6ES7521-1BL10-0AA0
SIMATIC S7-1500, modul de intrare digitală, DI 32x24 V DC BA, 32 canale în grupuri de 16, întârziere la intrare, tipic 3.2 ms, tip de intrare 3 (IEC 61131); livrare incl. conector frontal push-in.
Categorie de produs
Module digitaleProducător
SIEMENSSerie de produse
S7-1500| General information | |
|---|---|
| Product type designation | DI 32x24VDC BA |
| HW functional status | from FS01 |
| Firmware version | V1.0.0 |
| FW update possible | Yes |
| Product function | |
| I&M data | Yes; I&M0 to I&M3 |
| Isochronous mode | No |
| Prioritized startup | Yes |
| Engineering with | |
| STEP 7 TIA Portal configurable/integrated from version | V13 / V13 |
| STEP 7 configurable/integrated from version | V5.5 SP3 / - |
| PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 |
| PROFINET from GSD version/GSD revision | V2.3 / - |
| Operating mode | |
| DI | Yes |
| Counter | No |
| Oversampling | No |
| MSI | Yes |
| Supply voltage | |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes |
| Power | |
| Power consumption from the backplane bus | 1.05 W |
| Power loss | |
| Power loss, typ. | 3 W |
| Address area | |
| Address space per module | |
| Inputs | 4 byte; typical, maximum 32 bytes, see manual for details |
| Outputs | 0 byte |
| Digital inputs | |
| Number of digital inputs | 32 |
| Digital inputs, parameterizable | No |
| Sourcing/sinking input | P-reading |
| Input characteristic curve in accordance with IEC 61131, type 3 | Yes |
| Pulse extension | No |
| Edge evaluation | No |
| Signal change flutter | No |
| Flutter observation window | No |
| Number of simultaneously controllable inputs | |
| Number of simultaneously controllable inputs | 32 |
| Digital input functions, parameterizable | |
| Freely usable digital input | Yes |
| Counter | No |
| Digital input with oversampling | No |
| Input voltage | |
| Rated value (DC) | 24 V |
| for signal "0" | -30 to +5 V |
| for signal "1" | +11 to +30V |
| Input current | |
| for signal "1", typ. | 2.7 mA |
| Input delay (for rated value of input voltage) | |
| for standard inputs | |
| parameterizable | No |
| at "0" to "1", min. | 3 ms |
| at "0" to "1", max. | 4 ms |
| at "1" to "0", min. | 3 ms |
| at "1" to "0", max. | 4 ms |
| for interrupt inputs | |
| Parameterizable | No |
| for technological functions | |
| Parameterizable | No |
| Cable length | |
| shielded, max. | 1 000 m |
| unshielded, max. | 600 m |
| Encoder | |
| Connectable encoders | |
| 2-wire sensor | Yes |
| permissible quiescent current (2-wire sensor), max. | 1.5 mA |
| Interrupts/diagnostics/status information | |
| Diagnostics function | No |
| Alarms | |
| Diagnostic alarm | No |
| Hardware interrupt | No |
| Diagnoses | |
| Monitoring the supply voltage | No |
| Wire break | No |
| Short-circuit | No |
| Diagnostics indication LED | |
| RUN LED | Yes; green LED |
| ERROR LED | Yes; red LED |
| Monitoring of the supply voltage (PWR-LED) | No |
| Channel status display | Yes; green LED |
| for channel diagnostics | No |
| for module diagnostics | No |
| Potential separation | |
| Potential separation channels | |
| between the channels | No |
| between the channels, in groups of | 16 |
| between the channels and backplane bus | Yes |
| between the channels and the power supply of the electronics | No |
| Isolation | |
| Isolation tested with | 707 V DC (type test) |
| Standards, approvals, certificates | |
| Siemens Eco Profile (SEP) | Siemens EcoTech |
| Suitable for safety functions | No |
| Ecological footprint | |
| environmental product declaration | Yes |
| Global warming potential | |
| global warming potential, (total) [CO2 eq] | 18.9 kg |
| global warming potential, (during production) [CO2 eq] | 12.1 kg |
| global warming potential, (during operation) [CO2 eq] | 7.66 kg |
| global warming potential, (after end of life cycle) [CO2 eq] | -1.02 kg |
| Security | |
| signed firmware update | Yes; Firmware V3.0.0 or higher |
| securely removing data | No |
| data integrity | Yes; Firmware V3.0.0 or higher |
| Ambient conditions | |
| Ambient temperature during operation | |
| horizontal installation, min. | -30 °C; from FS04 |
| horizontal installation, max. | 60 °C |
| vertical installation, min. | -30 °C; from FS04 |
| vertical installation, max. | 40 °C |
| Altitude during operation relating to sea level | |
| Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| Absolute humidity | |
| dew point, min. | -60 °C; suitable for dry room applications |
| Dimensions | |
| Width | 25 mm |
| Height | 147 mm |
| Depth | 129 mm |
| Weights | |
| Weight, approx. | 260 g |
| Other | |
| Note: | Supplied incl. 40-pole push-in front connectors |
| Approvals / Certificates | |