i550
- Rated power 0.25 kW/0.33 HP
- Output current 1.7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 120 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.25 kW/0.33 HP
- Output current 1.7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 0.25 kW/0.33 HP
- Output current 1.7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 120 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.37 kW/0.5 HP
- Output current 1.3/1.1 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 0.55 kW/0.75 HP
- Output current 3.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 0.55 kW/0.75 HP
- Output current 3.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 1.8/1.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 120 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.75 kW/1 HP
- Output current 2.4/2.1 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 1.1 kW/1.5 HP
- Output current 6 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 120 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 1.1 kW/1.5 HP
- Output current 6 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 1.1 kW/1.5 HP
- Output current 6 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 1.1 kW/1.5 HP
- Output current 3.2/3 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 1.5 kW/2 HP
- Output current 7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 1.5 kW/2 HP
- Output current 7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 1.5 kW/2 HP
- Output current 3.9/3.5 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 2.2 kW/3 HP
- Output current 9.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 2.2 kW/3 HP
- Output current 9.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 5.6/4.8 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
-
Fault message ID
65289 0xFF09 Description
Keypad displayMotor phase missing
Mot.Phase miss. Cause
RemedyA failure of several motor phases has been detected.
Severity/response- Check wiring between inverter and motor.
- In case of a false tripping, adapt the settings for the motor phase failure detection.
No response (configurable)
- The event can only be reset after a blocking time. Setting parameters: 0x2D45:001 (P310.01)
-
Fault message ID
65290 0xFF0A Description
Keypad displayMotor phase failure phase U
Phase U failure Cause
RemedyA failure of the motor phase U has been detected.
Severity/response- Check wiring between inverter and motor.
- In case of a false tripping, adapt the settings for the motor phase failure detection. - 0x2D45:002 (P310.02) (Current threshold) - 0x2D45:003 (P310.03) (Voltage threshold)
No response (configurable)
- The event can only be reset after a blocking time. Setting parameters: 0x2D45:001 (P310.01)
-
Fault message ID
65291 0xFF0B Description
Keypad displayMotor phase failure phase V
Phase V failure Cause
RemedyA failure of the motor phase V has been detected.
Severity/response- Check wiring between inverter and motor.
- In case of a false tripping, adapt the settings for the motor phase failure detection. - 0x2D45:002 (P310.02) (Current threshold) - 0x2D45:003 (P310.03) (Voltage threshold)
No response (configurable)
- The event can only be reset after a blocking time. Setting parameters: 0x2D45:001 (P310.01)
-
Fault message ID
65292 0xFF0C Description
Keypad displayMotor phase failure phase W
Phase W failure Cause
RemedyA failure of the motor phase W has been detected.
Severity/response- Check wiring between inverter and motor.
- In case of a false tripping, adapt the settings for the motor phase failure detection. - 0x2D45:002 (P310.02) (Current threshold) - 0x2D45:003 (P310.03) (Voltage threshold)
No response (configurable)
- The event can only be reset after a blocking time. Setting parameters: 0x2D45:001 (P310.01)
-
Fault message ID
65305 0xFF19 Description
Keypad displayMotor parameter identification fault
Motor ID fault Cause
RemedyDuring the automatic identification of the motor, an error has occurred.
Severity/response- Set motor data so that they comply with the data on the motor nameplate.
- Check wiring of the motor.
Fault
-
Fault message ID
65311 0xFF1F Description
Keypad displayFMF Error
FMF Error Cause
RemedyConfiguration or runtime error
Severity/response- Check configuration
- Check FMF error code 0x4050:002 to determine the error cause.
Fault
-
Fault message ID
65317 0xFF25 Description
Keypad displayCascading overload
Cascad. overload Cause
RemedyCascade function for pumps and fans The maximum frequency in 0x2916 (P211.00) has been reached and no free additional pump is available.
Severity/response- Check configuration of the cascade function.
- Check drive sizing.
Warning
-
Fault message ID
65334 0xFF36 Description
Keypad displayWarning - Brake resistor overload
BrkResistor OL.W Cause
RemedyThe calculated thermal load of the brake resistor has reached the warning threshold set in 0x2550:008 (P707.08). The regenerative energy is too high.
