6ES7331-7TB10-0AB0

Siemens 6ES7331-7TB10-0AB0

SIMATIC DP, HART analog input SM 331, 2 AI, 0/4 - 20 mA HART from HART revision 5.0, for ET200M with IM 153-2, 1 x 20-pole

Siemens spare part — S7-300 product cancellation (PM410, 1 October 2025); available as a spare part until 2033.

Categorie de produs
Module analogice
Producător
SIEMENS
Serie de produse
S7-300
Supply voltage
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.180 mA
from backplane bus 5 V DC, max.100 mA
Output voltage
Power supply to the transmitters
presentYes
Rated value (DC)15 V; at 22 mA
short-circuit proofYes; approx. 30 mA
No-load voltage (DC)29.6 V
Power loss
Power loss, typ.4.5 W
Analog inputs
Number of analog inputs2
permissible input current for current input (destruction limit), max.40 mA
Input ranges (rated values), currents
0 to 20 mAYes
Input resistance (0 to 20 mA)50 Ω
4 mA to 20 mAYes
Input resistance (4 mA to 20 mA)50 Ω
Cable length
shielded, max.400 m
Analog value generation for the inputs
Measurement principleSigma Delta
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit; 10 bit to 15 bit + sign
Integration time, parameterizableYes
Integration time (ms)2,5 / 16,67 / 20 / 100 ms
Basic conversion time, including integration time (ms)2.5 / 16.67 / 20 / 100 (1 channel enabled); 7.5 / 50 / 60 / 300 (2 channels enabled)
Interference voltage suppression for interference frequency f1 in Hz10 / 50 / 60 / 400 Hz
Encoder
Connection of signal encoders
for current measurement as 2-wire transducerYes
for current measurement as 4-wire transducerYes
Errors/accuracies
Operational error limit in overall temperature range
Current, relative to input range, (+/-)0.45 %; From 0/4 to 20 mA
Basic error limit (operational limit at 25 °C)
Current, relative to input range, (+/-)0.1 %; From 0/4 to 20 mA
Interrupts/diagnostics/status information
Diagnostics functionYes; Parameterizable
Alarms
Diagnostic alarmYes; Parameterizable
Limit value alarmYes; Parameterizable, channels 0 and 1
Diagnoses
OverrangeYes; red LED, signal
Wire-break in signal transmitter cableYes; red LED, signal
Short-circuit of the signal encoder cableYes; red LED, signal
HART communication activeYes; green LED (H)
Diagnostics indication LED
Group error SF (red)Yes
Channel fault indicator F (red)Yes
Ex(i) characteristics
Module for Ex(i) protectionYes
maximum values for connecting terminals for gas group IIC
Uo (no-load voltage), max.26 V
Io (short-circuit current), max.96.1 mA
Po (power output), max.511 mW
Co (permissible external capacity), max.62 nF
Lo (permissible external inductivity), max.3 mH
Um (voltage at non-intrinsically safe connecting terminals), max.250 V; DC
Potential separation
Potential separation analog inputs
between the channelsYes
between the channels and backplane busYes
Permissible potential difference
between the inputs (UCM)60 V DC/30 V AC permitted potential difference (Viso) of signals from hazardous areas
Standards, approvals, certificates
CE markYes
UL approvalYes
FM approvalYes
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Use in hazardous areas
ATEX markingATEX II 3 G (2) GD Ex nA [ib Gb] [ib IIIC Db] IIC T4 Gc
ATEX certificateDEKRA 14 ATEX 0052X
FM markingClass I, Division 2, Group A, B, C, D T4; Class I, Zone 2, Group IIC T4
Ambient conditions
Ambient temperature during operation
min.0 °C
max.60 °C
Connection method
required front connector1x 20-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.260 g
Approvals / Certificates