6ES7322-1FH00-0AA0

Kategória produktu
Digitálne moduly
Výrobca
SIEMENS
Produktový rad
S7-300
Supply voltage
Load voltage L1
Rated value (AC)230 V; 120/230 V AC
permissible range, lower limit (AC)79 V
permissible range, upper limit (AC)264 V
Input current
from load voltage L1 (without load), max.2 mA
from backplane bus 5 V DC, max.200 mA
Power loss
Power loss, typ.8.6 W
Digital outputs
Number of digital outputs16
Short-circuit protectionYes; Fuse 8 A, 250 V; per group
required current for fuse shutdown, min.40 A
Response time, max.300 ms
Controlling a digital inputYes
Size of motor starters according to NEMA, max.4 NEMA compliant
Spare fuses8 A / quick response
Switching capacity of the outputs
on lamp load, max.50 W
Output voltage
for signal "1" (at max. current), min.L1 (-1.5 V)
for signal "1" (at min. current), min.L1 (-8.5 V)
Output current
for signal "1" rated value1 A
for signal "1" permissible range for 0 to 40 °C, min.10 mA
for signal "1" permissible range for 0 to 40 °C, max.1 A
for signal "1" permissible range for 40 to 60 °C, min.10 mA
for signal "1" permissible range for 40 to 60 °C, max.0.5 A
for signal "1" minimum load current10 mA
for signal "1" permissible surge current, max.20 A; with 2 half waves
for signal "0" residual current, max.2 mA
Parallel switching of two outputs
for upratingNo
for redundant control of a loadYes; only outputs of the same group
Switching frequency
with resistive load, max.10 Hz
with inductive load, max.0.5 Hz
with inductive load (acc. to IEC 60947-5-1, AC15), max.0.5 Hz
on lamp load, max.1 Hz
Total current of the outputs (per group)
horizontal installation
up to 40 °C, max.4 A
up to 60 °C, max.2 A
vertical installation
up to 40 °C, max.2 A
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Interrupts/diagnostics/status information
Diagnostics functionYes; Fuse blown or load voltage missing
Alarms
Diagnostic alarmNo
Diagnoses
Wire breakNo
Short-circuitNo
Fuse blownYes
Missing load voltageNo
Diagnostics indication LED
Rated load voltage PWR (green)No
Fuse OK FSG (green)Yes; Red LED for fuse
Group error SF (red)Yes
Status indicator digital output (green)Yes
Potential separation
Potential separation digital outputs
between the channels, in groups of8
between the channels and backplane busYes; Optocoupler
Isolation
Isolation tested with4 000 V DC
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.275 g
Approvals / Certificates