i950
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 3.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 1.8/1.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.75 kW/1 HP
- Output current 2.4/2.1 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 1.5 kW/2 HP
- Output current 7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 9.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 5.6/4.8 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 4 kW/5 HP
- Output current 16.5 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 4 kW/5 HP
- Output current 9.5/8.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 5.5 kW/7.5 HP
- Output current 23 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 7.5 kW/10 HP
- Output current 16.5/14 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 11 kW/15 HP
- Output current 23.5/21 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 15 kW/20 HP
- Output current 32/27 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 22 kW/30 HP
- Output current 47/40.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 30 kW/40 HP
- Output current 61/52 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 45 kW/60 HP
- Output current 89/77 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 55 kW/75 HP
- Output current 110/96 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 75 kW/100 HP
- Output current 150/124 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 90 kW/125 HP
- Output current 180/156 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 110 kW/150 HP
- Output current 212/180 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
-
Fault message ID
805312687 0x300018AF Description
CauseMMC - Address assignment error, more slaves connected than configured
RemedyMMC configuration file is faulty. Network topology is faulty.
Severity/responseAnalyze detailed error message in the logbook. Check MMC configuration file. Check network topology.
Warning
-
Fault message ID
805312688 0x300018B0 Description
CauseMMC - Address assignment error, invalid device
RemedyMMC configuration file is faulty. Network topology is faulty.
Severity/responseAnalyze detailed error message in the logbook. Check MMC configuration file. Check network topology.
Warning
-
Fault message ID
805312689 0x300018B1 Description
CauseMMC - Address assignment successful
RemedyMMC - Address assignment successful
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805312690 0x300018B2 Description
CauseMMC - Address assignment failed
RemedyMMC configuration file is faulty. Network topology is faulty.
Severity/responseAnalyze detailed error message in the logbook. Check MMC configuration file. Check network topology.
Warning
-
Fault message ID
805312691 0x300018B3 Description
CauseMMC - Address assignment done
RemedyMMC - Address assignment done
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805312692 0x300018B4 Description
CauseMMC - Address assignment error, writing address by CoE
RemedyMMC - Address assignment error, writing address by CoE
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805312693 0x300018B5 Description
CauseMMC - Slave identification error
RemedyMMC configuration file is faulty. Network topology is faulty.
Severity/responseAnalyze detailed error message in the logbook. Check MMC configuration file. Check network topology.
Warning
-
Fault message ID
805312694 0x300018B6 Description
CauseMMC - Slave identification error, slave ident data failed
RemedyMMC configuration file is faulty. Network topology is faulty.
Severity/responseAnalyze detailed error message in the logbook. Check MMC configuration file. Check network topology.
Warning
-
Fault message ID
805312695 0x300018B7 Description
CauseMMC - Service state cannot be changed, set bus to 'INIT' first
RemedyService request rejected because master not in "Init" status
Severity/responseCheck status of the master. Set status of the master to "Init".
Warning
-
Fault message ID
805312768 0x30001900 Description
Severity/responseCoE - Emergency request
Information
-
Fault message ID
805312867 0x30001963 Description
Severity/responseLast ETC message
Warning
-
Fault message ID
805405056 0x30018180 Description
CauseEtherCAT - DC synchronization required
RemedyEtherCAT Distributed Clock (DC) not activated.
Severity/responseActivate DC mode.
Warning
-
Fault message ID
805405057 0x30018181 Description
CauseEtherCAT - Communication error
RemedyEtherCAT communication interrupted.
Severity/response- Check bus cable.
- Increase watchdog time.
Fault > CiA402 (configurable)
Setting parameters: 0x285B:001
-
Fault message ID
805405312 0x30018280 Description
CauseEtherCAT - Wrong sync manager address
RemedyWrong Sync Manager setting from EtherCAT master
Severity/response- Check node.
- Check the sequence of the nodes.
- Check bus cable.
Fault
-
Fault message ID
805405313 0x30018281 Description
CauseEtherCAT - Wrong sync manager size
RemedyWrong Sync Manager setting from EtherCAT master
Severity/response- Check node.
- Check the sequence of the nodes.
- Check bus cable.
Fault
-
Fault message ID
805405314 0x30018282 Description
CauseEtherCAT - Wrong sync manager settings
RemedyWrong Sync Manager setting from EtherCAT master
Severity/response- Check node.
- Check the sequence of the nodes.
- Check bus cable.
Fault
-
Fault message ID
805405315 0x30018283 Description
CausePDO mapping: Unknown object
RemedyUnknown index in the PDO mapping
Severity/responseCorrect PDO mapping.
Fault
-
Fault message ID
805405316 0x30018284 Description
CauseNo PDO mapping object
RemedyThe index cannot be mapped as PDO.
Severity/responseCorrect PDO mapping.
Fault
-
Fault message ID
805405317 0x30018285 Description
CauseToo many objects mapped
RemedyMore than 64 objects are mapped.
Severity/responseReduce number of objects in PDO mapping.
Fault
-
Fault message ID
805405320 0x30018288 Description
CausePDO mapping object is already used by PLC.
RemedyThe object to be mapped is already used by the PLC.
Severity/responseRemove object from mapping.
