6AG1334-0KE00-7AB0

SIPLUS S7-300 SM 334 4 AI 2 AO based on 6ES7334-0KE00-0AB0 with conformal coating, -25…+70 °C, analog module isolated, 4 AI/2 AO, 12 bit, 0-10 V for Pt100 (climatic range -120-155 degrees) and 10 kOhm measuring range, 1x 20-pole

Siemens spare part — S7-300 product cancellation (PM410, 1 October 2025); available as a spare part until 2033.

Termékkategória
Analóg modulok
Gyártó
SIEMENS
Termékcsalád
S7-300
General information
based on6ES7334-0KE00-0AB0
Supply voltage
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
from supply and load voltage L+ (without load), max.80 mA
from backplane bus 5 V DC, max.60 mA
Power loss
Power loss, typ.2 W
Analog inputs
Number of analog inputs4
For voltage measurement2
For resistance measurement4
permissible input voltage for voltage input (destruction limit), max.20 V; continuous; 75 V for max. 1 s (mark to space ratio 1:20)
Constant measurement current for resistance-type transmitter, typ.490 µA; at PT100 (490 µA), at 10 kOhm (105 µa)
Cycle time (all channels) max.85 ms
Input ranges
VoltageYes
CurrentNo
ThermocoupleNo
Resistance thermometerYes
ResistanceYes
Input ranges (rated values), voltages
0 to +10 VYes
Input resistance (0 to 10 V)100 kΩ
Input ranges (rated values), resistance thermometer
Pt 100Yes; only climatic range
Input ranges (rated values), resistors
0 to 10000 ohmsYes
Characteristic linearization
ParameterizableYes
for resistance thermometerPt100 (climate)
Cable length
shielded, max.100 m
Analog outputs
Number of analog outputs2
Voltage output, short-circuit protectionYes
Voltage output, short-circuit current, max.10 mA
Output ranges, voltage
0 to 10 VYes
Load impedance (in rated range of output)
with voltage outputs, min.2.5 kΩ
with voltage outputs, capacitive load, max.1 µF
Cable length
shielded, max.100 m
Analog value generation for the inputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.12 bit
Integration time, parameterizableYes
Integration time (ms)16,67 / 20 ms
Interference voltage suppression for interference frequency f1 in Hz50 / 60 Hz
Analog value generation for the outputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.12 bit
Conversion time (per channel)500 µs
Settling time
for resistive load0.8 ms
for capacitive load0.8 ms
Encoder
Connection of signal encoders
for voltage measurementYes
for resistance measurement with two-wire connectionYes
for resistance measurement with three-wire connectionYes
for resistance measurement with four-wire connectionYes
Errors/accuracies
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)0.8 %; 0 to 10V
Resistance, relative to input range, (+/-)3.7 %; 10 kOhm
Resistance thermometer, relative to input range, (+/-)1.1 %
Voltage, relative to output range, (+/-)1.1 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.5 %; 0 to 10V
Resistance, relative to input range, (+/-)2.8 %; 10 kOhm
Resistance thermometer, relative to input range, (+/-)0.8 %
Voltage, relative to output range, (+/-)0.85 %
Interrupts/diagnostics/status information
AlarmsNo
Diagnostics functionNo
Potential separation
Potential separation analog inputs
between the channels and backplane busYes
Potential separation analog outputs
between the channelsNo
between the channels and backplane busYes
between the channels and the power supply of the electronicsYes
Isolation
Isolation tested with500 V DC
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Ambient conditions
Ambient temperature during operation
min.-25 °C; = Tmin
max.70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth117 mm
Weights
Weight, approx.200 g