6ES7332-5RD00-0AB0
SIMATIC S7, analog output SM 332, isolated, 4 AO; 0/4 to 20 mA, 20-pole, for signals from the hazardous area, diagnostics-capable, PTB tested
Siemens spare part — S7-300 product cancellation (PM410, 1 October 2025); available as a spare part until 2033.
Product category
Analog modulesManufacturer
SIEMENSProduct series
S7-300| Supply voltage | |
|---|---|
| Load voltage L+ | |
| Rated value (DC) | 24 V |
| Reverse polarity protection | Yes |
| Input current | |
| from load voltage L+ (without load), max. | 200 mA |
| from backplane bus 5 V DC, max. | 80 mA |
| Power loss | |
| Power loss, typ. | 4 W |
| Analog outputs | |
| Number of analog outputs | 4 |
| Voltage output, short-circuit protection | Yes |
| Voltage output, short-circuit current, max. | 70 mA |
| Current output, no-load voltage, max. | 14 V |
| Output ranges, current | |
| 0 to 20 mA | Yes |
| 4 mA to 20 mA | Yes |
| Connection of actuators | |
| for current output two-wire connection | Yes |
| Load impedance (in rated range of output) | |
| with current outputs, max. | 500 Ω |
| Cable length | |
| shielded, max. | 200 m |
| Analog value generation for the outputs | |
| Integration and conversion time/resolution per channel | |
| Resolution with overrange (bit including sign), max. | 15 bit |
| Errors/accuracies | |
| Operational error limit in overall temperature range | |
| Current, relative to output range, (+/-) | 0.55 % |
| Basic error limit (operational limit at 25 °C) | |
| Current, relative to output range, (+/-) | 0.2 % |
| Interrupts/diagnostics/status information | |
| Diagnostics function | Yes |
| Diagnoses | |
| Overrange | Yes |
| Wire-break in actuator cable | Yes |
| Diagnostics indication LED | |
| Group error SF (red) | Yes |
| Channel fault indicator F (red) | Yes |
| Ex(i) characteristics | |
| Module for Ex(i) protection | Yes |
| maximum values for connecting terminals for gas group IIC | |
| Uo (no-load voltage), max. | 14 V |
| Io (short-circuit current), max. | 70 mA |
| Po (power output), max. | 440 mW |
| Co (permissible external capacity), max. | 850 nF |
| Lo (permissible external inductivity), max. | 6.6 mH |
| Potential separation | |
| Potential separation analog outputs | |
| between the channels | Yes |
| between the channels and backplane bus | Yes |
| Between the channels and load voltage L+ | Yes |
| Standards, approvals, certificates | |
| Use in hazardous areas | |
| ATEX marking | [EEx ib] IIC |
| FM marking | Class I, Division 2, Group A, B, C, D T4 |
| Test number PTB | Ex-96.D.2026X |
| Ambient conditions | |
| Ambient temperature during operation | |
| max. | 60 °C |
| Connection method | |
| required front connector | 20-pin |
| Dimensions | |
| Width | 40 mm |
| Height | 125 mm |
| Depth | 120 mm |
| Weights | |
| Weight, approx. | 280 g |
| Approvals / Certificates | |