6AG1331-7SF00-4AB0
SIPLUS S7-300 SM 331 AI 20-pole based on 6ES7331-7SF00-0AB0 with conformal coating, 0…+60 °C, without PTB approval
Kategória produktu
Analógové modulyVýrobca
SIEMENSProduktový rad
S7-300| General information | |
|---|---|
| based on | 6ES7331-7SF00-0AB0 |
| Supply voltage | |
| Load voltage L+ | |
| Rated value (DC) | 24 V |
| Input current | |
| from backplane bus 5 V DC, max. | 120 mA |
| Power loss | |
| Power loss, typ. | 0.6 W |
| Analog inputs | |
| Number of analog inputs | 8; 8x thermocouples; 4x RTD thermoresistors |
| Input ranges | |
| Voltage | Yes |
| Current | No |
| Thermocouple | Yes |
| Resistance thermometer | Yes |
| Resistance | Yes |
| Input ranges (rated values), thermocouples | |
| Type B | Yes |
| Input resistance (Type B) | 10 MΩ |
| Type E | Yes |
| Input resistance (Type E) | 10 MΩ |
| Type J | Yes |
| Input resistance (type J) | 10 MΩ |
| Type K | Yes |
| Input resistance (Type K) | 10 MΩ |
| Type L | Yes |
| Input resistance (Type L) | 10 MΩ |
| Type N | Yes |
| Input resistance (Type N) | 10 MΩ |
| Type R | Yes |
| Input resistance (Type R) | 10 MΩ |
| Type S | Yes |
| Input resistance (Type S) | 10 MΩ |
| Type T | Yes |
| Input resistance (Type T) | 10 MΩ |
| Type U | Yes |
| Input resistance (Type U) | 10 MΩ |
| Input ranges (rated values), resistance thermometer | |
| Ni 100 | Yes |
| Input resistance (Ni 100) | 10 MΩ |
| Pt 100 | Yes |
| Input resistance (Pt 100) | 10 MΩ |
| Pt 200 | Yes |
| Input resistance (Pt 200) | 10 MΩ |
| Cable length | |
| shielded, max. | 200 m; TC: 50 m |
| Analog value generation for the inputs | |
| Integration and conversion time/resolution per channel | |
| Resolution with overrange (bit including sign), max. | 16 bit; 10 bit to 15 bit + sign |
| Integration time, parameterizable | Yes; 2.5 to 100 ms |
| Interference voltage suppression for interference frequency f1 in Hz | 10 to 400 Hz |
| Encoder | |
| Connection of signal encoders | |
| for current measurement as 2-wire transducer | Yes |
| for current measurement as 4-wire transducer | Yes |
| Errors/accuracies | |
| Operational error limit in overall temperature range | |
| Resistance thermometer, relative to input range, (+/-) | 0.09 to 0.04% |
| Basic error limit (operational limit at 25 °C) | |
| Resistance thermometer, relative to input range, (+/-) | 0.1 % |
| Interrupts/diagnostics/status information | |
| Diagnostics function | Yes |
| Diagnoses | |
| Diagnostic information readable | Yes |
| Overrange | Yes |
| Wire-break in signal transmitter cable | Yes |
| Short-circuit of the signal encoder cable | Yes |
| Diagnostics indication LED | |
| Group error SF (red) | Yes |
| Channel fault indicator F (red) | Yes |
| Ex(i) characteristics | |
| Module for Ex(i) protection | Yes |
| maximum values for connecting terminals for gas group IIC | |
| Uo (no-load voltage), max. | 5.9 V |
| Io (short-circuit current), max. | 28.8 mA |
| Po (power output), max. | 41.4 mW |
| Co (permissible external capacity), max. | 43 µF |
| Lo (permissible external inductivity), max. | 40 mH |
| Standards, approvals, certificates | |
| CE mark | Yes |
| UL approval | Yes; File E239877 |
| RCM (formerly C-TICK) | Yes |
| KC approval | Yes |
| EAC (formerly Gost-R) | Yes |
| Use in hazardous areas | |
| ATEX certificate | KEMA 09 ATEX 0077X |
| Railway application | |
| EN 50155 | No |
| Ambient conditions | |
| Ambient temperature during operation | |
| min. | 0 °C; = Tmin |
| max. | 60 °C; = Tmax |
| Ambient temperature during storage/transportation | |
| min. | -40 °C |
| max. | 70 °C |
| Altitude during operation relating to sea level | |
| Installation altitude above sea level, max. | 5 000 m |
| Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
| Relative humidity | |
| With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
| Resistance | |
| Use in stationary industrial systems | |
| to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
| to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * |
| Use on ships/at sea | |
| to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request |
| to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
| to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * |
| Usage in industrial process technology | |
| Against chemically active substances acc. to EN 60654-4 | Yes; Class 3 (excluding trichlorethylene) |
| Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) |
| Remark | |
| Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! |
| Connection method | |
| required front connector | 20-pin |
| Dimensions | |
| Width | 40 mm |
| Height | 125 mm |
| Depth | 120 mm |
| Weights | |
| Weight, approx. | 210 g |
| Approvals / Certificates | |