6ES7536-1MF00-0AB0

6ES7536-1MF00-0AB0

SIMATIC S7-1500, modul de intrare analogică F, F-AI 8xI 0(4)..20 mA PROFIsafe; lățime totală 35 mm; până la PL e (ISO 13849-1)/SIL 3 (IEC 61508).

Categorie de produs
Module analogice
Producător
SIEMENS
Serie de produse
S7-1500
General information
Product type designationF-AI 8xI 0(4) ... 20 mA
Firmware version
FW update possibleYes
Product function
I&M dataYes; I&M0 to I&M3
Engineering with
STEP 7 TIA Portal configurable/integrated from versionV18 with HSP0394 (FW V1.0) / V19 with HSP0451 (FW V2.0)
Operating mode
MSIYes; firmware V2.0 or higher
CiR - Configuration in RUN
Reparameterization possible in RUNNo
Calibration possible in RUNNo
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption (rated value)75 mA
Current consumption, max.2.5 A; All channels are supplied from the encoder supply
Encoder supply
Number of outputs8
Short-circuit protectionYes
24 V encoder supply
24 VYes; min. L+ (-1.5 V)
Short-circuit protectionYes
Output current per channel, max.300 mA
Power
Power consumption from the backplane bus0.5 W
Power loss
Power loss, typ.2.5 W
Address area
Address space per module
Inputs23 byte
Outputs6 byte
Hardware configuration
Automatic encodingYes
Analog inputs
Number of analog inputs8
permissible input current for current input (destruction limit), max.35 mA
Input ranges (rated values), currents
0 to 20 mAYes
Input resistance (0 to 20 mA)150 Ω
4 mA to 20 mAYes
Input resistance (4 mA to 20 mA)150 Ω
Cable length
shielded, max.1 000 m
Analog value generation for the inputs
Measurement principleSigma Delta
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit
Integration time, parameterizableYes
Integration time (ms)20 / 16,667
Interference voltage suppression for interference frequency f1 in Hz50 / 60 Hz
Smoothing of measured values
Number of smoothing levels7
parameterizableYes
Step: NoneYes; 1x conversion time
Step: lowYes; 2x / 4x conversion cycle time
Step: MediumYes; 8x / 16x conversion cycle time
Step: HighYes; 32x / 64x conversion cycle time
Encoder
Connection of signal encoders
for current measurement as 2-wire transducerYes
Burden of 2-wire transmitter, max.650 Ω
for current measurement as 4-wire transducerYes
Errors/accuracies
Linearity error (relative to input range), (+/-)0.05 %
Temperature error (relative to input range), (+/-)0.005 %/K
Crosstalk between the inputs, max.-70 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.05 %
Operational error limit in overall temperature range
Current, relative to input range, (+/-)0.3 %; without HART communication
Basic error limit (operational limit at 25 °C)
Current, relative to input range, (+/-)0.05 %; without HART communication
Influence of a HART signal modulated on the input signal in relation to input range
error occurred at interference frequency suppression: 60 Hz0.12 %
error occurred at interference frequency suppression: 50 Hz0.12 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.40 dB
Common mode voltage, max.60 V DC/30 V AC
Common mode interference, min.70 dB
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Limit value alarmNo
Diagnoses
Monitoring the supply voltageYes
Wire breakYes
Short-circuitYes
Overflow/UnderflowYes
Diagnostics indication LED
RUN LEDYes; green LED
ERROR LEDYes; red LED
Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Channel status displayYes; green LED
for channel diagnosticsYes; red LED
Potential separation
Potential separation analog inputs
between the channelsNo
between the channels, in groups of4
between the channels and backplane busYes
between the channels and the power supply of the electronicsYes
Permissible potential difference
between the inputs (UCM)60 V DC/30 V AC
Isolation
Isolation tested with707 V DC (type test)
Standards, approvals, certificates
Highest safety class achievable in safety mode
Performance level according to ISO 13849-1PLe
Category according to ISO 13849-1Cat. 4
SIL acc. to IEC 61508SIL 3
Probability of failure (for service life of 20 years and repair time of 100 hours)
Low demand mode: PFDavg in accordance with SIL3< 4.00E-05
High demand/continuous mode: PFH in accordance with SIL3< 1.00E-09 1/h
Ambient conditions
Ambient temperature during operation
horizontal installation, min.0 °C
horizontal installation, max.60 °C
vertical installation, min.0 °C
vertical installation, max.40 °C
Dimensions
Width35 mm
Height147 mm
Depth129 mm
Weights
Weight, approx.290 g
Approvals / Certificates