6AG1521-1BL00-7AB0

6AG1521-1BL00-7AB0

SIPLUS S7-1500 DI 32x24VDC HF bazat pe 6ES7521-1BL00-0AB0, cu strat de protecție (conformal coating), -40…+70 °C, modul de intrare digitală, 32 canale în grupuri de 16; întârziere la intrare 0.05..20 ms, tip de intrare 3 (IEC 61131); diagnosticare; întreruperi hardware.

Categorie de produs
Module digitale
Producător
SIEMENS
Serie de produse
S7-1500
General information
Product type designationDI 32x24VDC HF
HW functional statusE01
Firmware versionV1.0.0
FW update possibleYes
based on6ES7521-1BL00-0AB0
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeYes
Prioritized startupYes
Engineering with
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Operating mode
DIYes
CounterYes
OversamplingNo
MSIYes
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption, max.40 mA; 20 mA per group with 24 V DC supply
Power
Power consumption from the backplane bus1.1 W
Power loss
Power loss, typ.4.2 W
Digital inputs
Number of digital inputs32; > +60 °C, number of simultaneously controllable inputs max. 16
Digital inputs, parameterizableYes
Sourcing/sinking inputP-reading
Input characteristic curve in accordance with IEC 61131, type 3Yes
Digital input functions, parameterizable
Gate start/stopYes
Freely usable digital inputYes
Counter
Number, max.2
Counting frequency, max.3 kHz; FS04 and FW V2.2.1 or higher
Counting width32 bit
Counting direction up/downUp
Input voltage
Rated value (DC)24 V
for signal "0"-30 to +5 V
for signal "1"+11 to +30V
Input current
for signal "1", typ.2.5 mA
Input delay (for rated value of input voltage)
for standard inputs
parameterizableYes; 0.05 / 0.1 / 0.4 / 1.6 / 3.2 / 12.8 / 20 ms
at "0" to "1", min.0.05 ms
at "0" to "1", max.20 ms
at "1" to "0", min.0.05 ms
at "1" to "0", max.20 ms
for interrupt inputs
ParameterizableYes
for technological functions
ParameterizableYes
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Encoder
Connectable encoders
2-wire sensorYes
permissible quiescent current (2-wire sensor), max.1.5 mA
Isochronous mode
Filtering and processing time (TCI), min.80 µs; At 50 μs filter time
Bus cycle time (TDP), min.250 µs
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Hardware interruptYes
Diagnoses
Monitoring the supply voltageYes
Wire breakYes; to I < 350 µA
short-circuitNo
Fuse blownNo
Diagnostics indication LED
RUN LEDYes; green LED
ERROR LEDYes; red LED
Monitoring of the supply voltage (PWR-LED)Yes; green LED
Channel status displayYes; green LED
for channel diagnosticsYes; red LED
for module diagnosticsYes; red LED
Potential separation
Potential separation channels
between the channelsYes
between the channels, in groups of16
between the channels and backplane busYes
between the channels and the power supply of the electronicsNo
Isolation
Isolation tested with707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functionsNo
Ecological footprint
environmental product declarationYes
Global warming potential
global warming potential, (total) [CO2 eq]18.9 kg
global warming potential, (during production) [CO2 eq]12.1 kg
global warming potential, (during operation) [CO2 eq]7.66 kg
global warming potential, (after end of life cycle) [CO2 eq]-1.02 kg
Security
signed firmware updateNo
data integrityNo
Ambient conditions
Ambient temperature during operation
horizontal installation, min.-40 °C; = Tmin (incl. condensation/frost)
horizontal installation, max.70 °C; = Tmax; > +60 °C number of simultaneously controllable inputs max. 16
vertical installation, min.-40 °C; = Tmin
vertical installation, max.40 °C; = Tmax
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Coolants and lubricants
Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Dimensions
Width35 mm
Height147 mm
Depth129 mm
Weights
Weight, approx.260 g
Approvals / Certificates