i550
- Rated power 3 kW/4 HP
- Rated power LD 4 kW/5 HP
- Output current 7.3/6.3 A
- Output current LD 8.8/7.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 4 kW/5 HP
- Rated power LD 5.5 kW/7.5 HP
- Output current 16.5 A
- Output current LD 20.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 4 kW/5 HP
- Rated power LD 5.5 kW/7.5 HP
- Output current 9.5/8.2 A
- Output current LD 11.9/9.8 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 5.5 kW/7.5 HP
- Rated power LD 7.5 kW/10 HP
- Output current 23 A
- Output current LD 27.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 5.5 kW/7.5 HP
- Rated power LD 7.5 kW/10 HP
- Output current 13/11 A
- Output current LD 15.6/13.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 7.5 kW/10 HP
- Rated power LD 11 kW/15 HP
- Output current 16.5/14 A
- Output current LD 23/18.3 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 11 kW/15 HP
- Rated power LD 15 kW/20 HP
- Output current 23.5/21 A
- Output current LD 28.2/25.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 15 kW/20 HP
- Rated power LD 18.5 kW/25 HP
- Output current 32/27 A
- Output current LD 38.4/32.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 18.5 kW/25 HP
- Rated power LD 22 kW/30 HP
- Output current 40/34 A
- Output current LD 48/40.8 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 22 kW/30 HP
- Rated power LD 30 kW/40 HP
- Output current 47/40.4 A
- Output current LD 56.4/48.5 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 30 kW/40 HP
- Rated power LD 37 kW/50 HP
- Output current 61/52 A
- Output current LD 73.2/62.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 37 kW/50 HP
- Rated power LD 45 kW/60 HP
- Output current 76/65 A
- Output current LD 91.2/78 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 45 kW/60 HP
- Rated power LD 55 kW/75 HP
- Output current 89/77 A
- Output current LD 107/92.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 55 kW/75 HP
- Rated power LD 75 kW/100 HP
- Output current 110/96 A
- Output current LD 132/115 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 75 kW/100 HP
- Rated power LD 90 kW/120 HP
- Output current 150/124 A
- Output current LD 180/149 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 90 kW/125 HP
- Rated power LD 110 kW/150 HP
- Output current 180/156 A
- Output current LD 216/187 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 110 kW/150 HP
- Rated power LD 132 kW/175 HP
- Output current 212/180 A
- Output current LD 254/216 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
-
Fault message ID
0011 0x0011 Description
Short circuit of motor cableKeypad display
OC1 Cause
RemedyShort circuit
Excessive capacitive charging
current in the motor cable.
- Search for cause of short circuit.
Check motor cable.
Use motor cable which is shorter
or of lower capacitance.
-
Fault message ID
0012 0x0012 Description
Motor cable earth faultKeypad display
OC2 Cause
RemedyOne of the motor phases has
earth contact.
- Search for cause of short circuit.
- Check motor cable.
-
Fault message ID
0015 0x0015 Description
I x t overloadKeypad display
OC5 Cause
Remedy- Frequent and too long acceleration with overcurrent
- Continuous overload with Imotor > 1.05 x Irx
Check drive dimensioning.
-
Fault message ID
0016 0x0016 Description
Keypad displayI2xt overload
OC6 Cause
Remedy- Frequent and too long acceleration processes with motor overcurrent.
- Permanent motor overload with Imotor >Irmotor
Check drive dimensioning.
-
Fault message ID
x018 0x0018 Description
Keypad displayI2xt overload advance warning
OC8 Cause
Remedy- Frequent and too long acceleration processes with motor overcurrent.
- Permanent motor overload with Imotor >Irmotor
Check drive dimensioning.
-
Fault message ID
1020 0x1020 Description
Keypad displayOvervoltage in DC bus
OU Cause
RemedyBraking energy is too high. (DC−bus voltage is higher than set in C0173.)
- Use braking unit or regenerative module.
- Check dimensioning of the brake resistance.
-
Fault message ID
1030 0x1030 Description
Keypad displayUndervoltage in the DC bus
LU Cause
RemedyDC bus voltage is lower than specified in C0173.
Severity/response- Check mains voltage
- Check supply cable
cawc
-
Fault message ID
8784 0x2250 Description
CiA: Continuous over current (internal)Keypad display
PU over current Cause
Remedy- Continuous overcurrent on the inverter/ motor side.
- Overcurrent at the brake chopper (brake transistor).
- DC bus relay has not been closed due to a malfunction.
Severity/response- Check motor and wiring for short circuits.
- Check brake resistor and wiring.
- Check motor switching.
- Check settings of the motor data.
Fault
- The inverter is disabled immediately. The motor has no torque (is coasting).
- The event can only be reset after a blocking time.
-
Fault message ID
8992 0x2320 Description
Short circuit or earth leakage at the motor endKeypad display
Earth leak Cause
Remedy- Short circuit/earth fault of motor cable
- Capacitive charging current of the motor cable too high.
Severity/response- Check motor cable.
- Check length of the motor cable.
- Use shorter or lower-capacitance motor cable.
