6AG1531-7LH00-7AB0
SIPLUS S7-1500 AI 16xU BA na báze 6ES7531-7LH00-0AB0 s ochranným lakovaním, -40...+70 °C, modul analógových vstupov, AI 16xU BA, 16-bitové rozlíšenie, presnosť 0.5%, 16 kanálov v skupinách po 16, napätie spoločného módu 4 V DC, diagnostika, hardvérové prerušenia; dodávka vrátane prívodného elementu, tieniacej konzoly a tieniacej svorky: čelný konektor (skrutkové svorky alebo push-in) sa objednáva samostatne.
Kategória produktu
Analógové modulyVýrobca
SIEMENSProduktový rad
S7-1500| General information | |
|---|---|
| Product type designation | AI 16xU BA |
| Firmware version | |
| FW update possible | Yes |
| based on | 6ES7531-7LH00-0AB0 |
| Product function | |
| I&M data | Yes; I&M0 to I&M3 |
| Isochronous mode | No |
| Prioritized startup | No |
| Measuring range scalable | No |
| Scalable measured values | No |
| Adjustment of measuring range | No |
| Engineering with | |
| STEP 7 TIA Portal configurable/integrated from version | see entry ID: 109746275 |
| Operating mode | |
| Oversampling | No |
| MSI | Yes |
| CiR - Configuration in RUN | |
| Reparameterization possible in RUN | Yes |
| Calibration possible in RUN | No |
| Power | |
| Power consumption from the backplane bus | 0.85 W |
| Power loss | |
| Power loss, typ. | 0.75 W |
| Analog inputs | |
| Number of analog inputs | 16 |
| For voltage measurement | 16 |
| permissible input voltage for voltage input (destruction limit), max. | 12 V; 12 V continuous, 30 V for max. 1 s |
| Input ranges (rated values), voltages | |
| 0 to +5 V | No |
| 0 to +10 V | No |
| 1 V to 5 V | Yes |
| Input resistance (1 V to 5 V) | 10 MΩ |
| -1 V to +1 V | Yes |
| Input resistance (-1 V to +1 V) | 10 MΩ |
| -10 V to +10 V | Yes |
| Input resistance (-10 V to +10 V) | 10 MΩ |
| -2.5 V to +2.5 V | No |
| -25 mV to +25 mV | No |
| -250 mV to +250 mV | No |
| -5 V to +5 V | Yes |
| Input resistance (-5 V to +5 V) | 10 MΩ |
| -50 mV to +50 mV | No |
| -500 mV to +500 mV | No |
| -80 mV to +80 mV | No |
| Cable length | |
| shielded, max. | 200 m |
| Analog value generation for the inputs | |
| Measurement principle | integrating |
| Integration and conversion time/resolution per channel | |
| Resolution with overrange (bit including sign), max. | 16 bit |
| Integration time, parameterizable | Yes |
| Integration time (ms) | 2,5 / 16,67 / 20 / 100 ms |
| Basic conversion time, including integration time (ms) | 10 / 24 / 27 / 107 ms |
| additional conversion time for wire-break monitoring | 4 ms (to be considered for 1 to 5 V measurement) |
| Interference voltage suppression for interference frequency f1 in Hz | 400 / 60 / 50 / 10 Hz |
| Smoothing of measured values | |
| parameterizable | Yes |
| Step: None | Yes |
| Step: low | Yes |
| Step: Medium | Yes |
| Step: High | Yes |
| Encoder | |
| Connection of signal encoders | |
| for voltage measurement | Yes |
| Errors/accuracies | |
| Linearity error (relative to input range), (+/-) | 0.1 % |
| Temperature error (relative to input range), (+/-) | 0.006 %/K |
| Crosstalk between the inputs, max. | -50 dB |
| Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.1 % |
| Operational error limit in overall temperature range | |
| Voltage, relative to input range, (+/-) | 0.6 % |
| Basic error limit (operational limit at 25 °C) | |
| Voltage, relative to input range, (+/-) | 0.3 % |
| Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | |
| Series mode interference (peak value of interference < rated value of input range), min. | 40 dB |
| Common mode voltage, max. | 4 V |
| Common mode interference, min. | 60 dB |
| Interrupts/diagnostics/status information | |
| Diagnostics function | Yes |
| Alarms | |
| Diagnostic alarm | Yes |
| Limit value alarm | Yes; two upper and two lower limit values in each case |
| Diagnoses | |
| Monitoring the supply voltage | No |
| Wire break | Yes; Only for 1 ... 5 V |
| Short-circuit | No |
| Group error | No |
| Overflow/Underflow | Yes |
| Diagnostics indication LED | |
| RUN LED | Yes; green LED |
| ERROR LED | Yes; red LED |
| MAINT LED | No |
| Monitoring of the supply voltage (PWR-LED) | No |
| Channel status display | Yes; green LED |
| for channel diagnostics | Yes; red LED |
| for module diagnostics | Yes; red LED |
| Potential separation | |
| Potential separation channels | |
| between the channels | No |
| between the channels, in groups of | 16 |
| between the channels and backplane bus | Yes |
| Permissible potential difference | |
| between the inputs (UCM) | 8 V DC |
| Between the inputs and MANA (UCM) | 4 V DC |
| Isolation | |
| Isolation tested with | 707 V DC (type test) |
| Security | |
| signed firmware update | No |
| data integrity | No |
| Ambient conditions | |
| Ambient temperature during operation | |
| horizontal installation, min. | -40 °C; = Tmin (incl. condensation/frost) |
| horizontal installation, max. | 70 °C; = Tmax |
| vertical installation, min. | -40 °C; = Tmin (incl. condensation/frost) |
| vertical installation, max. | 40 °C; = Tmax |
| Altitude during operation relating to sea level | |
| Installation altitude above sea level, max. | 5 000 m |
| Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
| Relative humidity | |
| With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation |
| Resistance | |
| Coolants and lubricants | |
| Resistant to commercially available coolants and lubricants | Yes; Incl. diesel and oil droplets in the air |
| Use in stationary industrial systems | |
| to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
| Use on ships/at sea | |
| to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request |
| to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
| to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * |
| Usage in industrial process technology | |
| Against chemically active substances acc. to EN 60654-4 | Yes; Class 3 (excluding trichlorethylene) |
| Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) |
| Remark | |
| Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! |
| Conformal coating | |
| Coatings for printed circuit board assemblies acc. to EN 61086 | Yes; Class 2 for high reliability |
| Protection against fouling acc. to EN 60664-3 | Yes; Type 1 protection |
| Military testing according to MIL-I-46058C, Amendment 7 | Yes; Discoloration of coating possible during service life |
| Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A | Yes; Conformal coating, Class A |
| Dimensions | |
| Width | 35 mm |
| Height | 147 mm |
| Depth | 129 mm |
| Weights | |
| Weight, approx. | 250 g |
| Approvals / Certificates | |