6AG1314-6EH04-7AB0

SIPLUS S7-300 CPU 314C-2PN/DP based on 6ES7314-6EH04-0AB0 with conformal coating, -25…+70 °C, compact CPU with 192 KB work memory, 24 DI/16 DO, 4 AI, 2 AO, 1 Pt100, 4 high-speed counters (60 kHz), 1st interface MPI/DP 12 Mbps, 2nd interface Ethernet PROFINET, with 2-port switch, integrated power supply 24 V DC, front connector (2x 40-pole) and Micro Memory Card required

Siemens spare part — S7-300 product cancellation (PM410, 1 October 2025); available as a spare part until 2033.

Categorie de produs
CPU
Producător
SIEMENS
Serie de produse
S7-300
General information
Product type designationCPU 314C-2 PN/DP
based on6ES7314-6EH04-0AB0
Product function
Isochronous modeYes; For PROFINET only
Engineering with
Programming packageSTEP 7 V5.5 or higher with HSP 191
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
external protection for power supply lines (recommendation)Miniature circuit breaker, type C; min. 2 A; miniature circuit breaker type B, min. 4 A
Mains buffering
Mains/voltage failure stored energy time5 ms
Repeat rate, min.1 s
Load voltage L+
Digital inputs
Rated value (DC)24 V
Reverse polarity protectionYes
Digital outputs
Rated value (DC)24 V
Reverse polarity protectionNo
Input current
Current consumption (rated value)850 mA
Current consumption (in no-load operation), typ.190 mA
Inrush current, typ.5 A
I²t0.7 A²·s
Digital inputs
from load voltage L+ (without load), max.80 mA
Digital outputs
from load voltage L+, max.50 mA
Power loss
Power loss, typ.14 W
Storage
Work memory
integrated192 kbyte
expandableNo
Load memory
Plug-in (MMC)Yes
Plug-in (MMC), max.8 Mbyte
Data management on MMC (after last programming), min.10 a
Backup
presentYes; Guaranteed by MMC (maintenance-free)
without batteryYes; Program and data
CPU processing times
for bit operations, typ.0.06 µs
for word operations, typ.0.12 µs
for fixed point arithmetic, typ.0.16 µs
for floating point arithmetic, typ.0.59 µs
CPU-blocks
Number of elements (total)1 024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used.
DB
Number, max.1 024; Number range: 1 to 16000
Size, max.64 kbyte
FB
Number, max.1 024; Number range: 0 to 7999
Size, max.64 kbyte
FC
Number, max.1 024; Number range: 0 to 7999
Size, max.64 kbyte
OB
Number, max.see instruction list
Size, max.64 kbyte
Number of free cycle OBs1; OB 1
Number of time alarm OBs1; OB 10
Number of delay alarm OBs2; OB 20, 21
Number of cyclic interrupt OBs4; OB 32, 33, 34, 35
Number of process alarm OBs1; OB 40
Number of DPV1 alarm OBs3; OB 55, 56, 57
Number of isochronous mode OBs1; OB 61; only for PROFINET
Number of startup OBs1; OB 100
Number of asynchronous error OBs6; OB 80, 82, 83, 85, 86, 87 (OB83 only for PROFINET IO)
Number of synchronous error OBs2; OB 121, 122
Nesting depth
per priority class16
additional within an error OB4
Counters, timers and their retentivity
S7 counter
Number256
Retentivity
adjustableYes
presetZ 0 to Z 7
Counting range
can be setYes
lower limit0
upper limit999
IEC counter
presentYes
TypeSFB
NumberUnlimited (limited only by RAM capacity)
S7 timer
Number256
Retentivity
adjustableYes
presetNo retentivity
Time range
lower limit10 ms
upper limit9 990 s
IEC timer
presentYes
TypeSFB
NumberUnlimited (limited only by RAM capacity)
Data areas and their retentivity
Retentive data area (incl. timers, counters, flags), max.64 kbyte
Flag
Size, max.256 byte
Retentivity availableYes; MB 0 to MB 255
Retentivity presetMB 0 to MB 15
Number of clock memories8; 1 memory byte
Data blocks
Retentivity adjustableYes; via non-retain property on DB
Retentivity presetYes
Local data
per priority class, max.32 kbyte; Max. 2048 bytes per block
Address area
I/O address area
Inputs2 048 byte
Outputs2 048 byte
of which distributed
Inputs2 003 byte
Outputs2 010 byte
Process image
Inputs2 048 byte
Outputs2 048 byte
Inputs, adjustable2 048 byte
Outputs, adjustable2 048 byte
Inputs, default256 byte
Outputs, default256 byte
Subprocess images
Number of subprocess images, max.1; With PROFINET IO, the length of the user data is limited to 1600 bytes
Digital channels
Inputs16 048
