i950

i950-C0.37/230-2 i950-C0.37/230-2 Description
Lenze logo Order code / SKU
On request
  • Rated power 0.37 kW/0.5 HP
  • Output current 2.4 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 1/N(3)/PE 230/240 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter not integrated
i950-C0.55/230-2 i950-C0.55/230-2 Description
Lenze logo Order code / SKU
On request
  • Rated power 0.55 kW/0.75 HP
  • Output current 3.2 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 1/N(3)/PE 230/240 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter not integrated
i950-C0.55/400-3 i950-C0.55/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 0.55 kW/0.75 HP
  • Output current 1.8/1.6 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C0.75/230-2 i950-C0.75/230-2 Description
Lenze logo Order code / SKU
On request
  • Rated power 0.75 kW/1 HP
  • Output current 4.2 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 1/N(3)/PE 230/240 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter not integrated
i950-C0.75/400-3 i950-C0.75/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 0.75 kW/1 HP
  • Output current 2.4/2.1 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C1.5/230-2 i950-C1.5/230-2 Description
Lenze logo Order code / SKU
On request
  • Rated power 1.5 kW/2 HP
  • Output current 7 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 1/N(3)/PE 230/240 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter not integrated
i950-C2.2/230-3 i950-C2.2/230-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 2.2 kW/3 HP
  • Output current 9.6 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 230/240 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter not integrated
i950-C2.2/400-3 i950-C2.2/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 2.2 kW/3 HP
  • Output current 5.6/4.8 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C4/230-3 i950-C4/230-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 4 kW/5 HP
  • Output current 16.5 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 230/240 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter not integrated
i950-C4/400-3 i950-C4/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 4 kW/5 HP
  • Output current 9.5/8.2 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C5.5/230-3 i950-C5.5/230-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 5.5 kW/7.5 HP
  • Output current 23 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 230/240 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter not integrated
i950-C7.5/400-3 i950-C7.5/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 7.5 kW/10 HP
  • Output current 16.5/14 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C11/400-3 i950-C11/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 11 kW/15 HP
  • Output current 23.5/21 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C15/400-3 i950-C15/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 15 kW/20 HP
  • Output current 32/27 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C22/400-3 i950-C22/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 22 kW/30 HP
  • Output current 47/40.4 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C30/400-3 i950-C30/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 30 kW/40 HP
  • Output current 61/52 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C45/400-3 i950-C45/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 45 kW/60 HP
  • Output current 89/77 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C55/400-3 i950-C55/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 55 kW/75 HP
  • Output current 110/96 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C75/400-3 i950-C75/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 75 kW/100 HP
  • Output current 150/124 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C90/400-3 i950-C90/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 90 kW/125 HP
  • Output current 180/156 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
i950-C110/400-3 i950-C110/400-3 Description
Lenze logo Order code / SKU
On request
  • Rated power 110 kW/150 HP
  • Output current 212/180 A
  • Output frequency 0-599 Hz
  • Rated mains voltage 3/PE 400/480 V AC
  • Motor output Single axis
  • Generation B
  • Product series i950 cabinet
  • EMC filter Integrated
Showing 501–525 of 563
  • Fault message ID
    805312687
    0x300018AF Description

    MMC - Address assignment error, more slaves connected than configured

    Cause

    MMC configuration file is faulty. Network topology is faulty.

    Remedy

    Analyze detailed error message in the logbook. Check MMC configuration file. Check network topology.

    Severity/response

    Warning

  • Fault message ID
    805312688
    0x300018B0 Description

    MMC - Address assignment error, invalid device

    Cause

    MMC configuration file is faulty. Network topology is faulty.

    Remedy

    Analyze detailed error message in the logbook. Check MMC configuration file. Check network topology.

    Severity/response

    Warning

  • Fault message ID
    805312689
    0x300018B1 Description

    MMC - Address assignment successful

    Cause

    MMC - Address assignment successful

    Remedy

    For information only. No remedy necessary.

    Severity/response

    Warning

  • Fault message ID
    805312690
    0x300018B2 Description

    MMC - Address assignment failed

    Cause

    MMC configuration file is faulty. Network topology is faulty.

    Remedy

    Analyze detailed error message in the logbook. Check MMC configuration file. Check network topology.

    Severity/response

    Warning

  • Fault message ID
    805312691
    0x300018B3 Description

    MMC - Address assignment done

    Cause

    MMC - Address assignment done

    Remedy

    For information only. No remedy necessary.

    Severity/response

    Warning

  • Fault message ID
    805312692
    0x300018B4 Description

    MMC - Address assignment error, writing address by CoE

    Cause

    MMC - Address assignment error, writing address by CoE

    Remedy

    For information only. No remedy necessary.

    Severity/response

    Warning

  • Fault message ID
    805312693
    0x300018B5 Description

    MMC - Slave identification error

    Cause

    MMC configuration file is faulty. Network topology is faulty.

