6ES7322-8BF00-0AB0

Siemens 6ES7322-8BF00-0AB0

Kategória produktu
Digitálne moduly
Výrobca
SIEMENS
Produktový rad
S7-300
Supply voltage
Load voltage L+
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Input current
from load voltage L+ (without load), max.90 mA
from backplane bus 5 V DC, max.70 mA
Power loss
Power loss, typ.5 W
Digital outputs
Number of digital outputs8
Short-circuit protectionYes; Electronic
Response threshold, typ.0.75 to 1.5 A
Limitation of inductive shutdown voltage toL+ (-45 V)
Controlling a digital inputYes
Switching capacity of the outputs
on lamp load, max.5 W
Load resistance range
lower limit48 Ω
upper limit3 kΩ
Output voltage
for signal "1", min.L+ (-0.8 to -1.6 V)
Output current
for signal "1" rated value0.5 A
for signal "1" permissible range for 0 to 40 °C, min.10 mA
for signal "1" permissible range for 0 to 40 °C, max.0.6 A
for signal "1" permissible range for 40 to 60 °C, min.10 mA
for signal "1" permissible range for 40 to 60 °C, max.0.6 A
for signal "1" minimum load current10 mA
for signal "0" residual current, max.0.5 mA
Output delay with resistive load
"0" to "1", max.180 µs
"1" to "0", max.245 µs
Parallel switching of two outputs
for upratingNo
for redundant control of a loadOutputs with series diodes only
Switching frequency
with resistive load, max.100 Hz
with inductive load, max.2 Hz
with inductive load (acc. to IEC 60947-5-1, DC13), max.2 Hz
on lamp load, max.10 Hz
Total current of the outputs (per group)
horizontal installation
up to 40 °C, max.4 A
up to 60 °C, max.3 A
vertical installation
up to 40 °C, max.4 A
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Interrupts/diagnostics/status information
Diagnostics functionYes; Parameterizable
Alarms
Diagnostic alarmYes; Parameterizable
Diagnoses
Diagnostic information readableYes
Wire breakYes
short-circuitYes
Fuse blownNo
Missing load voltageYes
Diagnostics indication LED
Rated load voltage PWR (green)No
Fuse OK FSG (green)No
Group error SF (red)Yes
Status indicator digital output (green)Yes; per channel
Channel fault indicator F (red)Yes
Potential separation
Potential separation digital outputs
between the channels, in groups of8
between the channels and backplane busYes; Optocoupler
Isolation
Isolation tested with500 V DC
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.210 g
Approvals / Certificates