Fault
-
Fault message ID
805406464 0x30018700 Description
CauseEtherCAT - Sync error
Remedy- EtherCAT Sync0 has failed.
- PDO was sent or received too late.
Severity/response- Check in the EtherCAT master configuration whether Distributed Clock is activated.
- Restart EtherCAT configuration.
- Shift PDO reception time via user shift time.
- Increase telegram failure error counter: 40x10F1:002
Fault
-
Fault message ID
805406465 0x30018701 Description
CauseSync PLL - Time-out
RemedyError during state change Pre- Operational → Safe-Operational:
- EtherCAT Sync0 has failed.
- The Sync0 jitter is too high.
Severity/response- Check DC deviation in EtherCAT master.
- Restart EtherCAT configuration.
Fault
-
Fault message ID
805437220 0x3001FF24 Description
CauseInvalid Sync0 cycle time
RemedyThe requested Sync0 cycle is outside the supported limits.
Severity/responseCorrect Sync0 cycle.
Fault
-
Fault message ID
805437270 0x3001FF56 Description
CauseCheck OUT-port of EtherCAT master
RemedyThe Ethernet connector is plugged into the IN port.
Severity/responseCorrect wiring.
(configurable)
Setting parameters:
-
Fault message ID
805437271 0x3001FF57 Description
CauseCheck IN-port of EtherCAT slave
RemedyThe Ethernet connector is plugged into the OUT port.
Severity/responseCorrect wiring.
(configurable)
Setting parameters:
-
0x2B02:009
Parameter
Frequency grid points (x) user V/f characteristic: x9 = f09 Data type
I16 Default setting
30 Hz Attributes
- -
0x2B02:010
Parameter
Frequency grid points (x) user V/f characteristic: x10 = f10 Data type
I16 Default setting
40 Hz Attributes
- -
0x2B02:011
Parameter
Frequency grid points (x) user V/f characteristic: x11 = f11 Data type
I16 Default setting
50 Hz Attributes
- -
0x2B03:001
Parameter
Voltage grid points (y) user V/f characteristic: y1 = U01 (x = f01) Data type
U32 Default setting
400.00 V Attributes
- -
0x2B03:002
Parameter
Voltage grid points (y) user V/f characteristic: y2 = U02 (x = f02) Data type
U32 Default setting
320.00 V Attributes
- -
0x2B03:003
Parameter
Voltage grid points (y) user V/f characteristic: y3 = U03 (x = f03) Data type
U32 Default setting
240.00 V Attributes
- -
0x2B03:004
Parameter
Voltage grid points (y) user V/f characteristic: y4 = U04 (x = f04) Data type
U32 Default setting
160.00 V Attributes
- -
0x2B03:005
Parameter
Voltage grid points (y) user V/f characteristic: y5 = U05 (x = f05) Data type
U32 Default setting
80.00 V Attributes
- -
0x2B03:006
Parameter
Voltage grid points (y) user V/f characteristic: y6 = U06 (x = f06) Data type
U32 Default setting
0.00 V Attributes
- -
0x2B03:007
Parameter
Voltage grid points (y) user V/f characteristic: y7 = U07 (x = f07) Data type
U32 Default setting
80.00 V Attributes
- -
0x2B03:008
Parameter
Voltage grid points (y) user V/f characteristic: y8 = U08 (x = f08) Data type
U32 Default setting
160.00 V Attributes
- -
0x2B03:009
Parameter
Voltage grid points (y) user V/f characteristic: y9 = U09 (x = f09) Data type
U32 Default setting
240.00 V Attributes
- -
0x2B03:010
Parameter
Voltage grid points (y) user V/f characteristic: y10 = U10 (x = f10) Data type
U32 Default setting
320.00 V Attributes
- -
0x2B03:011
Parameter
Voltage grid points (y) user V/f characteristic: y11 = U11 (x = f11) Data type
U32 Default setting
400.00 V Attributes
- -
0x2B04
Parameter
V/f boost controller - current setpoint Data type
U32 Default setting
0.00 A Attributes
- -
0x2B05:001
Parameter
V/f boost controller settings: Gain Data type
U32 Default setting
148.21 V/A Attributes
- -
0x2B05:002
Parameter
V/f boost controller settings: Reset time Data type
U32 Default setting
3.77 ms Attributes
- -
0x2B05:003
Parameter
V/f boost controller settings: Dynamic current setpoint Data type
U32 Default setting
0.00 A Attributes
- -
0x2B06
Parameter
Voltage boost Data type
U16 Default setting
0.0 V Attributes
- -
0x2B07:001
Parameter
Load adaption: Direction of rotation Data type
U8 Default setting
Passive load [0] Attributes
C -
0x2B07:002
Parameter
Load adaption: Load adaption value Data type
U32 Default setting
20.00 % Attributes
- -
0x2B08:001
Parameter
V/f Imax controller: Gain Data type
U32 Default setting
0.001 Hz/A Attributes
- -
0x2B08:002
Parameter
V/f Imax controller: Reset time Data type
U32 Default setting
100.0 ms Attributes
- -
0x2B09:001
Parameter
Slip compensation: Gain Data type
I16 Default setting
0.00 % Attributes
- -
0x2B09:002
Parameter
Slip compensation: Filter time Data type
U16 Default setting
2000 ms Attributes
-