of which central1 016
Outputs16 096
of which central1 008
Analog channels
Inputs1 006
of which central253
Outputs1 007
of which central250
Hardware configuration
Number of expansion units, max.3
Number of DP masters
integrated1
via CP4
Number of operable FMs and CPs (recommended)
FM8
CP, PtP8
CP, LAN10
Rack
Racks, max.4
Modules per rack, max.8; In rack 3 max. 7
Time of day
Clock
Hardware clock (real-time)Yes
retentive and synchronizableYes
Backup time6 wk; At 40 °C ambient temperature
Deviation per day, max.10 s; Typ.: 2 s
Behavior of the clock following POWER-ONClock continues running after POWER OFF
Behavior of the clock following expiry of backup periodthe clock continues at the time of day it had when power was switched off
Operating hours counter
Number1
Number/Number range0
Range of values0 to 2^31 hours (when using SFC 101)
Granularity1 h
retentiveYes; Must be restarted at each restart
Clock synchronization
supportedYes
to MPI, masterYes
on MPI, deviceYes
to DP, masterYes; With DP slave only slave clock
on DP, deviceYes
in AS, masterYes
in AS, deviceYes
on Ethernet via NTPYes; As client
Digital inputs
Number of digital inputs24
of which inputs usable for technological functions16
integrated channels (DI)24
Input characteristic curve in accordance with IEC 61131, type 1Yes
Number of simultaneously controllable inputs
horizontal installation
up to 40 °C, max.24
up to 60 °C, max.12; up to 70 °C
vertical installation
up to 40 °C, max.12
Input voltage
Rated value (DC)24 V
for signal "0"-3 to +5V
for signal "1"+15 to +30 V
Input current
for signal "1", typ.8 mA
Input delay (for rated value of input voltage)
for standard inputs
parameterizableYes; 0.1 / 0.3 / 3 / 15 ms (You can reconfigure the input delay of the standard inputs during program runtime. Please note that under certain circumstances your newly set filter time may not be effective until the next filter cycle.)
Rated value3 ms
for technological functions
at "0" to "1", max.8 µs; Minimum pulse width/minimum pause between pulses at maximum counting frequency
Cable length
shielded, max.1 000 m; 50 m for technological functions
unshielded, max.600 m; for technological functions: No
for technological functions
shielded, max.50 m; at maximum count frequency
unshielded, max.not allowed
Digital outputs
Number of digital outputs16
of which high-speed outputs4; Notice: You cannot connect the fast outputs of your CPU in parallel
integrated channels (DO)16
Short-circuit protection
Response threshold, typ.1 A
Limitation of inductive shutdown voltage toL+ (-48 V)
Controlling a digital inputYes
Switching capacity of the outputs
on lamp load, max.5 W
Load resistance range
lower limit48 Ω
upper limit4 kΩ
Output voltage
for signal "1", min.L+ (-0.8 V)
Output current
for signal "1" rated value500 mA
for signal "1" permissible range, min.5 mA
for signal "1" permissible range, max.0.6 A
for signal "1" minimum load current5 mA
for signal "0" residual current, max.0.5 mA
Parallel switching of two outputs
for upratingNo
for redundant control of a loadYes
Switching frequency
with resistive load, max.100 Hz
with inductive load, max.0.5 Hz
on lamp load, max.100 Hz
of the pulse outputs, with resistive load, max.2.5 kHz
Total current of the outputs (per group)
horizontal installation
up to 40 °C, max.3 A
up to 60 °C, max.2 A; 1.5 A @ > 60 °C
vertical installation
up to 40 °C, max.2 A
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Analog inputs
Number of analog inputs5
For voltage/current measurement4
For resistance/resistance thermometer measurement1
integrated channels (AI)5; 4x current/voltage, 1x resistance
permissible input voltage for current input (destruction limit), max.5 V; Permanent
permissible input voltage for voltage input (destruction limit), max.30 V; Permanent
permissible input current for voltage input (destruction limit), max.0.5 mA; Permanent
permissible input current for current input (destruction limit), max.50 mA; Permanent
Electrical input frequency, max.400 Hz
No-load voltage for resistance-type transmitter, typ.3.3 V
