6AG1518-4JP00-4AB0

6AG1518-4JP00-4AB0

SIPLUS S7-1500 CPU 1518HF-4 PN na báze 6ES7518-4JP00-0AB0 s ochranným lakovaním, centrálna procesorová jednotka s pracovnou pamäťou 9 MB pre program a 60 MB pre dáta, 1. rozhranie: PROFINET RT s 2-portovým switchom, 2. rozhranie: PROFINET, 3. rozhranie: PROFINET, 4./5. rozhranie: H-SYNC, vyžaduje sa SIMATIC Memory Card.

Kategória produktu
CPU
Výrobca
SIEMENS
Produktový rad
S7-1500
General information
Product type designationCPU 1518HF-4PN
Firmware version
FW update possibleYes
based on6ES7518-4JP00-0AB0
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeNo
SysLogYes
Display
Screen diagonal [cm]6.1 cm
Control elements
Number of keys6
Mode selector switch1
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Mains buffering
Mains/voltage failure stored energy time5 ms
Input current
Current consumption (rated value)1.55 A
Current consumption, max.1.95 A
Inrush current, max.1.95 A; Rated value
I²t0.4 A²·s
Power
Infeed power to the backplane bus12 W
Power consumption from the backplane bus (balanced)30 W
Power loss
Power loss, typ.24 W
Storage
Number of slots for SIMATIC memory card1
SIMATIC memory card requiredYes
Work memory
integrated (for program)9 Mbyte
integrated (for data)60 Mbyte
Load memory
Plug-in (SIMATIC Memory Card), max.32 Gbyte
Backup
maintenance-freeYes
CPU processing times
for bit operations, typ.4 ns
for word operations, typ.6 ns
for fixed point arithmetic, typ.6 ns
for floating point arithmetic, typ.24 ns
CPU-blocks
Number of elements (total)20 000; Blocks (OB, FB, FC, DB) and UDTs
DB
Number range1 ... 60 999; subdivided into: number range that can be used by the user: 1 ... 59 999, and number range of DBs created via SFC 86: 60 000 ... 60 999
Size, max.16 Mbyte; For DBs with absolute addressing, the max. size is 64 KB
FB
Number range0 ... 65 535
Size, max.1 Mbyte
FC
Number range0 ... 65 535
Size, max.1 Mbyte
OB
Size, max.1 Mbyte
Number of free cycle OBs100
Number of time alarm OBs20
Number of delay alarm OBs20
Number of cyclic interrupt OBs20; with minimum OB 3x cycle of 1 ms
Number of process alarm OBs50
Number of DPV1 alarm OBs3
Number of startup OBs100
Number of asynchronous error OBs4
Number of synchronous error OBs2
Number of diagnostic alarm OBs1
Nesting depth
per priority class24; Up to 8 possible for F-blocks
Counters, timers and their retentivity
S7 counter
Number2 048
Retentivity
adjustableYes
IEC counter
NumberAny (only limited by the main memory)
Retentivity
can be setYes
S7 timer
Number2 048
Retentivity
adjustableYes
IEC timer
NumberAny (only limited by the main memory)
Retentivity
can be setYes
Data areas and their retentivity
Retentive data area (incl. timers, counters, flags), max.768 kbyte; In total; available retentive memory for bit memories, timers, counters, DBs, and technology data (axes): 700 KB
Flag
Size, max.16 kbyte
Number of clock memories8; 8 clock memory bit, grouped into one clock memory byte
Data blocks
Retentivity adjustableYes
Retentivity presetNo
Local data
per priority class, max.64 kbyte; max. 16 KB per block
Address area
Number of IO modules8 192; max. number of modules / submodules
I/O address area
Inputs32 kbyte; All inputs are in the process image
Outputs32 kbyte; All outputs are in the process image
per integrated IO subsystem
Inputs (volume)16 kbyte
Outputs (volume)16 kbyte
Subprocess images
Number of subprocess images, max.31
Hardware configuration
Number of distributed IO systems64; A distributed I/O system is characterized not only by the integration of distributed I/O via PROFINET, but also by the connection of I/O via IE/PB-Links.
