6ES7334-0KE00-0AB0

Kategória produktu
Analógové moduly
Výrobca
SIEMENS
Produktový rad
S7-300
Supply voltage
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
from supply and load voltage L+ (without load), max.80 mA
from backplane bus 5 V DC, max.60 mA
Power loss
Power loss, typ.2 W
Analog inputs
Number of analog inputs4
For voltage measurement2
For resistance measurement4
permissible input voltage for voltage input (destruction limit), max.20 V; continuous; 75 V for max. 1 s (mark to space ratio 1:20)
Constant measurement current for resistance-type transmitter, typ.490 µA; at PT100 (490 µA), at 10 kOhm (105 µa)
Cycle time (all channels) max.85 ms
Input ranges
VoltageYes
CurrentNo
ThermocoupleNo
Resistance thermometerYes
ResistanceYes
Input ranges (rated values), voltages
0 to +10 VYes
Input resistance (0 to 10 V)100 kΩ
Input ranges (rated values), resistance thermometer
Pt 100Yes; only climatic range
Input ranges (rated values), resistors
0 to 10000 ohmsYes
Characteristic linearization
ParameterizableYes
for resistance thermometerPt100 (climate)
Cable length
shielded, max.100 m
Analog outputs
Number of analog outputs2
Voltage output, short-circuit protectionYes
Voltage output, short-circuit current, max.30 mA
Output ranges, voltage
0 to 10 VYes
Load impedance (in rated range of output)
with voltage outputs, min.2.5 kΩ
with voltage outputs, capacitive load, max.1 µF
Cable length
shielded, max.100 m
Analog value generation for the inputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.12 bit
Integration time, parameterizableYes
Integration time (ms)16,67 / 20 ms
Interference voltage suppression for interference frequency f1 in Hz50 / 60 Hz
Analog value generation for the outputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.12 bit
Conversion time (per channel)500 µs
Settling time
for resistive load0.8 ms
for capacitive load0.8 ms
Encoder
Connection of signal encoders
for voltage measurementYes
for resistance measurement with two-wire connectionYes
for resistance measurement with three-wire connectionYes
for resistance measurement with four-wire connectionYes
Errors/accuracies
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)0.7 %; 0 to 10V
Resistance, relative to input range, (+/-)3.5 %; 10 kOhm
Resistance thermometer, relative to input range, (+/-)1 %
Voltage, relative to output range, (+/-)1 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.5 %; 0 to 10V
Resistance, relative to input range, (+/-)2.8 %; 10 kOhm
Resistance thermometer, relative to input range, (+/-)0.8 %
Voltage, relative to output range, (+/-)0.85 %
Interrupts/diagnostics/status information
AlarmsNo
Diagnostics functionNo
Potential separation
Potential separation analog inputs
between the channels and backplane busYes
Potential separation analog outputs
between the channelsNo
between the channels and backplane busYes
between the channels and the power supply of the electronicsYes
Isolation
Isolation tested with500 V DC
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth117 mm
Weights
Weight, approx.200 g
Approvals / Certificates