Constant measurement current for resistance-type transmitter, typ.1.25 mA
Technical unit for temperature measurement adjustableYes; Degrees Celsius / degrees Fahrenheit / Kelvin
Input ranges
VoltageYes; ±10 V / 100 kΩ; 0 V to 10 V / 100 kΩ
CurrentYes; ±20 mA / 100 Ω; 0 mA to 20 mA / 100 Ω; 4 mA to 20 mA / 100 Ω
Resistance thermometerYes; Pt 100 / 10 MΩ
ResistanceYes; 0 Ω to 600 Ω / 10 MΩ
Input ranges (rated values), voltages
0 to +10 VYes
Input resistance (0 to 10 V)100 kΩ
Input ranges (rated values), currents
0 to 20 mAYes
Input resistance (0 to 20 mA)100 Ω
-20 mA to +20 mAYes
Input resistance (-20 mA to +20 mA)100 Ω
4 mA to 20 mAYes
Input resistance (4 mA to 20 mA)100 Ω
Input ranges (rated values), resistance thermometer
Pt 100Yes
Input resistance (Pt 100)10 MΩ
Input ranges (rated values), resistors
0 to 600 ohmsYes
Input resistance (0 to 600 ohms)10 MΩ
Thermocouple (TC)
Temperature compensation
ParameterizableNo
Characteristic linearization
ParameterizableYes; by software
for resistance thermometerPt 100
Cable length
shielded, max.100 m
Analog outputs
integrated channels (AO)2
Voltage output, short-circuit protectionYes
Voltage output, short-circuit current, max.55 mA
Current output, no-load voltage, max.14 V
Output ranges, voltage
0 to 10 VYes
-10 V to +10 VYes
Output ranges, current
0 to 20 mAYes
-20 mA to +20 mAYes
4 mA to 20 mAYes
Connection of actuators
for voltage output two-wire connectionYes; Without compensation of the line resistances
for voltage output four-wire connectionNo
for current output two-wire connectionYes
Load impedance (in rated range of output)
with voltage outputs, min.1 kΩ
with voltage outputs, capacitive load, max.0.1 µF
with current outputs, max.300 Ω
with current outputs, inductive load, max.0.1 mH
Destruction limits against externally applied voltages and currents
Voltages at the outputs towards MANA16 V; Permanent
Current, max.50 mA; Permanent
Cable length
shielded, max.200 m
Analog value generation for the inputs
Measurement principleActual value encryption (successive approximation)
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.12 bit
Integration time, parameterizableYes; 16.6 / 20 ms
Interference voltage suppression for interference frequency f1 in Hz50 / 60 Hz
Time constant of the input filter0.38 ms
Basic execution time of the module (all channels released)1 ms
Analog value generation for the outputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.12 bit
Conversion time (per channel)1 ms
Settling time
for resistive load0.6 ms
for capacitive load1 ms
for inductive load0.5 ms
Encoder
Connection of signal encoders
for voltage measurementYes
for current measurement as 2-wire transducerYes; with external supply
for current measurement as 4-wire transducerYes
for resistance measurement with two-wire connectionYes; Without compensation of the line resistances
for resistance measurement with three-wire connectionNo
for resistance measurement with four-wire connectionNo
Connectable encoders
2-wire sensorYes
permissible quiescent current (2-wire sensor), max.1.5 mA
Errors/accuracies
Temperature error (relative to input range), (+/-)0.006 %/K
Crosstalk between the inputs, min.60 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.06 %
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-)0.1 %
Linearity error (relative to output range), (+/-)0.15 %
Temperature error (relative to output range), (+/-)0.01 %/K
Crosstalk between the outputs, min.60 dB
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-)0.06 %
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)1.6 %
Current, relative to input range, (+/-)1.6 %
Resistance, relative to input range, (+/-)1.6 %
Voltage, relative to output range, (+/-)1.6 %
Current, relative to output range, (+/-)1.6 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.8 %; Linearity error ±0.06 %
Current, relative to input range, (+/-)0.8 %; Linearity error ±0.06 %
Resistance, relative to input range, (+/-)0.8 %; Linearity error ±0.2 %
Resistance thermometer, relative to input range, (+/-)0.8 %
Voltage, relative to output range, (+/-)0.8 %