Number of IO Controllers
Integrated1
Rack
Modules per rack, max.9; CPU + 2 PS + 6 CP
Time of day
Clock
TypeHardware clock
Backup time6 wk; At 40 °C ambient temperature, typically
Deviation per day, max.10 s; Typ.: 2 s
Operating hours counter
Number16
Clock synchronization
supportedYes
on Ethernet via NTPYes
Interfaces
Number of PROFINET interfaces3
1. Interface
Interface types
RJ 45 (Ethernet)Yes; X1
Number of ports2
integrated switchYes
Protocols
IP protocolYes; IPv4
PROFINET IO ControllerYes
PROFINET IO DeviceNo
SIMATIC communicationYes; Only Server
Open IE communicationYes; Optionally also encrypted
Web serverNo
Media redundancyYes
PROFINET IO Controller
Services
Isochronous modeNo
IRTNo
Dynamic Frame Packing (DFP)Yes
PROFIenergyYes; per user program
Prioritized startupNo
Number of connectable IO Devices, max.256
Updating timesThe minimum value of the update time also depends on communication share set for PROFINET IO, on the number of IO devices, and on the quantity of configured user data
PROFINET Security Class1
Update time for RT
for send cycle of 1 ms1 ms to 512 ms
2. Interface
Interface types
RJ 45 (Ethernet)Yes; X2
Number of ports1
integrated switchNo
Protocols
IP protocolYes; IPv4
PROFINET IO ControllerNo
PROFINET IO deviceNo
SIMATIC communicationYes; Only Server
Open IE communicationYes; Optionally also encrypted
Web serverYes
Media redundancyNo
3. Interface
Interface types
RJ 45 (Ethernet)Yes; X3
Number of ports1
integrated switchNo
Protocols
IP protocolYes; IPv4
PROFINET IO ControllerNo
PROFINET IO deviceNo
SIMATIC communicationYes; Only Server
Open IE communicationYes; Optionally also encrypted
Web serverYes
4. Interface
Interface typePluggable synchronization submodule (FO)
Plug-in interface modulesSynchronization module 6ES7960-1CB00-0AA5 or 6ES7960-1FB00-0AA5
5. Interface
Interface typePluggable synchronization submodule (FO)
Plug-in interface modulesSynchronization module 6AG1960-1CB00-4AA5 or 6AG1960-1FB00-4AA5
Interface types
RJ 45 (Ethernet)
100 MbpsYes
1000 MbpsYes; Only possible at the X3 interface of the CPU 1518
AutonegotiationYes
AutocrossingYes
Industrial Ethernet status LEDYes
Protocols
PROFIsafeYes; V2.4 / V2.6
Number of connections
Number of connections, max.384; via integrated interfaces of the CPU and connected CPs
Number of connections reserved for ES/HMI/web10
Number of connections via integrated interfaces320
Number of S7 routing paths64
Redundancy mode
PROFINET system redundancy (S2)Yes
PROFINET system redundancy (R1)Yes
Media redundancy
Media redundancyonly via 1st interface (X1)
MRPYes; MRP Automanager according to IEC 62439-2 Edition 2.0
MRP interconnection, supportedYes; as MRP ring node according to IEC 62439-2 Edition 3.0
MRPDNo
Switchover time on line break, typ.200 ms; PROFINET MRP
Number of stations in the ring, max.50
SIMATIC communication
PG/OP communicationYes; encryption with TLS V1.3 pre-selected
S7 routingYes
S7 communication, as serverYes
S7 communication, as clientNo
Open IE communication
TCP/IPYes
Data length, max.64 kbyte
several passive connections per port, supportedYes
ISO-on-TCP (RFC1006)Yes
Data length, max.64 kbyte
UDPYes
Data length, max.2 kbyte; 1 472 bytes for UDP broadcast
UDP multicastYes; 128 multicast circuits (of which max. 5 via X1)
DHCPNo
DNSYes
SNMPYes
DCPYes
LLDPYes
encryptionYes; Optional
Web server
HTTPNo
HTTPSYes; only via Web API
web APIYes
Number of sessions, max.200
number of simultaneous HTTP calls, max.4
HTTP request body, max.131 072 byte
OPC UA
Runtime license requiredYes; "Large" license required per CPU
OPC UA ClientNo
OPC UA ServerYes; Data access (read, write, subscribe), method call, custom address space
Application authenticationYes
Security policiesavailable security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256, Aes128Sha256RsaOaep, Aes256Sha256RsaPss
User authentication"anonymous" or by user name & password
GDS support (certificate management)No
Number of sessions, max.32
Number of subscriptions per session, max.25