    Remedy

    Analyze detailed error message in the logbook. Check MMC configuration file. Check network topology.

    Severity/response

    Warning

  • Fault message ID
    805312694
    0x300018B6 Description

    MMC - Slave identification error, slave ident data failed

    Cause

    MMC configuration file is faulty. Network topology is faulty.

    Remedy

    Analyze detailed error message in the logbook. Check MMC configuration file. Check network topology.

    Severity/response

    Warning

  • Fault message ID
    805312695
    0x300018B7 Description

    MMC - Service state cannot be changed, set bus to 'INIT' first

    Cause

    Service request rejected because master not in "Init" status

    Remedy

    Check status of the master. Set status of the master to "Init".

    Severity/response

    Warning

  • Fault message ID
    805312768
    0x30001900 Description

    CoE - Emergency request

    Severity/response

    Information

  • Fault message ID
    805312867
    0x30001963 Description

    Last ETC message

    Severity/response

    Warning

  • Fault message ID
    805405056
    0x30018180 Description

    EtherCAT - DC synchronization required

    Cause

    EtherCAT Distributed Clock (DC) not activated.

    Remedy

    Activate DC mode.

    Severity/response

    Warning

  • Fault message ID
    805405057
    0x30018181 Description

    EtherCAT - Communication error

    Cause

    EtherCAT communication interrupted.

    Remedy
    • Check bus cable.
    • Increase watchdog time.
    Severity/response

    Fault > CiA402 (configurable)

    Setting parameters: 0x285B:001

  • Fault message ID
    805405312
    0x30018280 Description

    EtherCAT - Wrong sync manager address

    Cause

    Wrong Sync Manager setting from EtherCAT master

    Remedy
    • Check node.
    • Check the sequence of the nodes.
    • Check bus cable.
    Severity/response

    Fault

  • Fault message ID
    805405313
    0x30018281 Description

    EtherCAT - Wrong sync manager size

    Cause

    Wrong Sync Manager setting from EtherCAT master

    Remedy
    • Check node.
    • Check the sequence of the nodes.
    • Check bus cable.
    Severity/response

    Fault

  • Fault message ID
    805405314
    0x30018282 Description

    EtherCAT - Wrong sync manager settings

    Cause

    Wrong Sync Manager setting from EtherCAT master

    Remedy
    • Check node.
    • Check the sequence of the nodes.
    • Check bus cable.
    Severity/response

    Fault

  • Fault message ID
    805405315
    0x30018283 Description

    PDO mapping: Unknown object

    Cause

    Unknown index in the PDO mapping

    Remedy

    Correct PDO mapping.

    Severity/response

    Fault

  • Fault message ID
    805405316
    0x30018284 Description

    No PDO mapping object

    Cause

    The index cannot be mapped as PDO.

    Remedy

    Correct PDO mapping.

    Severity/response

    Fault

  • Fault message ID
    805405317
    0x30018285 Description

    Too many objects mapped

    Cause

    More than 64 objects are mapped.

    Remedy

    Reduce number of objects in PDO mapping.

    Severity/response

    Fault

  • Fault message ID
    805405320
    0x30018288 Description

    PDO mapping object is already used by PLC.

    Cause

    The object to be mapped is already used by the PLC.

    Remedy

    Remove object from mapping.

    Severity/response

    Fault

  • Fault message ID
    805406464
    0x30018700 Description

    EtherCAT - Sync error

    Cause
    • EtherCAT Sync0 has failed.
    • PDO was sent or received too late.
    Remedy
    • Check in the EtherCAT master configuration whether Distributed Clock is activated.
    • Restart EtherCAT configuration.
    • Shift PDO reception time via user shift time.
    • Increase telegram failure error counter: 40x10F1:002
    Severity/response

    Fault

  • Fault message ID
    805406465
    0x30018701 Description

    Sync PLL - Time-out

    Cause

    Error during state change Pre- Operational → Safe-Operational:

    • EtherCAT Sync0 has failed.
    • The Sync0 jitter is too high.
    Remedy
    • Check DC deviation in EtherCAT master.
    • Restart EtherCAT configuration.
    Severity/response

    Fault

  • Fault message ID
    805437220
    0x3001FF24 Description

    Invalid Sync0 cycle time

    Cause

    The requested Sync0 cycle is outside the supported limits.

    Remedy

    Correct Sync0 cycle.

    Severity/response

    Fault

  • Fault message ID
    805437270
    0x3001FF56 Description

    Check OUT-port of EtherCAT master

    Cause

    The Ethernet connector is plugged into the IN port.

    Remedy

    Correct wiring.

    Severity/response

    (configurable)

    Setting parameters:

  • Fault message ID
    805437271
    0x3001FF57 Description

    Check IN-port of EtherCAT slave

    Cause

    The Ethernet connector is plugged into the OUT port.

    Remedy

    Correct wiring.

    Severity/response

    (configurable)

    Setting parameters: