6GK7343-1GX31-0XE0

Categorie de produs
Comunicație
Producător
SIEMENS
Serie de produse
S7-300
product type designationCP 343-1 Advanced
product brand nameSIMATIC NET
Technical Product Detail Pagehttps://i.siemens.com/1P6GK7343-1GX31-0XE0
transfer rate
transfer rate
at the 1st interface10 ... 1000 Mbit/s
at the 2nd interface10 ... 100 Mbit/s
interfaces
number of interfaces / according to Industrial Ethernet3
number of electrical connections
at the 1st interface / according to Industrial Ethernet1
at the 2nd interface / according to Industrial Ethernet2
for power supply1
type of electrical connection
at the 1st interface / according to Industrial EthernetRJ45 port
at the 2nd interface / according to Industrial EthernetRJ45 port
type of electrical connection
for power supply2-pole plugable terminal block
design of the removable storage
C-PLUGYes
supply voltage, current consumption, power loss
type of voltage / of the supply voltageDC
supply voltage / 1 / from backplane bus5 V
supply voltage / external24 V
supply voltage / external / at DC / rated value24 V
relative positive tolerance / at DC / at 24 V20 %
relative negative tolerance / at DC / at 24 V15 %
consumed current
from backplane bus / at DC / at 5 V / typical0.14 A
from external supply voltage / at DC / at 24 V / typical0.48 A
from external supply voltage / at DC / at 24 V / maximum0.62 A
power loss [W]14.7 W
ambient conditions
ambient temperature
for vertical installation / during operation0 ... 40 °C
for horizontally arranged busbars / during operation0 ... 60 °C
during storage-40 ... +70 °C
during transport-40 ... +70 °C
relative humidity
at 25 °C / without condensation / during operation / maximum95 %
protection class IPIP20
design, dimensions and weights
module formatCompact module
width80 mm
height125 mm
depth120 mm
net weight0.45 kg
fastening method
S7-300 rail mountingYes
performance data / open communication
number of possible connections / for open communication / by means of SEND/RECEIVE blocks / maximum16
data volume
as user data per ISO connection / for open communication / by means of SEND/RECEIVE blocks / maximum8 Kibyte
as user data per ISO on TCP connection / for open communication / by means of SEND/RECEIVE blocks / maximum8 Kibyte
as user data per TCP connection / for open communication / by means of SEND/RECEIVE blocks / maximum8 Kibyte
as user data per UDP connection / for open IE communication / by means of SEND/RECEIVE blocks / maximum2 Kibyte
number of Multicast stations16
performance data / S7 communication
number of possible connections / for S7 communication
maximum16
performance data / multi-protocol mode
number of active connections / with multi-protocol mode48
performance data / IT functions
number of possible connections
as client / by means of FTP / maximum10
as server / by means of FTP / maximum2
number of possible connections
as server / by means of HTTP / maximum4
as email client / maximum1
data volume / as user data for email / maximum8 Kibyte
storage capacity / of the user memory
as flash memory file system28 Mibyte
as RAM30 Mibyte
number of possible write cycles / of the flash memory cells100000
performance data / PROFINET communication / as PN IO controller
product function / PROFINET IO controllerYes
number of PN IO devices / on PROFINET IO controller / operable / total128
number of PN IO IRT devices / on PROFINET IO controller / operable128
number of external PN IO lines / with PROFINET / per rack1
data volume
as user data for input variables / as PROFINET IO controller / maximum4 Kibyte
as user data for output variables / as PROFINET IO controller / maximum4 Kibyte
as user data for input variables per PN IO device / as PROFINET IO controller / maximum1433 byte
as user data for output variables per PN IO device / as PROFINET IO controller / maximum1433 byte
as user data for input variables per PN IO device / for each sub-module as PROFINET IO controller / maximum240 byte
as user data for output variables per PN IO device / for each sub-module as PROFINET IO controller / maximum240 byte
performance data / PROFINET communication / as PN IO device
product function / PROFINET IO deviceYes
data volume
as user data for input variables / as PROFINET IO device / maximum1024 byte
as user data for output variables / as PROFINET IO device / maximum1024 byte
as user data for input variables / for each sub-module as PROFINET IO device240 byte
as user data for output variables / for each sub-module as PROFINET IO device240 byte
as user data for the consistency area for each sub-module240 byte
number of submodules / per PROFINET IO-Device32
performance data / PROFINET CBA
number of remote connection partners / with PROFINET CBA64
number of connections / with PROFINET CBA / total1000
data volume
as user data for digital inputs / with PROFINET CBA / maximum8 Kibyte
as user data for digital outputs / with PROFINET CBA / maximum8 Kibyte
as user data for arrays and data types / in the case of acyclic transmission / with PROFINET CBA / maximum8 Kibyte
as user data for arrays and data types / with PROFINET CBA / with cyclical transfer / maximum250 byte
as user data for arrays and data types / with PROFINET CBA / in the case of local interconnection / maximum2400 byte
performance data / PROFINET CBA / remote interconnection / with acyclic transfer
update time / of the remote interconnections / in the case of acyclic transmission / with PROFINET CBA100 ms
number of remote connections to input variables / in the case of acyclic transmission / with PROFINET CBA / maximum128
number of remote connections to output variables / in the case of acyclic transmission / with PROFINET CBA / maximum128
data volume
as user data for remote interconnections with input variables / in the case of acyclic transmission / with PROFINET CBA8 Kibyte
as user data for remote interconnections with output variables / in the case of acyclic transmission / with PROFINET CBA8 Kibyte
performance data / PROFINET CBA / remote interconnection / with cyclic transfer