Fault
- The inverter is disabled immediately. The motor has no torque (is coasting).
- The event can only be reset after a blocking time.
-
Fault message ID
9024 0x2340 Description
Short circuit at the motor endKeypad display
Motor shorted Cause
RemedyShort circuit of motor cable
Severity/responseCheck motor cable for short circuit.
Fault
- The inverter is disabled immediately. The motor has no torque (is coasting).
- The event can only be reset after a blocking time.
-
Fault message ID
9040 0x2350 Description
CiA: i²xt overload (thermal state)Keypad display
i2t motor Cause
RemedyMotor thermally overloaded, e. g. by an impermissible continuous current or by frequent or too long acceleration processes.
Severity/responseCheck drive sizing.
- Check machine/driven mechanics for excessive load.
- Check settings of the motor data.
- Reduce values for slip compensation 0x2B09:001 (P315.01), 0x2B09:002 (P315.02) and oscillation damping 0x2B0A:001 (P318.01), 0x2B0A:002 (P318.02).
Fault (configurable)
- The event can only be reset after a blocking time.
-
Fault message ID
9090 0x2382 Description
Fault - Device utilization (ixt) too highKeypad display
Ixt error Cause
RemedyDevice utilisation (ixt) too high by frequent and too long acceleration processes.
Severity/responseCheck drive sizing.
- Reduce the maximum current of the inverter 0x6073 (P324.00).
- In case of high mass inertias, reduce maximum current of the inverter 0x6073 (P324.00) to 150 %.
Fault (configurable)
- The event can only be reset after a blocking time.
-
Fault message ID
9091 0x2383 Description
Keypad displayWarning - Device utilization (ixt) too high
Ixt warning Cause
RemedyDevice utilisation (ixt) too high by frequent and too long acceleration processes.
Severity/responseCheck drive dimensioning.
Warning
-
Fault message ID
9095 0x2387 Description
Keypad displayClamp responded too often
Clamp timeout Cause
RemedyMaximum current of the axis (display in 0x2DDF:002) has been reached too often in succession.
Severity/response- Select a flatter speed ramp.
- Reduce the load.
- Set Imax controller more dynamically.
Fault
-
Fault message ID
9096 0x2388 Description
Keypad displaySL-PSM stall detection active
SL-PSM stall det. Cause
RemedyOverload of the motor with sensorless control for synchronous motors (SL-PSM).
Severity/response- Reduce load at the axis.
- Check settings of the SL-PSM parameters.
Trouble
- The inverter is disabled immediately. The motor has no torque (is coasting).
-
Fault message ID
9098 0x238A Description
Keypad displayMaximum current reached
Imax reached Cause
RemedyThe actual current0x6078 (P103.00) is equal to or higher than the max. current 0x6073 (P324.00).
Severity/response- Reduce the load on the motor or change the settings for the maximum current. 0x6073 (P324.00)
Information
-
Fault message ID
12576 0x3120 Description
Keypad displayMains phase fault
Mains Phase fail Cause
RemedyMains phase failure
Severity/response- Check wiring of the mains connection.
- Check fuses.
Fault
-
Fault message ID
12672 0x3180 Description
Keypad displayUPS operation active
UPS oper. active Cause
RemedyOperation on uninterrupted 1x230V current supply (UPS) has been activated: Only a reduced output current is provided.
Severity/responseSwitch back to operation with regular mains voltage
Warning
-
Fault message ID
12816 0x3210 Description
Keypad displayFault - DC bus overvoltage
DC Bus OV Cause
RemedyDC-bus voltage has exceeded the error threshold for overvoltage due to a too high braking energy or a too high mains voltage. The error threshold (display in 0x2540:006 (P208.06) results from the setting of the rated mains voltage in 0x2540:001 (P208.01).
Severity/responseReduce dynamic performance of the load profile.
Check mains voltage.
Check settings for brake energy
management.0x2541:001 (P706.01) = [0]: Connect brake resistor to the power unit and activate the integrated brake chopper
Fault
-
Fault message ID
12817 0x3211 Description
Keypad displayDC bus overvoltage warning
Warn.DC Bus OV Cause
RemedyDC-bus voltage has exceeded the warning threshold for overvoltage set in 0x2540:005 (P208.05) due to a too high braking energy or a too high mains voltage.
Severity/response- Reduce dynamic performance of the load profile.
- Check mains voltage.
- Check settings for brake energy management.
- 0x2541:001 (P706.01) = [0]: Connect brake resistor to the power unit and activate the integrated brake chopper.
Warning
-
Fault message ID
12832 0x3220 Description
Keypad displayFault - DC bus undervoltage
DC Bus UV Cause
RemedyDC-bus voltage has fallen below the error threshold for undervoltage. The error threshold (display in 0x2540:003 (P208.03)) results from the setting of the rated mains voltage in 0x2540:001 (P208.01).
Severity/response- Check mains voltage.
- 0x2D87 (P105.00)Check DC-bus voltage.
- Check mains settings.
- Check fuses.
Trouble
-
Fault message ID
12833 0x3221 Description
Keypad displayDC bus undervoltage warning
Warn.DC Bus UV Cause
RemedyDC-bus voltage has fallen below the warning threshold for undervoltage set in 0x2540:002 (P208.02).
