6AG1521-1BH00-7AB0
SIPLUS S7-1500 DI 16x24VDC HF na báze 6ES7521-1BH00-0AB0 s ochranným lakovaním, -40…+70 °C, modul digitálnych vstupov, 16 kanálov v skupinách po 16; vstupné zdržanie 0.05..20 ms, vstupný typ 3 (IEC 61131); diagnostika; hardvérové prerušenia.
Kategória produktu
Digitálne modulyVýrobca
SIEMENSProduktový rad
S7-1500| General information | |
|---|---|
| Product type designation | DI 16x24VDC HF |
| HW functional status | E01 |
| Firmware version | V1.0.0 |
| based on | 6ES7521-1BH00-0AB0 |
| Product function | |
| I&M data | Yes; I&M0 to I&M3 |
| Isochronous mode | Yes |
| Prioritized startup | Yes |
| Engineering with | |
| STEP 7 TIA Portal configurable/integrated from version | see entry ID: 109746275 |
| Operating mode | |
| DI | Yes |
| Counter | Yes |
| Oversampling | No |
| MSI | Yes |
| Supply voltage | |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes |
| Input current | |
| Current consumption, max. | 20 mA |
| Power | |
| Power consumption from the backplane bus | 1.1 W |
| Power loss | |
| Power loss, typ. | 2.6 W |
| Digital inputs | |
| Number of digital inputs | 16 |
| Sourcing/sinking input | P-reading |
| Input characteristic curve in accordance with IEC 61131, type 3 | Yes |
| Digital input functions, parameterizable | |
| Gate start/stop | Yes |
| Freely usable digital input | Yes |
| Counter | |
| Number, max. | 2 |
| Counting frequency, max. | 6 kHz |
| Counting width | 32 bit |
| Counting direction up/down | Up |
| Input voltage | |
| Rated value (DC) | 24 V |
| for signal "0" | -30 to +5 V |
| for signal "1" | +11 to +30V |
| Input current | |
| for signal "1", typ. | 2.5 mA |
| Input delay (for rated value of input voltage) | |
| for standard inputs | |
| parameterizable | Yes; 0.05 / 0.1 / 0.4 / 1.6 / 3.2 / 12.8 / 20 ms |
| at "0" to "1", min. | 0.05 ms |
| at "0" to "1", max. | 20 ms |
| at "1" to "0", min. | 0.05 ms |
| at "1" to "0", max. | 20 ms |
| for interrupt inputs | |
| Parameterizable | Yes |
| for technological functions | |
| Parameterizable | Yes |
| Cable length | |
| shielded, max. | 1 000 m |
| unshielded, max. | 600 m |
| Encoder | |
| Connectable encoders | |
| 2-wire sensor | Yes |
| permissible quiescent current (2-wire sensor), max. | 1.5 mA |
| Isochronous mode | |
| Filtering and processing time (TCI), min. | 80 µs; At 50 μs filter time |
| Bus cycle time (TDP), min. | 250 µs |
| Interrupts/diagnostics/status information | |
| Diagnostics function | Yes |
| Alarms | |
| Diagnostic alarm | Yes |
| Hardware interrupt | Yes |
| Diagnoses | |
| Monitoring the supply voltage | Yes |
| Wire break | Yes; to I < 350 µA |
| short-circuit | No |
| Diagnostics indication LED | |
| RUN LED | Yes; green LED |
| ERROR LED | Yes; red LED |
| Monitoring of the supply voltage (PWR-LED) | Yes; green LED |
| Channel status display | Yes; green LED |
| for channel diagnostics | Yes; red LED |
| for module diagnostics | Yes; red LED |
| Potential separation | |
| Potential separation channels | |
| between the channels | No |
| between the channels, in groups of | 16 |
| between the channels and backplane bus | Yes |
| between the channels and the power supply of the electronics | No |
| Isolation | |
| Isolation tested with | 707 V DC (type test) |
| Standards, approvals, certificates | |
| Suitable for safety functions | No |
| Ecological footprint | |
| environmental product declaration | Yes |
| Global warming potential | |
| global warming potential, (total) [CO2 eq] | 18.9 kg |
| global warming potential, (during production) [CO2 eq] | 12.1 kg |
| global warming potential, (during operation) [CO2 eq] | 7.66 kg |
| global warming potential, (after end of life cycle) [CO2 eq] | -1.02 kg |
| Security | |
| signed firmware update | No |
| data integrity | No |
| Ambient conditions | |
| Ambient temperature during operation | |
| horizontal installation, min. | -40 °C; = Tmin (incl. condensation/frost) |
| horizontal installation, max. | 70 °C; = Tmax |
| vertical installation, min. | -40 °C; = Tmin |
| vertical installation, max. | 40 °C; = Tmax |
| Altitude during operation relating to sea level | |
| Installation altitude above sea level, max. | 5 000 m |
| Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
| Relative humidity | |
| With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
| Resistance | |
| Coolants and lubricants | |
| Resistant to commercially available coolants and lubricants | Yes; Incl. diesel and oil droplets in the air |
| Use in stationary industrial systems | |
| to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
| to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * |
| Use on ships/at sea | |
| to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request |
| to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
| to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * |
| Usage in industrial process technology | |
| Against chemically active substances acc. to EN 60654-4 | Yes; Class 3 (excluding trichlorethylene) |
| Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) |
| Remark | |
| Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! |
| Conformal coating | |
| Coatings for printed circuit board assemblies acc. to EN 61086 | Yes; Class 2 for high reliability |
| Protection against fouling acc. to EN 60664-3 | Yes; Type 1 protection |
| Military testing according to MIL-I-46058C, Amendment 7 | Yes; Discoloration of coating possible during service life |
| Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A | Yes; Conformal coating, Class A |
| Dimensions | |
| Width | 35 mm |
| Height | 147 mm |
| Depth | 129 mm |
| Weights | |
| Weight, approx. | 240 g |
| Approvals / Certificates | |