6AG1322-1CF00-7AA0

Siemens 6AG1322-1CF00-7AA0

SIPLUS S7-300 SM 322 8 DO 48-125 V based on 6ES7322-1CF00-0AA0 with conformal coating, -25…+70 °C, digital output isolated, 8 DO, 48-125 V DC, 1.5 A, 1x 20-pole

Siemens spare part — S7-300 product cancellation (PM410, 1 October 2025); available as a spare part until 2033.

Kategória produktu
Digitálne moduly
Výrobca
SIEMENS
Produktový rad
S7-300
General information
based on6ES7322-1CF00-0AA0
Supply voltage
Load voltage L+
Rated value (DC)48 V; 48 V DC to 125 V DC
permissible range, lower limit (DC)40 V
permissible range, upper limit (DC)140 V
Reverse polarity protectionYes; through fuse
Input current
from load voltage L+ (without load), max.2 mA
from backplane bus 5 V DC, max.100 mA
Power loss
Power loss, typ.7.2 W
Digital outputs
Number of digital outputs8
Short-circuit protectionYes; Electronic
Response threshold, typ.4.4 A
Limitation of inductive shutdown voltage toM (-1 V)
Controlling a digital inputYes
Spare fuses6.3 A / 250 V, quick-response, 5x 20 mm
Switching capacity of the outputs
on lamp load, max.15 W; 15 W (48 V) or 40 W (125 V)
Output voltage
for signal "1", min.L+ (-1.2 V)
Output current
for signal "1" rated value1.5 A
for signal "1" permissible range for 0 to 40 °C, min.10 mA
for signal "1" permissible range for 0 to 40 °C, max.1.5 A
for signal "1" permissible range for 40 to 60 °C, min.10 mA
for signal "1" permissible range for 40 to 60 °C, max.1.5 A
for signal "1" minimum load current10 mA
for signal "1" permissible surge current, max.3 A; for 10 ms
for signal "0" residual current, max.0.5 mA
Output delay with resistive load
"0" to "1", max.2 ms
"1" to "0", max.15 ms
Parallel switching of two outputs
for upratingNo
for redundant control of a loadYes; only outputs of the same group
Switching frequency
with resistive load, max.25 Hz
with inductive load, max.0.5 Hz
with inductive load (acc. to IEC 60947-5-1, DC13), max.0.5 Hz
on lamp load, max.10 Hz
Total current of the outputs (per group)
horizontal installation
up to 40 °C, max.6 A
up to 50 °C, max.4 A
up to 60 °C, max.3 A
up to 70 °C, max.1 A
vertical installation
up to 40 °C, max.4 A
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Interrupts/diagnostics/status information
AlarmsNo
Diagnostics functionNo
Alarms
Diagnostic alarmNo
Diagnoses
Wire breakNo
Short-circuitNo
Fuse blownNo
Missing load voltageNo
Diagnostics indication LED
Rated load voltage PWR (green)No
Fuse OK FSG (green)No
Group error SF (red)Yes
Status indicator digital output (green)Yes
Potential separation
Potential separation digital outputs
between the channelsYes
between the channels, in groups of4
between the channels and backplane busYes; Optocoupler
Isolation
Isolation tested with1 500 V AC
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Railway application
EN 50155Yes; T1 Category 1 Class A/B horizontal mounting position
Ambient conditions
Ambient temperature during operation
min.-25 °C
max.70 °C; = Tmax; for use on railway vehicles according to EN50155, the rated temperature range -25 ... +55 °C (T1) or 60 °C @ UL/ULhaz/ATEX/FM use applies
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.2 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.250 g
Approvals / Certificates