6AG1321-7RD00-4AB0
SIPLUS S7-300 SM 321 4DI NAMUR based on 6ES7321-7RD00-0AB0 with conformal coating, 0…+60 °C, digital input isolated 4 DI; 24 V DC, NAMUR/DIN 19234, for signals from the hazardous area, diagnostics-capable, PTB tested
Categorie de produs
Module digitaleProducător
SIEMENSSerie de produse
S7-300| General information | |
|---|---|
| based on | 6ES7321-7RD00-0AB0 |
| Supply voltage | |
| Load voltage L+ | |
| Rated value (DC) | 24 V |
| Reverse polarity protection | Yes |
| Input current | |
| from load voltage L+ (without load), max. | 50 mA |
| from backplane bus 5 V DC, max. | 80 mA |
| Encoder supply | |
| Type of output voltage | via the inputs |
| Power loss | |
| Power loss, typ. | 1.1 W |
| Digital inputs | |
| Number of digital inputs | 4 |
| Number of NAMUR inputs | 4 |
| Input voltage | |
| Type of input voltage | DC |
| Rated value (DC) | 8.2 V; from internal power circuit supply |
| Input current | |
| on wire-break, max. | 0.1 mA |
| on short-circuit, max. | 8.5 mA |
| for NAMUR encoders | |
| for signal "0", min. | 0.35 mA |
| for signal "0", max. | 1.2 mA |
| for signal "1", min. | 2.1 mA |
| for signal "1", max. | 7 mA |
| Input delay (for rated value of input voltage) | |
| Input frequency (with a time delay of 0.1 ms), max. | 2 kHz |
| for NAMUR inputs | |
| Parameterizable | Yes; 0.1 / 0.5 / 3 / 15 / 20 ms (plus 0.25 ms preparation time) |
| Cable length | |
| unshielded, max. | 200 m |
| Encoder | |
| Connectable encoders | |
| NAMUR encoder | Yes; Two-wire connection |
| Interrupts/diagnostics/status information | |
| Diagnostics function | Yes |
| Diagnoses | |
| Diagnostic information readable | Yes |
| Diagnostics indication LED | |
| Group error SF (red) | Yes |
| Status indicator digital input (green) | Yes |
| Channel fault indicator F (red) | Yes |
| Ex(i) characteristics | |
| Module for Ex(i) protection | Yes |
| maximum values for connecting terminals for gas group IIC | |
| Uo (no-load voltage), max. | 10 V |
| Io (short-circuit current), max. | 14.1 mA |
| Po (power output), max. | 33.7 mW |
| Co (permissible external capacity), max. | 3 µF |
| Lo (permissible external inductivity), max. | 100 mH |
| Potential separation | |
| Potential separation digital inputs | |
| between the channels | Yes; 60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in NON-hazardous area |
| between the channels, in groups of | 1 |
| between the channels and backplane bus | Yes; 60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in NON-hazardous area |
| Between the channels and load voltage L+ | Yes; 60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in NON-hazardous area |
| Standards, approvals, certificates | |
| CE mark | Yes |
| UL approval | Yes; File E239877 |
| RCM (formerly C-TICK) | Yes |
| KC approval | Yes |
| EAC (formerly Gost-R) | Yes |
| Use in hazardous areas | |
| ATEX marking | ATEX II 3 G (2) GD Ex nA [ib Gb] [ib IIIC Db] IIC T4 Gc |
| ATEX certificate | 10 ATEX 0062X |
| Ambient conditions | |
| Ambient temperature during operation | |
| min. | 0 °C; = Tmin |
| max. | 60 °C; = Tmax |
| Ambient temperature during storage/transportation | |
| min. | -40 °C |
| max. | 70 °C |
| Altitude during operation relating to sea level | |
| Installation altitude above sea level, max. | 5 000 m |
| Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
| Relative humidity | |
| With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
| Resistance | |
| Use in stationary industrial systems | |
| to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
| to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * |
| Use on ships/at sea | |
| to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request |
| to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
| to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * |
| Usage in industrial process technology | |
| Against chemically active substances acc. to EN 60654-4 | Yes; Class 3 (excluding trichlorethylene) |
| Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) |
| Remark | |
| Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! |
| Connection method | |
| required front connector | 20-pin |
| Dimensions | |
| Width | 40 mm |
| Height | 125 mm |
| Depth | 120 mm |
| Weights | |
| Weight, approx. | 230 g |
| Approvals / Certificates | |