6ES7322-5GH00-0AB0

Categorie de produs
Module digitale
Producător
SIEMENS
Serie de produse
S7-300
Supply voltage
Mains buffering
Mains/voltage failure stored energy time5 ms
Load voltage L+
Rated value (DC)24 V; 24 / 48
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)57.6 V
Reverse polarity protectionYes
Input current
from supply voltage L+, max.200 mA
from backplane bus 5 V DC, max.100 mA
Power loss
Power loss, typ.2.8 W
Digital outputs
Number of digital outputs16
Short-circuit protectionNo; to be provided externally
Controlling a digital inputYes
Size of motor starters according to NEMA, max.Size 5 according to NEMA
Switching capacity of the outputs
on lamp load, max.2.5 W
Output voltage
for signal "1", min.L+ (-0.25 V)
Output current
for signal "1" rated value0.5 A
for signal "1" permissible range for 0 to 40 °C, max.0.5 A
for signal "1" permissible range for 40 to 60 °C, max.0.5 A
for signal "1" permissible surge current, max.1.5 A; for 50 ms, 1 A 2 s one-time
for signal "0" residual current, max.10 µA
Output delay with resistive load
"0" to "1", max.6 ms
"1" to "0", max.3 ms
Parallel switching of two outputs
for upratingNo
for redundant control of a loadYes
Switching frequency
with resistive load, max.10 Hz
with inductive load, max.0.5 Hz
with inductive load (acc. to IEC 60947-5-1, DC13), max.0.5 Hz
on lamp load, max.0.5 Hz
Total current of the outputs (per group)
horizontal installation
up to 40 °C, max.0.5 A; 8 A per module
up to 60 °C, max.0.5 A; 8 A per module
vertical installation
up to 40 °C, max.0.5 A; 8 A per module
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Interrupts/diagnostics/status information
Diagnostics functionYes; Parameterizable
Alarms
Diagnostic alarmYes; Parameterizable
Diagnoses
Diagnostic information readableYes
Diagnostics indication LED
Group error SF (red)Yes
Status indicator digital output (green)Yes
Potential separation
Potential separation digital outputs
between the channelsYes
between the channels, in groups of1
between the channels and backplane busYes; Optocoupler
between the channels and the power supply of the electronicsYes
Isolation
Isolation tested with1 500 V AC
Connection method
required front connector40-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.260 g
Approvals / Certificates