Current, relative to output range, (+/-)0.8 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.30 dB
Common mode interference, min.40 dB
Interfaces
Number of PROFINET interfaces1; 2 ports (switch) RJ45
Number of RS 485 interfaces1; Combined MPI / PROFIBUS DP
Number of RS 422 interfaces0
1. Interface
Interface typeIntegrated RS 485 interface
IsolatedYes
Interface types
RS 485Yes
Output current of the interface, max.200 mA
Protocols
MPIYes
PROFIBUS DP masterYes
PROFIBUS DP deviceYes
Point-to-point connectionNo
MPI
Transmission rate, max.12 Mbit/s
Services
PG/OP communicationYes
RoutingYes
Global data communicationYes
S7 basic communicationYes
S7 communicationYes
S7 communication, as clientNo; but via CP and loadable FB
S7 communication, as serverYes
PROFIBUS DP master
Transmission rate, max.12 Mbit/s
max. number of DP devices124
Services
PG/OP communicationYes
RoutingYes
Global data communicationNo
S7 basic communicationYes; I blocks only
S7 communicationYes
S7 communication, as clientNo
S7 communication, as serverYes
EquidistanceYes
Isochronous modeNo
SYNC/FREEZEYes
activation/deactivation of DP devicesYes
max. number of DP devices that can be activated/deactivated at the same time8
Direct data exchange (slave-to-slave communication)Yes; as subscriber
DPV1Yes
Address area
Inputs, max.2 kbyte
Outputs, max.2 kbyte
User data per DP device
Inputs, max.244 byte
Outputs, max.244 byte
PROFIBUS DP device
Transmission rate, max.12 Mbit/s
automatic baud rate searchYes; only with passive interface
Address area, max.32
User data per address area, max.32 byte
Services
PG/OP communicationYes
RoutingYes; Only with active interface
Global data communicationNo
S7 basic communicationNo
S7 communicationYes
S7 communication, as clientNo
S7 communication, as serverYes; Connection configured on one side only
Direct data exchange (slave-to-slave communication)Yes
DPV1No
Transfer memory
Inputs244 byte
Outputs244 byte
2. Interface
Interface typePROFINET
IsolatedYes
automatic detection of transmission rateYes; 10/100 Mbit/s
AutonegotiationYes
AutocrossingYes
Change of IP address at runtime, supportedYes
Interface types
RJ 45 (Ethernet)Yes
Number of ports2
integrated switchYes
Protocols
MPINo
PROFINET IO ControllerYes; Also simultaneously with IO-Device functionality
PROFINET IO DeviceYes; Also simultaneously with IO Controller functionality
PROFINET CBAYes
PROFIBUS DP masterNo
PROFIBUS DP deviceNo
Open IE communicationYes; Via TCP/IP, ISO on TCP, and UDP
Web serverYes
Media redundancyYes
PROFINET IO Controller
Transmission rate, max.100 Mbit/s
Services
PG/OP communicationYes
RoutingYes
S7 communicationYes; With loadable FBs, max. configurable connections: 10, max. number of instances: 32
Isochronous modeYes; OB 61
IRTYes
Shared deviceYes
Prioritized startupYes
Number of IO devices with prioritized startup, max.32
Number of connectable IO Devices, max.128
Of which IO devices with IRT, max.64
of which in line, max.64
Number of IO Devices with IRT and the option "high flexibility"128
of which in line, max.61
Number of connectable IO Devices for RT, max.128
of which in line, max.128
Activation/deactivation of IO DevicesYes
Number of IO Devices that can be simultaneously activated/deactivated, max.8
IO Devices changing during operation (partner ports), supportedYes
Number of IO Devices per tool, max.8
Device replacement without swap mediumYes
Send cycles250 μs, 500 μs,1 ms; 2 ms, 4 ms (not in the case of IRT with "high flexibility" option)
Updating time250 µs to 512 ms (depending on the operating mode, see Manual "S7-300 CPU 31xC and CPU 31x, technical Data" for more details)
Address area
Inputs, max.2 kbyte
Outputs, max.2 kbyte
User data consistency, max.1 024 byte
PROFINET IO Device
Services
PG/OP communicationYes
RoutingYes
S7 communicationYes; With loadable FBs, max. configurable connections: 10, max. number of instances: 32
Isochronous modeNo
IRTYes
PROFIenergyYes; With SFB 73 / 74 prepared for loadable PROFIenergy standard FB for I-Device
Shared deviceYes
Number of IO Controllers with shared device, max.2
