0xFF09
Cause
A failure of several motor phases has been detected.
Description
Motor phase missing
Remedy
- Check wiring between inverter and motor.
- In case of a false tripping, adapt the settings for the motor phase failure detection.
Product categories
i550i950Severity/response
No response (configurable)
- The event can only be reset after a blocking time. Setting parameters: 0x2D45:001 (P310.01)
Blocking time: 2 s
Fault message ID
65289Keypad display
Mot.Phase miss.