Severity/response- Check drive dimensioning.
- Check settings for the brake energy management. Note: The warning status is reset if the thermal load falls below the warning threshold of - 20 %.
Warning (configurable) Setting parameters: 0x2550:010 (P707.10)
-
Fault message ID
65335 0xFF37 Description
Keypad displayAutomatic start disabled
Auto start disab Cause
RemedyAt mains connection, a start command was already available and the automatic start at power-up is set in 0x2838:002 (P203.02) to "Off [0]".
Severity/responseDeactivate starting command and reset error.
Fault
-
Fault message ID
65336 0xFF38 Description
Keypad displayLoad loss detected
Load loss Cause
RemedyIn a running motor, the motor load (current) is monitored. When the motor load falls below the threshold value specified in Load loss detection: threshold (0x4006:001 (P710.01)) for the period of time specified in Load loss detection: delay time (0x4006:002 (P710.02)), load loss protection is triggered.
Severity/responseCheck utilisation
No response (configurable) Setting parameters: 0x4006:003 (P710.03)
-
Fault message ID
65337 0xFF39 Description
Keypad displayMotor overload
Motor overload Cause
RemedyIf the apparent motor current exceeds a defined threshold value 0x4007:002 for a certain amount of time 0x4007:001, heavy duty monitoring is triggered.
Severity/responseCheck the motor load.
No response (configurable) Setting parameters: 0x4007:003
-
Fault message ID
65366 0xFF56 Description
Keypad displayMaximum motor frequency reached
Max. motor freq. Cause
Remedy- The limitation of the maximum motor speed set in 0x6080 (P322.00) is active.
- The maximum output frequency of the inverter has been reached.
- Depending on the parameter setting of 0x2D44:001 (P350.01) (Overspeed monitoring: threshold), the speed limitation (0x6080 / Max. motor speed) may become active before speed monitoring.
Severity/responseCheck application.
Warning
-
Fault message ID
65370 0xFF5A Description
Keypad displayManual mode disabled
Man. mode disabl Cause
Severity/responseIndicates the deactivation of the manual speed control.
Warning
-
Fault message ID
65371 0xFF5B Description
Keypad displayManual mode activated
Man. mode act. Cause
Severity/responseIndicates the activation of the manual speed control.
Warning
-
Fault message ID
65372 0xFF5C Description
Keypad displayManual mode time-out
ManMode time-out Cause
RemedyIf "manual operation" is active, an error is generated in case the communication links get lost.
Severity/responseThe error can be only be reset if the connection is restored or the control mode is changed to a different value than "manual operation".
Fault
-
Fault message ID
65393 0xFF71 Description
Keypad displayWrong password
Wrong password Cause
RemedyA wrong password has been entered several times.
Severity/responseWait until the blocking time has elapsed and then enter the correct password.
Warning
- The blocking time for entering a password is more than 10 seconds. (The blocking time is doubled every time an incorrect password is entered.)
- No password can be entered as long as the blocking time is active.
-
Fault message ID
65394 0xFF72 Description
Keypad displayBrand protection - not compatible
Warning Cause
RemedyInverter is not compatible with the Controller/PLC (brand protection).
- The Controller has not written a deactivation password in the parameter yet.
- The deactivation password written by the Controller is incorrect.
Severity/responseUse corresponding (compatible) OEM components.
Warning
- No response from the inverter.
- The decision on whether the machine will be commissioned or not is made by the Controller.
-
Fault message ID
65395 0xFF73 Description
Keypad displayFatal Error
Fatal Error Cause
RemedyError when reading the data from the control unit.
Severity/response- Switch inverter off and on again.
- If the error occurs again, the manufacturer must be contacted, since the control unit or the device has to be replaced.
Fault
- Operation of the inverter is not possible.
-
Fault message ID
65396 0xFF74 Description
Keypad displayPower unit fatal error
PU fatal error Cause
RemedyError when reading the data from the power unit.
Severity/response- Switch inverter off and on again.
- If the error occurs again, the manufacturer must be contacted, since the power unit or the device has to be replaced.
Fault
- Operation of the inverter is not possible.