Transfer memory
Inputs, max.1 440 byte; Per IO Controller with shared device
Outputs, max.1 440 byte; Per IO Controller with shared device
Submodules
Number, max.64
User data per submodule, max.1 024 byte
PROFINET CBA
acyclic transmissionYes
cyclic transmissionYes
Open IE communication
Number of connections, max.8
Local port numbers used at the system end0, 20, 21, 23, 25, 80, 102, 135, 161, 443, 8080, 34962, 34963, 34964, 65532, 65533, 65534, 65535
Keep-alive function, supportedYes
Protocols
PROFIsafeNo
Redundancy mode
Media redundancy
Switchover time on line break, typ.200 ms; PROFINET MRP
Number of stations in the ring, max.50
Open IE communication
TCP/IPYes; via integrated PROFINET interface and loadable FBs
Number of connections, max.8
Data length for connection type 01H, max.1 460 byte
Data length for connection type 11H, max.32 768 byte
several passive connections per port, supportedYes
ISO-on-TCP (RFC1006)Yes; via integrated PROFINET interface and loadable FBs
Number of connections, max.8
Data length, max.32 768 byte
UDPYes; via integrated PROFINET interface and loadable FBs
Number of connections, max.8
Data length, max.1 472 byte
Web server
supportedYes
User-defined websitesYes
Number of HTTP clients5
Communication functions
PG/OP communicationYes
Data record routingYes
Global data communication
supportedYes
Number of GD loops, max.8
Number of GD packets, max.8
Number of GD packets, transmitter, max.8
Number of GD packets, receiver, max.8
Size of GD packets, max.22 byte
Size of GD packet (of which consistent), max.22 byte
S7 basic communication
supportedYes
User data per job, max.76 byte
User data per job (of which consistent), max.76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)
S7 communication
supportedYes
as serverYes
as clientYes; via integrated PROFINET interface and loadable FB or via CP and loadable FB
User data per job, max.See online help of STEP 7 (shared parameters of the SFBs/FBs and of the SFCs/FCs of S7 Communication)
S5 compatible communication
supportedYes; via CP and loadable FC
PROFINET CBA (at set setpoint communication load)
Setpoint for the CPU communication load50 %
Number of remote interconnection partners32
number of master/device functions30
total of all master/device connections1 000
data length of all incoming master/device connections, max.4 000 byte
data length of all outgoing master/device connections, max.4 000 byte
Number of device-internal and PROFIBUS interconnections500
Data length of device-internal und PROFIBUS interconnections, max.4 000 byte
Data length per connection, max.1 400 byte
Remote interconnections with cyclic transmission
Transmission frequency: Transmission interval, min.10 ms
Number of incoming interconnections200
Number of outgoing interconnections200
Data length of all incoming interconnections, max.2 000 byte
Data length of all outgoing interconnections, max.2 000 byte
Data length per connection, max.450 byte
HMI variables via PROFINET (acyclic)
Number of stations that can log on for HMI variables (PN OPC/iMap)3; 2x PN OPC/1x iMap
HMI variable updating500 ms
Number of HMI variables200
Data length of all HMI variables, max.2 000 byte
PROFIBUS proxy functionality
supportedYes
Number of linked PROFIBUS devices16
Data length per connection, max.240 byte; Slave-dependent
Number of connections
overall12
usable for PG communication11
reserved for PG communication1
adjustable for PG communication, min.1
adjustable for PG communication, max.11
usable for OP communication11
reserved for OP communication1
adjustable for OP communication, min.1
adjustable for OP communication, max.11
usable for S7 basic communication8
reserved for S7 basic communication0
adjustable for S7 basic communication, min.0
adjustable for S7 basic communication, max.8
usable for S7 communication10
reserved for S7 communication0
adjustable for S7 communication, min.0
adjustable for S7 communication, max.10
total number of instances, max.32
usable for routingX1 as MPI: max. 10; X1 as DP master: max. 24; X1 as DP slave (active): max. 14; X2 as PROFINET: 24 max.
