6ES7536-1MF00-0AB0
SIMATIC S7-1500, F-analog input module, F-AI 8xI 0(4)..20 mA PROFIsafe; 35 mm, overall width; up to PL e (ISO 13849-1)/ SIL 3 (IEC 61508).
Product category
Analog modulesManufacturer
SIEMENSProduct series
S7-1500| General information | |
|---|---|
| Product type designation | F-AI 8xI 0(4) ... 20 mA |
| Firmware version | |
| FW update possible | Yes |
| Product function | |
| I&M data | Yes; I&M0 to I&M3 |
| Engineering with | |
| STEP 7 TIA Portal configurable/integrated from version | V18 with HSP0394 (FW V1.0) / V19 with HSP0451 (FW V2.0) |
| Operating mode | |
| MSI | Yes; firmware V2.0 or higher |
| CiR - Configuration in RUN | |
| Reparameterization possible in RUN | No |
| Calibration possible in RUN | No |
| Supply voltage | |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes |
| Input current | |
| Current consumption (rated value) | 75 mA |
| Current consumption, max. | 2.5 A; All channels are supplied from the encoder supply |
| Encoder supply | |
| Number of outputs | 8 |
| Short-circuit protection | Yes |
| 24 V encoder supply | |
| 24 V | Yes; min. L+ (-1.5 V) |
| Short-circuit protection | Yes |
| Output current per channel, max. | 300 mA |
| Power | |
| Power consumption from the backplane bus | 0.5 W |
| Power loss | |
| Power loss, typ. | 2.5 W |
| Address area | |
| Address space per module | |
| Inputs | 23 byte |
| Outputs | 6 byte |
| Hardware configuration | |
| Automatic encoding | Yes |
| Analog inputs | |
| Number of analog inputs | 8 |
| permissible input current for current input (destruction limit), max. | 35 mA |
| Input ranges (rated values), currents | |
| 0 to 20 mA | Yes |
| Input resistance (0 to 20 mA) | 150 Ω |
| 4 mA to 20 mA | Yes |
| Input resistance (4 mA to 20 mA) | 150 Ω |
| Cable length | |
| shielded, max. | 1 000 m |
| Analog value generation for the inputs | |
| Measurement principle | Sigma Delta |
| Integration and conversion time/resolution per channel | |
| Resolution with overrange (bit including sign), max. | 16 bit |
| Integration time, parameterizable | Yes |
| Integration time (ms) | 20 / 16,667 |
| Interference voltage suppression for interference frequency f1 in Hz | 50 / 60 Hz |
| Smoothing of measured values | |
| Number of smoothing levels | 7 |
| parameterizable | Yes |
| Step: None | Yes; 1x conversion time |
| Step: low | Yes; 2x / 4x conversion cycle time |
| Step: Medium | Yes; 8x / 16x conversion cycle time |
| Step: High | Yes; 32x / 64x conversion cycle time |
| Encoder | |
| Connection of signal encoders | |
| for current measurement as 2-wire transducer | Yes |
| Burden of 2-wire transmitter, max. | 650 Ω |
| for current measurement as 4-wire transducer | Yes |
| Errors/accuracies | |
| Linearity error (relative to input range), (+/-) | 0.05 % |
| Temperature error (relative to input range), (+/-) | 0.005 %/K |
| Crosstalk between the inputs, max. | -70 dB |
| Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.05 % |
| Operational error limit in overall temperature range | |
| Current, relative to input range, (+/-) | 0.3 %; without HART communication |
| Basic error limit (operational limit at 25 °C) | |
| Current, relative to input range, (+/-) | 0.05 %; without HART communication |
| Influence of a HART signal modulated on the input signal in relation to input range | |
| error occurred at interference frequency suppression: 60 Hz | 0.12 % |
| error occurred at interference frequency suppression: 50 Hz | 0.12 % |
| Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | |
| Series mode interference (peak value of interference < rated value of input range), min. | 40 dB |
| Common mode voltage, max. | 60 V DC/30 V AC |
| Common mode interference, min. | 70 dB |
| Interrupts/diagnostics/status information | |
| Diagnostics function | Yes |
| Alarms | |
| Diagnostic alarm | Yes |
| Limit value alarm | No |
| Diagnoses | |
| Monitoring the supply voltage | Yes |
| Wire break | Yes |
| Short-circuit | Yes |
| Overflow/Underflow | Yes |
| Diagnostics indication LED | |
| RUN LED | Yes; green LED |
| ERROR LED | Yes; red LED |
| Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
| Channel status display | Yes; green LED |
| for channel diagnostics | Yes; red LED |
| Potential separation | |
| Potential separation analog inputs | |
| between the channels | No |
| between the channels, in groups of | 4 |
| between the channels and backplane bus | Yes |
| between the channels and the power supply of the electronics | Yes |
| Permissible potential difference | |
| between the inputs (UCM) | 60 V DC/30 V AC |
| Isolation | |
| Isolation tested with | 707 V DC (type test) |
| Standards, approvals, certificates | |
| Highest safety class achievable in safety mode | |
| Performance level according to ISO 13849-1 | PLe |
| Category according to ISO 13849-1 | Cat. 4 |
| SIL acc. to IEC 61508 | SIL 3 |
| Probability of failure (for service life of 20 years and repair time of 100 hours) | |
| Low demand mode: PFDavg in accordance with SIL3 | < 4.00E-05 |
| High demand/continuous mode: PFH in accordance with SIL3 | < 1.00E-09 1/h |
| Ambient conditions | |
| Ambient temperature during operation | |
| horizontal installation, min. | 0 °C |
| horizontal installation, max. | 60 °C |
| vertical installation, min. | 0 °C |
| vertical installation, max. | 40 °C |
| Dimensions | |
| Width | 35 mm |
| Height | 147 mm |
| Depth | 129 mm |
| Weights | |
| Weight, approx. | 290 g |
| Approvals / Certificates | |