update time / of the remote interconnections / with cyclical transfer / with PROFINET CBA8 ms
number of remote connections to input variables / with PROFINET CBA / with cyclic transfer / maximum200
number of remote connections to output variables / with cyclical transfer / with PROFINET CBA / maximum200
data volume
as user data for remote interconnections with input variables / with cyclical transfer / with PROFINET CBA / maximum2000 byte
as user data for remote interconnections with output variables / with cyclical transfer / with PROFINET CBA / maximum2000 byte
performance data / PROFINET CBA / HMI variables via PROFINET / acyclic
number of connectable HMI stations / for HMI variables / in the case of acyclic transmission / with PROFINET CBA3
update time / of the HMI variables / in the case of acyclic transmission / with PROFINET CBA500 ms
number of HMI variables / in the case of acyclic transmission / with PROFINET CBA / maximum200
data volume / as user data for HMI variables / in the case of acyclic transmission / with PROFINET CBA / maximum8 Kibyte
performance data / PROFINET CBA / device-internal interconnections
number of internal connections / with PROFINET CBA / maximum256
data volume / of the internal connections / with PROFINET CBA / maximum2400 byte
performance data / PROFINET CBA / interconnections to constants
number of connections with constants / with PROFINET CBA / maximum200
data volume / as user data for interconnections with constants / with PROFINET CBA / maximum4096 byte
performance data / PROFINET CBA / PROFIBUS proxy functionality
product function / with PROFINET CBA / PROFIBUS proxy functionalityNo
performance data / telecontrol
protocol / is supported
TCP/IPYes
product functions / management, configuration, engineering
product function / MIB supportYes
protocol / is supported
SNMP v1Yes
SNMP v3Yes
DCPYes
LLDPYes
configuration software
requiredSTEP7 V5.5 SP2 HF1 or higher / STEP 7 Professional V12 (TIA Portal) or higher
for PROFINET CBA / requiredSIMATIC iMap V3.0 SP4 and higher
identification & maintenance function
I&M0 - device-specific informationYes
I&M1 - higher level designation/location designationYes
product function / is supported / identification linkYes; acc. to IEC 61406-1:2022
product functions / diagnostics
product function / web-based diagnosticsYes
product functions / switch
product feature / switchYes
product function
switch-managedNo
with IRT / PROFINET IO switchYes
configuration with STEP 7Yes
product functions / redundancy
product function
ring redundancyYes
redundancy managerYes
protocol / is supported / Media Redundancy Protocol (MRP)Yes
product functions / security
firewall versionstateful inspection
product function / with VPN connectionIPSec
type of encryption algorithms / with VPN connectionAES-256, AES-192, AES-128, 3DES-168, DES-56
type of authentication procedure / with VPN connectionPreshared key (PSK), X.509v3 certificates
type of hashing algorithms / with VPN connectionMD5, SHA-1
number of possible connections / with VPN connection32
product function
password protection for Web applicationsYes
ACL - IP-basedYes
ACL - IP-based for PLC/routingYes
switch-off of non-required servicesYes
blocking of communication via physical portsYes
log file for unauthorized accessNo
product functions / time
product function / SICLOCK supportYes
product function / pass on time synchronizationYes
protocol / is supported
NTPYes
standards, specifications, approvals
certificate of suitability / CE markingYes
certificate of suitability / UKCA markingYes
certificate of suitability / KC approvalYes
certificate of suitability / Regulatory Compliance Mark (RCM)Yes
certificate of suitability / RoHS conformityYes
certificate of suitability / EAC approvalYes
standards, specifications, approvals / hazardous environments / header
certificate of suitability / ATEXYes
certificate of suitability / IECExYes
certificate of suitability / ULhazloc approvalYes
certificate of suitability / CCC / for hazardous zone according to GB standardYes
certificate of suitability / FM registrationYes
standards, specifications, approvals / marine classification / header
Marine classification association / Polski Rejestr Statkow (PRS)Yes
standards, specifications, approvals / Environmental Product Declaration
Environmental Product DeclarationYes
global warming potential [CO2 eq]
total153.1 kg
during manufacturing26.4 kg
during operation126.16 kg
after end of life0.54 kg
further information / internet links
internet link
to website: Selection guide for cables and connectorshttps://support.industry.siemens.com/cs/ww/en/view/109766358
to web page: selection aid TIA Selection Toolhttps://www.siemens.com/tstcloud
to website: Industrial communicationhttps://www.siemens.com/simatic-net
to web page: SiePortalhttps://sieportal.siemens.com/
to website: Image databasehttps://www.automation.siemens.com/bilddb
to website: CAx-Download-Managerhttps://siemens.com/cax
to website: Industry Online Supporthttps://support.industry.siemens.com
security information
security informationSiemens provides products and solutions with industrial cybersecurity functions that support the secure operation of plants, systems, machines and networks. In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement - and continuously maintain - a holistic, state-of-the-art industrial cybersecurity concept. Siemens’ products and solutions constitute one element of such a concept. Customers are responsible for preventing unauthorized access to their plants, systems, machines and networks. Such systems, machines and components should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures (e.g. firewalls and/or network segmentation) are in place. For additional information on industrial cybersecurity measures that may be implemented, please visit www.siemens.com/cybersecurity-industry. Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to cyber threats. To stay informed about product updates, subscribe to the Siemens Industrial Cybersecurity RSS Feed under https://www.siemens.com/cert. (V4.7)
Approvals / Certificates