S7 message functions
Number of login stations for message functions, max.12; Depending on the configured connections for PG/OP and S7 basic communication
Process diagnostic messagesYes
simultaneously active Alarm_S blocks, max.300
Test commissioning functions
Status blockYes; Up to 2 simultaneously
Single stepYes
Number of breakpoints4
Status/control
Status/control variableYes
VariablesInputs, outputs, memory bits, DB, times, counters
Number of variables, max.30
of which status variables, max.30
of which control variables, max.14
Forcing
ForcingYes
Forcing, variablesInputs, outputs
Number of variables, max.10
Diagnostic buffer
presentYes
Number of entries, max.
can be setNo
of which powerfail-proof100; Only the last 100 entries are retained
Number of entries readable in RUN, max.499
can be setYes; From 10 to 499
preset10
Service data
Can be read outYes
Interrupts/diagnostics/status information
Diagnostics indication LED
Status indicator digital input (green)Yes
Status indicator digital output (green)Yes
Integrated Functions
Counter
Number of counters4; See "Technological Functions" manual
Counting frequency, max.60 kHz
Frequency measurementYes
Number of frequency meters4; up to 60 kHz (see "Technological Functions" manual)
controlled positioningYes
integrated function blocks (closed-loop control)Yes; PID controller (see "Technological Functions" manual)
PID controllerYes
Number of pulse outputs4; Pulse width modulation up to 2.5 kHz (see "Technological Functions" Manual)
Limit frequency (pulse)2.5 kHz
Potential separation
Potential separation digital inputs
Potential separation digital inputsYes
between the channelsNo
between the channels and backplane busYes
Potential separation digital outputs
Potential separation digital outputsYes
between the channelsYes
between the channels, in groups of8
between the channels and backplane busYes
Potential separation analog inputs
Potential separation analog inputsYes; common for analog I/O
between the channelsNo
between the channels and backplane busYes
Potential separation analog outputs
Potential separation analog outputsYes; common for analog I/O
between the channelsNo
between the channels and backplane busYes
Isolation
Isolation tested with600 V DC
Standards, approvals, certificates
CE markYes
KC approvalYes
EAC (formerly Gost-R)Yes
Ambient conditions
Ambient temperature during operation
min.-25 °C; = Tmin
max.70 °C; = Tmax; @ 60°C for UL/ATEX/FM use
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Configuration
Configuration software
STEP 7Yes; V5.5 or higher
Programming
Command setsee instruction list
Nesting levels8
System functions (SFC)see instruction list
System function blocks (SFB)see instruction list
Programming language
LADYes
FBDYes
STLYes
SCLYes
CFCYes
GRAPHYes
HiGraph®Yes
Know-how protection
User program protection/password protectionYes
Block encryptionYes; With S7 block Privacy
Dimensions
Width120 mm
Height125 mm
Depth130 mm
Weights
Weight, approx.730 g
Approvals / Certificates