S7-1500| General information | |
|---|---|
| Product type designation | F-DQ 8x24VDC/2A PPM |
| Firmware version | |
| FW update possible | Yes |
| based on | 6ES7526-2BF00-0AB0 |
| Product function | |
| I&M data | Yes; I&M0 to I&M3 |
| Engineering with | |
| STEP 7 TIA Portal configurable/integrated from version | see entry ID: 109746275 |
| Operating mode | |
| DQ | Yes |
| MSO | No |
| Supply voltage | |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes |
| power supply according to NEC Class 2 required | No |
| Input current | |
| Current consumption (rated value) | 110 mA; without load |
| Current consumption, max. | 130 mA; without load |
| Output voltage | |
| Rated value (DC) | 24 V |
| Power | |
| Power consumption from the backplane bus | 0.8 W |
| Power loss | |
| Power loss, typ. | 11 W |
| Address area | |
| Address space per module | |
| Inputs | 6 byte; S7-300/400F CPU, 5 byte |
| Outputs | 6 byte; S7-300/400F CPU, 5 byte |
| Hardware configuration | |
| Automatic encoding | Yes |
| Electronic coding element type F | Yes |
| Digital outputs | |
| Number of digital outputs | 8 |
| Current-sinking | Yes |
| Current-sourcing | Yes |
| Short-circuit protection | Yes |
| Open-circuit detection | Yes |
| Response threshold, typ. | 8 mA |
| Overload protection | Yes |
| Response threshold, typ. | 2.9 A |
| Limitation of inductive shutdown voltage to | PM-switching: -24 V + (-47 V), PP-switching: -24 V |
| Controlling a digital input | Yes; digital output, according to IEC 61131-2, type 2 |
| Switching capacity of the outputs | |
| with resistive load, max. | 2 A |
| on lamp load, max. | 10 W |
| Load resistance range | |
| lower limit | 12 Ω |
| upper limit | 2 000 Ω |
| Output voltage | |
| for signal "1", min. | 24 V; L+ (-0.5 V) |
| Output current | |
| for signal "1" rated value | 2 A |
| for signal "0" residual current, max. | 0.5 mA; Current-sourcing, or current sourcing and sinking switches individually, current sinking: max. 1 mA |
| Switching frequency | |
| with resistive load, max. | 30 Hz |
| with inductive load, max. | 0.1 Hz |
| on lamp load, max. | 10 Hz |
| Total current of the outputs | |
| Current per channel, max. | 2 A |
| Total current of the outputs (per module) | |
| horizontal installation | |
| up to 40 °C, max. | 16 A |
| up to 60 °C, max. | 8 A |
| vertical installation | |
| up to 40 °C, max. | 8 A |
| Cable length | |
| shielded, max. | 1 000 m |
| unshielded, max. | 500 m |
| Interrupts/diagnostics/status information | |
| Diagnostics function | Yes |
| Substitute values connectable | No |
| Alarms | |
| Diagnostic alarm | Yes |
| Diagnoses | |
| Monitoring the supply voltage | Yes |
| Wire break | Yes |
| Short-circuit | Yes |
| Group error | Yes |
| Diagnostics indication LED | |
| RUN LED | Yes; green LED |
| ERROR LED | Yes; red LED |
| Monitoring of the supply voltage (PWR-LED) | Yes |
| Channel status display | Yes; green LED |
| for channel diagnostics | Yes; red LED |
| for module diagnostics | Yes; red LED |
| Potential separation | |
| Potential separation channels | |
| between the channels | No |
| between the channels and backplane bus | Yes |
| Isolation | |
| Isolation tested with | 707 V DC (type test) |
| Standards, approvals, certificates | |
| Suitable for safety functions | Yes |
| Highest safety class achievable in safety mode | |
| Performance level according to ISO 13849-1 | PLe |
| SIL acc. to IEC 61508 | SIL 3 |
| Probability of failure (for service life of 20 years and repair time of 100 hours) | |
| Low demand mode: PFDavg in accordance with SIL3 | < 6.00E-05 |
| High demand/continuous mode: PFH in accordance with SIL3 | < 2.00E-09 1/h |
| Ambient conditions | |
| Ambient temperature during operation | |
| horizontal installation, min. | -30 °C; = Tmin (incl. condensation/frost) |
| horizontal installation, max. | 60 °C; = Tmax |
| vertical installation, min. | -30 °C; = Tmin |
| vertical installation, max. | 40 °C; = Tmax |
| Altitude during operation relating to sea level | |
| Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| Relative humidity | |
| With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
| Resistance | |
| Coolants and lubricants | |
| Resistant to commercially available coolants and lubricants | Yes; Incl. diesel and oil droplets in the air |
| Use in stationary industrial systems | |
| to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
| to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * |
| Use on ships/at sea | |
| to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request |
| to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
| to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * |
| Usage in industrial process technology | |
| Against chemically active substances acc. to EN 60654-4 | Yes; Class 3 (excluding trichlorethylene) |
| Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) |
| Remark | |
| Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! |
| Conformal coating | |
| Coatings for printed circuit board assemblies acc. to EN 61086 | Yes; Class 2 for high reliability |
| Protection against fouling acc. to EN 60664-3 | Yes; Type 1 protection |
| Military testing according to MIL-I-46058C, Amendment 7 | Yes; Discoloration of coating possible during service life |
| Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A | Yes; Conformal coating, Class A |
| Dimensions | |
| Width | 35 mm |
| Height | 147 mm |
| Depth | 129 mm |
| Weights | |
| Weight, approx. | 300 g |
| Approvals / Certificates | |