6ES7522-1BF00-0AB0

6ES7522-1BF00-0AB0

SIMATIC S7-1500, modul digitálnych výstupov DQ 8x24 V DC/2A HF; 8 kanálov v skupinách po 8; 8 A na skupinu; diagnostika; náhradná hodnota: 2 kanály možno použiť na pulzne šírkovú moduláciu (PWM). Modul podporuje bezpečnostné vypnutie záťažových skupín do SIL2 podľa EN IEC 62061:2021 a kategórie 3 / PL d podľa EN ISO 13849-1:2015. Čelný konektor (skrutkové svorky alebo push-in) sa objednáva samostatne.

Kategória produktu
Digitálne moduly
Výrobca
SIEMENS
Produktový rad
S7-1500
General information
Product type designationDQ 8x24VDC/2A HF
HW functional statusFS03
Firmware versionV2.2.0
FW update possibleYes
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeNo
Prioritized startupYes
Engineering with
STEP 7 TIA Portal configurable/integrated from versionV13 SP1 / -
STEP 7 configurable/integrated from versionV5.5 SP3 / -
PROFIBUS from GSD version/GSD revisionV1.0 / V5.1
PROFINET from GSD version/GSD revisionV2.3 / -
Operating mode
DQYes
DQ with energy-saving functionYes; with an application
PWMYes; FS02 and FW V2.1.0 or higher; two outputs can be operated with max. 500 Hz PWM
Cam control (switching at comparison values)No
OversamplingNo
MSOYes
Integrated operating cycle counterYes
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes; through internal protection with 10 A per group
Input current
Current consumption, max.40 mA; 20 mA per group, no output is activated.
Output voltage
Rated value (DC)24 V
Power
Power consumption from the backplane bus0.9 W
Power loss
Power loss, typ.5.6 W; 6.8 W for PWM operation
Digital outputs
Type of digital outputTransistor
Number of digital outputs8
Current-sourcingYes
Digital outputs, parameterizableYes
Short-circuit protectionYes
Response threshold, typ.3 A
Limitation of inductive shutdown voltage to-17 V
Controlling a digital inputYes
Digital output functions, parameterizable
Freely usable digital outputYes
PWM outputYes; FS02 and FW V2.1.0 or higher
Number, max.2
Cycle duration, parameterizableYes; 2 ... 100 ms continuous
ON period, min.0 %
ON period, max.100 %
Resolution of the duty cycle0.1 %
Minimum pulse duration300 µs
Switching capacity of the outputs
on lamp load, max.10 W
Load resistance range
lower limit12 Ω
upper limit4 kΩ
Output voltage
for signal "1", min.L+ (-0.8 V)
Output current
for signal "1" rated value2 A
for signal "1" permissible range, max.2.4 A; note derating specification for PWM operation
for signal "0" residual current, max.0.5 mA
Output delay with resistive load
"0" to "1", typ.80 µs
"0" to "1", max.100 µs
"1" to "0", typ.300 µs
"1" to "0", max.500 µs
Parallel switching of two outputs
for logic linksYes
for upratingNo
for redundant control of a loadYes
Switching frequency
with resistive load, max.100 Hz; With PWM operation: 500 Hz
with inductive load, max.0.5 Hz; According to IEC 60947-5-1, DC-13; max. 500 Hz with PWM operation only with external circuit; see additional description in the manual
on lamp load, max.10 Hz
Total current of the outputs
Current per channel, max.2 A; see additional description in the manual
Current per group, max.8 A; see additional description in the manual
Current per module, max.16 A; see additional description in the manual
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Interrupts/diagnostics/status information
Diagnostics functionYes
Substitute values connectableYes
Alarms
Diagnostic alarmYes
Maintenance interruptYes
Diagnoses
Monitoring the supply voltageYes
Wire breakNo
Short-circuitYes
Group errorYes
Diagnostics indication LED
RUN LEDYes; green LED
ERROR LEDYes; red LED
MAINT LEDYes; Yellow LED
Monitoring of the supply voltage (PWR-LED)Yes; green LED
Channel status displayYes; green LED
for channel diagnosticsYes; red LED
for module diagnosticsYes; red LED
Potential separation
Potential separation channels
between the channelsNo
between the channels, in groups of4
between the channels and backplane busYes
Isolation
Isolation tested with707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functionsNo
Suitable for safety-related tripping of standard modulesYes; From FS03
Highest safety class achievable for safety-related tripping of standard modules
Performance level according to ISO 13849-1PL d
Category according to ISO 13849-1Cat. 3
SIL acc. to IEC 62061SIL 2
remark on safety-oriented shutdownhttps://support.industry.siemens.com/cs/de/en/view/39198632
Security
signed firmware updateNo
data integrityNo
Ambient conditions
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Dimensions
Width35 mm
Height147 mm
Depth129 mm
Weights
Weight, approx.240 g
Approvals / Certificates