Sampling interval, min.25 ms
Publishing interval, min.25 ms
Number of server methods, max.100
Number of inputs/outputs per server method, max.20
Number of monitored items, recommended max.12 000; for 1 s sampling interval and 1 s send interval
Number of server interfaces, max.10 of each "Server interfaces" / "Companion specification" type and 20 of the type "Reference namespace"
Number of nodes for user-defined server interfaces, max.50 000
Alarms and ConditionsNo
Further protocols
MODBUSYes; MODBUS TCP
Isochronous mode
EquidistanceNo
S7 message functions
Number of login stations for message functions, max.64
number of subscriptions, max.750
number of tags/attributes for subscriptions, max.50 000
Program alarmsYes
Number of configurable program messages, max.10 000; Program messages are generated by the "Program_Alarm" block, ProDiag or GRAPH
Number of loadable program messages in RUN, max.10 000
Number of simultaneously active program alarms
Number of program alarms4 000
Number of alarms for system diagnostics1 000
Test commissioning functions
Joint commission (Team Engineering)No
Status blockYes; Up to 16 simultaneously
Single stepNo
Number of breakpoints20; Breakpoints are only supported in RUN-Solo status
Status/control
Status/control variableYes
Variablesinputs/outputs, bit memories, DBs, peripheral I/Os (without fail-safe), times, counters
Number of variables, max.
of which status variables, max.200; per job
of which control variables, max.200; per job
Forcing
ForcingYes; without fail-safe
Forcing, variablesperipheral inputs/outputs (without fail-safe)
Number of variables, max.200
Diagnostic buffer
presentYes
Number of entries, max.3 200
of which powerfail-proof1 000
Traces
Number of configurable Traces8
Memory size per trace, max.512 kbyte
Interrupts/diagnostics/status information
Diagnostics indication LED
RUN/STOP LEDYes
ERROR LEDYes
MAINT LEDYes
Connection display LINK TX/RXYes
Supported technology objects
Motion ControlNo
Controller
PID_CompactYes; Universal PID controller with integrated optimization
PID_3StepYes; PID controller with integrated optimization for valves
PID-TempYes; PID controller with integrated optimization for temperature
Counting and measuringYes
Standards, approvals, certificates
Highest safety class achievable in safety mode
Performance level according to ISO 13849-1PLe
SIL acc. to IEC 61508SIL 3
Probability of failure (for service life of 20 years and repair time of 100 hours)
Low demand mode: PFDavg in accordance with SIL3< 2.00E-05
High demand/continuous mode: PFH in accordance with SIL3< 1.00E-09
Security
PROFINET Security Class1
Ambient conditions
Ambient temperature during operation
horizontal installation, min.0 °C
horizontal installation, max.60 °C; Display: 50 °C, at an operating temperature of typically 50 °C, the display is switched off
vertical installation, min.0 °C
vertical installation, max.40 °C; Display: 40 °C, at an operating temperature of typically 40 °C, the display is switched off
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
Resistance
Coolants and lubricants
Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold, fungal and dry rot spores (excluding fauna)
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Configuration
Programming
Programming language
LADYes; incl. failsafe
FBDYes; incl. failsafe
STLYes
SCLYes
CFCYes; either CFC or failsafe functionality
GRAPHYes
Know-how protection
User program protection/password protectionYes
Copy protectionNo
Block protectionYes
Access protection
protection of confidential configuration dataYes
Password for displayYes
Protection level: Write protectionYes
Protection level: Read/write protectionYes
Protection level: Write protection for FailsafeYes
Protection level: Complete protectionYes
User administrationYes
Cycle time monitoring
lower limitadjustable minimum cycle time
upper limitadjustable maximum cycle time
Dimensions
Width210 mm
Height147 mm
Depth129 mm
Weights
Weight, approx.2 116 g
Approvals / Certificates