
| Reverse polarity protection | Yes |
| Input current | |
| from supply and load voltage L+ (without load), max. | 80 mA |
| from backplane bus 5 V DC, max. | 60 mA |
| Power loss | |
| Power loss, typ. | 2 W |
| Analog inputs | |
| Number of analog inputs | 4 |
| For voltage measurement | 2 |
| For resistance measurement | 4 |
| permissible input voltage for voltage input (destruction limit), max. | 20 V; continuous; 75 V for max. 1 s (mark to space ratio 1:20) |
| Constant measurement current for resistance-type transmitter, typ. | 490 µA; at PT100 (490 µA), at 10 kOhm (105 µa) |
| Cycle time (all channels) max. | 85 ms |
| Input ranges | |
| Voltage | Yes |
| Current | No |
| Thermocouple | No |
| Resistance thermometer | Yes |
| Resistance | Yes |
| Input ranges (rated values), voltages | |
| 0 to +10 V | Yes |
| Input resistance (0 to 10 V) | 100 kΩ |
| Input ranges (rated values), resistance thermometer | |
| Pt 100 | Yes; only climatic range |
| Input ranges (rated values), resistors | |
| 0 to 10000 ohms | Yes |
| Characteristic linearization | |
| Parameterizable | Yes |
| for resistance thermometer | Pt100 (climate) |
| Cable length | |
| shielded, max. | 100 m |
| Analog outputs | |
| Number of analog outputs | 2 |
| Voltage output, short-circuit protection | Yes |
| Voltage output, short-circuit current, max. | 10 mA |
| Output ranges, voltage | |
| 0 to 10 V | Yes |
| Load impedance (in rated range of output) | |
| with voltage outputs, min. | 2.5 kΩ |
| with voltage outputs, capacitive load, max. | 1 µF |
| Cable length | |
| shielded, max. | 100 m |
| Analog value generation for the inputs | |
| Integration and conversion time/resolution per channel | |
| Resolution with overrange (bit including sign), max. | 12 bit |
| Integration time, parameterizable | Yes |
| Integration time (ms) | 16,67 / 20 ms |
| Interference voltage suppression for interference frequency f1 in Hz | 50 / 60 Hz |
| Analog value generation for the outputs | |
| Integration and conversion time/resolution per channel | |
| Resolution with overrange (bit including sign), max. | 12 bit |
| Conversion time (per channel) | 500 µs |
| Settling time | |
| for resistive load | 0.8 ms |
| for capacitive load | 0.8 ms |
| Encoder | |
| Connection of signal encoders | |
| for voltage measurement | Yes |
| for resistance measurement with two-wire connection | Yes |
| for resistance measurement with three-wire connection | Yes |
| for resistance measurement with four-wire connection | Yes |
| Errors/accuracies | |
| Operational error limit in overall temperature range | |
| Voltage, relative to input range, (+/-) | 0.8 %; 0 to 10V |
| Resistance, relative to input range, (+/-) | 3.7 %; 10 kOhm |
| Resistance thermometer, relative to input range, (+/-) | 1.1 % |
| Voltage, relative to output range, (+/-) | 1.1 % |
| Basic error limit (operational limit at 25 °C) | |
| Voltage, relative to input range, (+/-) | 0.5 %; 0 to 10V |
| Resistance, relative to input range, (+/-) | 2.8 %; 10 kOhm |
| Resistance thermometer, relative to input range, (+/-) | 0.8 % |
| Voltage, relative to output range, (+/-) | 0.85 % |
| Interrupts/diagnostics/status information | |
| Alarms | No |
| Diagnostics function | No |
| Potential separation | |
| Potential separation analog inputs | |
| between the channels and backplane bus | Yes |
| Potential separation analog outputs | |
| between the channels | No |
| between the channels and backplane bus | Yes |
| between the channels and the power supply of the electronics | Yes |
| Isolation | |
| Isolation tested with | 500 V DC |
| Standards, approvals, certificates | |
| CE mark | Yes |
| UL approval | Yes; File E239877 |
| RCM (formerly C-TICK) | Yes |
| KC approval | Yes |
| EAC (formerly Gost-R) | Yes |
| Ambient conditions | |
| Ambient temperature during operation | |
| min. | -25 °C; = Tmin |
| max. | 70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use |
| Ambient temperature during storage/transportation | |
| min. | -40 °C |
| max. | 70 °C |
| Altitude during operation relating to sea level | |
| Installation altitude above sea level, max. | 5 000 m |
| Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
| Relative humidity | |
| With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
| Resistance | |
| Use in stationary industrial systems | |
| to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
| to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * |
| Use on ships/at sea | |
| to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request |
| to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
| to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * |
| Usage in industrial process technology | |
| Against chemically active substances acc. to EN 60654-4 | Yes; Class 3 (excluding trichlorethylene) |
| Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) |
| Remark | |
| Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! |
| Connection method | |
| required front connector | 20-pin |
| Dimensions | |
| Width | 40 mm |
| Height | 125 mm |
| Depth | 117 mm |
| Weights | |
| Weight, approx. | 200 g |
| Approvals / Certificates | |