6ES7332-5RD00-0AB0

Siemens 6ES7332-5RD00-0AB0

SIMATIC S7, analog output SM 332, isolated, 4 AO; 0/4 to 20 mA, 20-pole, for signals from the hazardous area, diagnostics-capable, PTB tested

Siemens spare part — S7-300 product cancellation (PM410, 1 October 2025); available as a spare part until 2033.

Kategoria produktu
Moduły analogowe
Producent
SIEMENS
Seria produktów
S7-300
Supply voltage
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.200 mA
from backplane bus 5 V DC, max.80 mA
Power loss
Power loss, typ.4 W
Analog outputs
Number of analog outputs4
Voltage output, short-circuit protectionYes
Voltage output, short-circuit current, max.70 mA
Current output, no-load voltage, max.14 V
Output ranges, current
0 to 20 mAYes
4 mA to 20 mAYes
Connection of actuators
for current output two-wire connectionYes
Load impedance (in rated range of output)
with current outputs, max.500 Ω
Cable length
shielded, max.200 m
Analog value generation for the outputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.15 bit
Errors/accuracies
Operational error limit in overall temperature range
Current, relative to output range, (+/-)0.55 %
Basic error limit (operational limit at 25 °C)
Current, relative to output range, (+/-)0.2 %
Interrupts/diagnostics/status information
Diagnostics functionYes
Diagnoses
OverrangeYes
Wire-break in actuator cableYes
Diagnostics indication LED
Group error SF (red)Yes
Channel fault indicator F (red)Yes
Ex(i) characteristics
Module for Ex(i) protectionYes
maximum values for connecting terminals for gas group IIC
Uo (no-load voltage), max.14 V
Io (short-circuit current), max.70 mA
Po (power output), max.440 mW
Co (permissible external capacity), max.850 nF
Lo (permissible external inductivity), max.6.6 mH
Potential separation
Potential separation analog outputs
between the channelsYes
between the channels and backplane busYes
Between the channels and load voltage L+Yes
Standards, approvals, certificates
Use in hazardous areas
ATEX marking[EEx ib] IIC
FM markingClass I, Division 2, Group A, B, C, D T4
Test number PTBEx-96.D.2026X
Ambient conditions
Ambient temperature during operation
max.60 °C
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.280 g
Approvals / Certificates