Severity/response- Check mains voltage.
- 0x2D87 (P105.00) Check DC-bus voltage.
- Check mains settings.
- Check fuses.
Warning
-
Fault message ID
12834 0x3222 Description
Keypad displayDC-bus voltage to low for power up
DC-bus on-UV Cause
RemedyThe input voltage is too low to switch on the inverter.
Severity/response- Check mains voltage.
- Check mains settings.
- Check fuses.
Warning
-
Fault message ID
16912 0x4210 Description
Keypad displayFault - Power unit overtemperature
PU Overtemp. Cause
RemedyThe heatsink temperature of the power unit (display in 0x2D84:001 (P117.01)) has exceeded the fixed error threshold (100 °C).
- Ambient temperature too high.
- Fan or ventilation slots are polluted.
- Fan is defective.
Severity/response- Check mains voltage.
- Provide for a sufficient cooling of the device. In case of a 100 % load, 60 C to +70°C are normal. Display of the heatsink temperature in 0x2D84:001 (P117.01).
- Clean fan and ventilation slots. If required, replace fan.
- Reduce switching frequency 0x2939 (P305.00)
Fault
-
Fault message ID
17024 0x4280 Description
Keypad displayFault - Heat sink temperature sensor
Heatsink sensor Cause
RemedySensor for the temperature monitoring of the power unit is defective. The failure of the temperature monitoring function poses the risk of overheating!
Severity/responseHardware error: it is necessary to contact the manufacturer, since the device must be replaced.
Fault
-
0x1F93:002
Parameter
NMT_EPLNodeID_REC: NodeIDByHW_BOOL Data type
U8 Default setting
- (Read only) Fieldbus
POWERLINK -
0x1F98:001
Parameter
NMT_CycleTiming_REC: IsochrTxMaxPayload_ U16 Data type
U16 Default setting
- (Read only) Fieldbus
POWERLINK -
0x1F98:002
Parameter
NMT_CycleTiming_REC: IsochrRxMaxPayload_ U16 Data type
U16 Default setting
- (Read only) Fieldbus
POWERLINK -
0x1F98:003
Parameter
NMT_CycleTiming_REC: PResMaxLatency_U32 Data type
U32 Default setting
x ns (Read only) Fieldbus
POWERLINK -
0x1F98:004
Parameter
NMT_CycleTiming_REC: PReqActPayload_U16 Data type
U16 Default setting
36 Fieldbus
POWERLINK -
0x1F98:005
Parameter
NMT_CycleTiming_REC: PResActPayload_U16 Data type
U16 Default setting
36 Fieldbus
POWERLINK -
0x1F98:006
Parameter
NMT_CycleTiming_REC: ASndMaxLatency_U32 Data type
U32 Default setting
x ns (Read only) Fieldbus
POWERLINK -
0x1F98:007
Parameter
NMT_CycleTiming_REC: MultipleCycleCnt_U8 Data type
U8 Default setting
0 Fieldbus
POWERLINK -
0x1F98:008
Parameter
NMT_CycleTiming_REC: AsyncMTUSize_U16 Data type
U16 Default setting
300 Fieldbus
POWERLINK -
0x1F98:009
Parameter
NMT_CycleTiming_REC: Prescaler_U16 Data type
U16 Default setting
2 Fieldbus
POWERLINK -
0x1F99
Parameter
NMT_CNBasicEthernetTimeout_u32 Data type
U32 Default setting
0 Fieldbus
POWERLINK -
0x1F9A
Parameter
NMT_HostName_VSTR Data type
STRING[32] Fieldbus
POWERLINK -
0x1F9B:001 ... 0x1F9B:100
Parameter
NMT_MultiplCycleAssign_AU8: NMT_MultiplCycleAssign_AU8 1 ... NMT_MultiplCycleAssign_AU8 100 Data type
U8 Default setting
- (Read only) Fieldbus
POWERLINK -
0x1F9E
Parameter
NMT_ResetCmd_U8 Data type
U8 Default setting
- (Read only) Fieldbus
POWERLINK -
0x2000:001
Parameter
Device data: Product code Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2000:002
Parameter
Device data: Serial number Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2000:004
Parameter
Device data: CU firmware version Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2000:005
Parameter
Device data: CU firmware type Data type
STRING[50] Display Code
P190.05 Default setting
- (Read only) Fieldbus
general -
0x2000:006
Parameter
Device data: CU bootloader version Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2000:007
Parameter
Device data: CU bootloader type Data type
STRING[50] Display Code
P190.07 Default setting
- (Read only) Fieldbus
general -
0x2000:008
Parameter
Device data: Object directory version Data type
U32 Default setting
- (Read only) Attributes
- -
0x2000:010
Parameter
Device data: PU firmware version Data type
STRING[50] Display Code
P190.10 Default setting
- (Read only) Fieldbus
general -
0x2000:011
Parameter
Device data: PU firmware type Data type
STRING[50] Display Code
P190.11 Default setting
- (Read only) Fieldbus
general -
0x2000:012