-
Fault message ID
65413 0xFF85 Description
Keypad displayKeypad full control active
Keypad full ctrl Cause
RemedyIf the "Keypad Full Control" control mode is active.
Severity/responseTo exit the control mode, press the keypad key CTRL.
Warning
- Both the activity of controlling and the setpoint selection are carried out via the keypad.
-
0x10F3:035
Parameter
Diagnosis History: Diagnosis message 29 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:036
Parameter
Diagnosis History: Diagnosis message 30 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:037
Parameter
Diagnosis History: Diagnosis message 31 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x1200:000
Parameter
SDO1 server parameter: Highest sub-index supported Data type
U8 Default setting
- (Read only) Fieldbus
CANopen -
0x1200:001
Parameter
SDO1 server parameter: COB-ID client > server (rx) Data type
U32 Default setting
- (Read only) Fieldbus
CANopen -
0x1200:002
Parameter
SDO1 server parameter: COB-ID server > client (tx) Data type
U32 Default setting
- (Read only) Fieldbus
CANopen -
0x1201:000
Parameter
SDO2 server parameter: Highest sub-index supported Data type
U8 Default setting
- (Read only) Fieldbus
CANopen -
0x1201:001
Parameter
SDO2 server parameter: COB-ID client > server (rx) Data type
U32 Default setting
0x80000640 Fieldbus
CANopen -
0x1201:002
Parameter
SDO2 server parameter: COB-ID server > client (tx) Data type
U32 Default setting
0x800005C0 Fieldbus
CANopen -
0x1201:003
Parameter
SDO2 server parameter: Node-ID of the SDO client Data type
U8 Default setting
0 Fieldbus
CANopen -
0x1300
Parameter
SDO_SequLayerTimeout_U32 Data type
U32 Default setting
15000 ms Fieldbus
POWERLINK -
0x1301
Parameter
SDO_CmdLayerTimeout_U32 Data type
U32 Default setting
30000 ms Fieldbus
POWERLINK -
0x1400:000
Parameter
RPDO1 communication parameter: Highest sub- index supported Data type
U8 Default setting
- (Read only) Fieldbus
CANopen -
0x1400:001
Parameter
PDO_RxCommParam_00h_REC: NodeID_U8 Data type
U8 Default setting
0 Fieldbus
POWERLINK -
0x1400:001
Parameter
RPDO1 communication parameter: COB-ID Data type
U32 Display Code
P540.01 Default setting
0x00000200 Fieldbus
CANopen -
0x1400:002
Parameter
RPDO1 communication parameter: Transmission type Data type
U8 Display Code
P540.02 Default setting
255 Fieldbus
CANopen -
0x1400:002
Parameter
PDO_RxCommParam_00h_REC: MappingVersion_U8 Data type
U8 Default setting
- (Read only) Fieldbus
POWERLINK -
0x1400:005
Parameter
RPDO1 communication parameter: Event timer Data type
U16 Display Code
P540.05 Default setting
100 ms Fieldbus
CANopen -
0x1401:001
Parameter
RPDO2 communication parameter: COB-ID Data type
U32 Display Code
P541.01 Default setting
0x80000300 Fieldbus
CANopen -
0x1401:002
Parameter
RPDO2 communication parameter: Transmission type Data type
U8 Display Code
P541.02 Default setting
255 Fieldbus
CANopen -
0x1401:005
Parameter
RPDO2 communication parameter: Event timer Data type
U16 Display Code
P541.05 Default setting
100 ms Fieldbus
CANopen -
0x1402:001
Parameter
RPDO3 communication parameter: COB-ID Data type
U32 Display Code
P542.01 Default setting
0x80000400 Fieldbus
CANopen -
0x1402:002
Parameter
RPDO3 communication parameter: Transmission type Data type
U8 Display Code
P542.02 Default setting
255 Fieldbus
CANopen -
0x1402:005
Parameter
RPDO3 communication parameter: Event timer Data type
U16 Display Code
P542.05 Default setting
100 ms Fieldbus
CANopen -
0x1600:000
Parameter
RPDO1 mapping parameter: Number of mapped application objects in PDO Data type
U8 Default setting
2 Fieldbus
CANopen