6ES7322-1CF00-0AA0

Siemens 6ES7322-1CF00-0AA0

SIMATIC S7-300, digital output SM 322, isolated, 8 DO, 48-125 V DC, 1.5 A, 1x 20-pole

Siemens spare part — S7-300 product cancellation (PM410, 1 October 2025); available as a spare part until 2033.

Categorie de produs
Module digitale
Producător
SIEMENS
Serie de produse
S7-300
Supply voltage
Load voltage L+
Rated value (DC)48 V; 48 V DC to 125 V DC
permissible range, lower limit (DC)40 V
permissible range, upper limit (DC)140 V
Reverse polarity protectionYes; through fuse
Input current
from load voltage L+ (without load), max.2 mA
from backplane bus 5 V DC, max.100 mA
Power loss
Power loss, typ.7.2 W
Digital outputs
Number of digital outputs8
Short-circuit protectionYes; Electronic
Response threshold, typ.4.4 A
Limitation of inductive shutdown voltage toM (-1 V)
Controlling a digital inputYes
Spare fuses6.3 A / 250 V, quick-response, 5x 20 mm
Switching capacity of the outputs
on lamp load, max.15 W; 15 W (48 V) or 40 W (125 V)
Output voltage
for signal "1", min.L+ (-1.2 V)
Output current
for signal "1" rated value1.5 A
for signal "1" permissible range for 0 to 40 °C, min.10 mA
for signal "1" permissible range for 0 to 40 °C, max.1.5 A
for signal "1" permissible range for 40 to 60 °C, min.10 mA
for signal "1" permissible range for 40 to 60 °C, max.1.5 A
for signal "1" minimum load current10 mA
for signal "1" permissible surge current, max.3 A; for 10 ms
for signal "0" residual current, max.0.5 mA
Output delay with resistive load
"0" to "1", max.2 ms
"1" to "0", max.15 ms
Parallel switching of two outputs
for upratingNo
for redundant control of a loadYes; only outputs of the same group
Switching frequency
with resistive load, max.25 Hz
with inductive load, max.0.5 Hz
with inductive load (acc. to IEC 60947-5-1, DC13), max.0.5 Hz
on lamp load, max.10 Hz
Total current of the outputs (per group)
horizontal installation
up to 40 °C, max.6 A
up to 50 °C, max.4 A
up to 60 °C, max.3 A
vertical installation
up to 40 °C, max.4 A
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Interrupts/diagnostics/status information
AlarmsNo
Diagnostics functionNo
Alarms
Diagnostic alarmNo
Diagnoses
Wire breakNo
Short-circuitNo
Fuse blownNo
Missing load voltageNo
Diagnostics indication LED
Rated load voltage PWR (green)No
Fuse OK FSG (green)No
Group error SF (red)Yes
Status indicator digital output (green)Yes
Potential separation
Potential separation digital outputs
between the channelsYes
between the channels, in groups of4
between the channels and backplane busYes; Optocoupler
Isolation
Isolation tested with1 500 V AC
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.250 g
Approvals / Certificates