6ES7521-7EH00-0AB0

6ES7521-7EH00-0AB0

SIMATIC S7-1500, modul de intrare digitală DI 16x 24...125 V UC HF, 16 canale în grupuri de 1; întârziere la intrare 0.05..20 ms; tip de intrare 3 (IEC 61131); diagnosticare, întreruperi hardware: conectorul frontal (cleme cu șurub sau push-in) se comandă separat.

Categorie de produs
Module digitale
Producător
SIEMENS
Serie de produse
S7-1500
General information
Product type designationDI 16x24 ... 125 V UC HF
HW functional statusfrom FS01
Firmware versionfrom V1.0.0
FW update possibleYes
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeNo
Prioritized startupYes
Engineering with
STEP 7 TIA Portal configurable/integrated from versionV14 / -
STEP 7 configurable/integrated from versionV5.5 SP3 / -
PROFIBUS from GSD version/GSD revisionV1.0 / V5.1
PROFINET from GSD version/GSD revisionV2.3 / -
Operating mode
DIYes
CounterYes; from V1.1.0; only in DC operation
OversamplingNo
MSIYes
Supply voltage
Reverse polarity protectionYes
Power
Power consumption from the backplane bus1.2 W
Power loss
Power loss, typ.2.2 W; At 24 V DC; 6.0 W at 125 V AC
Address area
Address space per module
Inputs2 byte; typical, maximum 20 bytes, see manual for details
Outputs0 byte; typical, maximum 16 bytes, see manual for details
Digital inputs
Number of digital inputs16
Digital inputs, parameterizableYes
Sourcing/sinking inputYes
Input characteristic curve in accordance with IEC 61131, type 3Yes; At 24 V DC
Pulse extensionNo
Edge evaluationNo
Signal change flutterNo
Flutter observation windowNo
Number of simultaneously controllable inputs
Number of simultaneously controllable inputs16; see additional description in the manual
Digital input functions, parameterizable
Freely usable digital inputYes
CounterYes; from FS04
Number, max.2; Channel 0 and 1
Counting frequency, max.6 kHz
Counting width32 bit
Counting direction up/downYes; Up
Digital input with oversamplingNo
Input voltage
Rated value (DC)24 V; 48 V, 125 V
Rated value (AC)24 V; 48 V, 125 V (50 - 60 Hz)
for signal "0"-5 ... +5 V
for signal "1"+11 ... +146 V
Input current
for signal "1", typ.3 mA; At 24 V DC
Input delay (for rated value of input voltage)
for standard inputs
parameterizableYes; 0.05 / 0.1 / 0.4 / 1.6 / 3.2 / 12.8 / 20 ms parameterizable with DC, 20 ms fixed with AC
at "0" to "1", min.0.05 ms
at "0" to "1", max.20 ms
at "1" to "0", min.0.05 ms
at "1" to "0", max.20 ms
for interrupt inputs
ParameterizableYes
for technological functions
ParameterizableNo
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Encoder
Connectable encoders
2-wire sensorYes
permissible quiescent current (2-wire sensor), max.1.5 mA
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Hardware interruptYes
Diagnoses
Monitoring the supply voltageNo
Wire breakYes; To I < 550 µA
Short-circuitNo
Diagnostics indication LED
RUN LEDYes; green LED
ERROR LEDYes; red LED
Monitoring of the supply voltage (PWR-LED)No
Channel status displayYes; green LED
for channel diagnosticsYes; red LED
for module diagnosticsYes; red LED
Potential separation
Potential separation channels
between the channelsYes
between the channels, in groups of1
between the channels and backplane busYes
Permissible potential difference
between different circuits146 V DC/132 V AC
Isolation
Isolation tested with2 000 V DC
Standards, approvals, certificates
Siemens Eco Profile (SEP)Siemens EcoTech
Suitable for safety functionsNo
Ecological footprint
environmental product declarationYes
Global warming potential
global warming potential, (total) [CO2 eq]18.9 kg
global warming potential, (during production) [CO2 eq]12.1 kg
global warming potential, (during operation) [CO2 eq]7.66 kg
global warming potential, (after end of life cycle) [CO2 eq]-1.02 kg
Security
signed firmware updateYes; Firmware V3.0.0 or higher
securely removing dataNo
data integrityYes; Firmware V3.0.0 or higher
Ambient conditions
Ambient temperature during operation
horizontal installation, min.-30 °C; from FS04
horizontal installation, max.60 °C
vertical installation, min.-30 °C; from FS04
vertical installation, max.40 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.Restrictions for installation altitudes > 2 000 m, see manual
Absolute humidity
dew point, min.-60 °C; suitable for dry room applications
Dimensions
Width35 mm
Height147 mm
Depth129 mm
Weights
Weight, approx.240 g
Other
Note:please order front connectors (screw-in/push-in) separately
Approvals / Certificates