6AG1212-1HE40-4XB0

6AG1212-1HE40-4XB0

SIPLUS S7-1200 CPU 1212C DC/DC/relay bazat pe 6ES7212-1HE40-0XB0, cu strat de protecție (conformal coating), -20…+60 °C, CPU compact, DC/DC/relay, I/O integrate: 8 DI 24 V DC 6 DQ releu 2 A 2 AI 0-10 V DC, alimentare: 20.4-28.8 V D, memorie program/date 75 KB

Categorie de produs
CPU
Sistem de magistrală
PROFINET
Tensiune nominală
24V DC
Producător
SIEMENS
Serie de produse
S7-1200
Memorie de lucru
75 kbyte
Memorie de încărcare
1 Mbyte
Intrări digitale
8 - (24V DC)
Ieșiri digitale
6 - (Relee 2A)
Intrări analogice
2 - (0-10V)
Ieșiri analogice
0
Protocoale
PROFINET IO ControllerComunicație IE deschisăPROFINET IO DeviceServer web
Protecție (IP)
IP20
Putere disipată
9 W
Consum de curent
400 mA; tipic
General information
Product type designationCPU 1212C DC/DC/relay
based on6ES7212-1HE40-0XB0
Engineering with
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Supply voltage
Rated value (DC)
24 V DCYes
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Load voltage L+
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Input current
Current consumption (rated value)400 mA; CPU only
Current consumption, max.1 200 mA; CPU with all expansion modules
Inrush current, max.12 A; at 28.8 V
I²t0.8 A²·s
Output current
for backplane bus (5 V DC), max.1 000 mA; Max. 5 V DC for SM and CM
Encoder supply
24 V encoder supply
24 VL+ minus 4 V DC min.
Power loss
Power loss, typ.9 W
Storage
Work memory
integrated100 kbyte
Load memory
Integrated2 Mbyte
Plug-in (SIMATIC Memory Card), max.with SIMATIC memory card
Backup
presentYes
maintenance-freeYes
without batteryYes
CPU processing times
for bit operations, typ.0.08 µs; / instruction
for word operations, typ.1.7 µs; / instruction
for floating point arithmetic, typ.2.3 µs; / instruction
CPU-blocks
Number of elements (total)DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used
OB
Number, max.Limited only by RAM for code
Data areas and their retentivity
Retentive data area (incl. timers, counters, flags), max.14 kbyte
Flag
Size, max.4 kbyte; Size of bit memory address area
Local data
per priority class, max.16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB
Address area
Process image
Inputs, adjustable1 kbyte
Outputs, adjustable1 kbyte
Hardware configuration
Number of modules per system, max.3 comm. modules, 1 signal board, 2 signal modules
number of expansion boards (SB, CB, BB)1
number of signal modules (SM)2
number of communications modules (CM)3
Time of day
Clock
Hardware clock (real-time)Yes
Backup time480 h; Typical
Deviation per day, max.±60 s/month at 25 °C
Digital inputs
Number of digital inputs8; Integrated
of which inputs usable for technological functions4; HSC (High Speed Counting)
Sourcing/sinking inputYes
Number of simultaneously controllable inputs
all mounting positions
up to 40 °C, max.8
Input voltage
Rated value (DC)24 V
for signal "0"5 V DC at 1 mA
for signal "1"15 V DC at 2.5 mA
Input delay (for rated value of input voltage)
for standard inputs
parameterizable0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 μs; 0.05 / 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 ms
at "0" to "1", min.0.2 ms
at "0" to "1", max.12.8 ms
for interrupt inputs
ParameterizableYes
for technological functions
ParameterizableSingle phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz
Cable length
shielded, max.500 m; 50 m for technological functions
unshielded, max.300 m; for technological functions: No
Digital outputs
Number of digital outputs6; Relays
Switching capacity of the outputs
with resistive load, max.2 A
on lamp load, max.30 W with DC, 200 W with AC
Output delay with resistive load
"0" to "1", max.10 ms; max.
"1" to "0", max.10 ms; max.
Relay outputs
Number of relay outputs6
Number of operating cycles, max.mechanically 10 million, at rated load voltage 100 000
Cable length
shielded, max.500 m
unshielded, max.150 m
Analog inputs
Number of analog inputs2
Input ranges
VoltageYes
Input ranges (rated values), voltages
0 to +10 VYes
Input resistance (0 to 10 V)≥100k ohms
Cable length
shielded, max.100 m; twisted and shielded
Analog outputs
Number of analog outputs0
Analog value generation for the inputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.10 bit
Integration time, parameterizableYes
Conversion time (per channel)625 µs
Encoder
Connectable encoders
2-wire sensorYes
Interfaces
Number of PROFINET interfaces1
1. Interface
Interface typePROFINET
IsolatedYes
automatic detection of transmission rateYes
AutonegotiationYes
AutocrossingYes
Interface types
RJ 45 (Ethernet)Yes
Number of ports1
integrated switchNo
Protocols
PROFINET IO ControllerYes
PROFINET IO deviceYes
SIMATIC communicationYes
Open IE communicationYes; Optionally also encrypted
Web serverYes
Media redundancyNo
PROFINET IO Controller
Transmission rate, max.100 Mbit/s
Services
PG/OP communicationYes; encryption with TLS V1.3 pre-selected
Isochronous modeNo
IRTNo
PROFIenergyNo
Prioritized startupYes
Number of IO devices with prioritized startup, max.16
Number of connectable IO Devices, max.16
Number of connectable IO Devices for RT, max.16
of which in line, max.16
Number of IO Devices that can be simultaneously activated/deactivated, max.8
Updating timeThe minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data.
PROFINET IO Device
Services
PG/OP communicationYes; encryption with TLS V1.3 pre-selected
Isochronous modeNo
IRTNo
Dynamic Frame Packing (DFP)No
PROFIenergyYes
Prioritized startupYes
Shared deviceYes
Number of IO Controllers with shared device, max.2
Asset management recordYes
Protocols
Supports protocol for PROFINET IOYes
PROFIsafeNo
PROFIBUSYes; CM 1243-5 (master) or CM 1242-5 (slave) required
OPC UAYes; OPC UA Server
AS-InterfaceYes; CM 1243-2 required
Protocols (Ethernet)
TCP/IPYes
DHCPNo
SNMPYes
DCPYes
LLDPYes
Redundancy mode
PROFINET system redundancy (S2)No
PROFINET system redundancy (R1)No
Media redundancy
MRPNo
MRP interconnection, supportedNo
MRPDNo
SIMATIC communication
S7 routingYes
Open IE communication
TCP/IPYes
Data length, max.8 kbyte
ISO-on-TCP (RFC1006)Yes
Data length, max.8 kbyte
UDPYes
Data length, max.1 472 byte
Web server
supportedYes
User-defined websitesYes
OPC UA
Runtime license requiredYes; "Basic" license required
OPC UA ServerYes; data access (read, write, subscribe), method call, runtime license required
Application authenticationAvailable security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256
User authentication"anonymous" or by user name & password
Number of sessions, max.10
Number of subscriptions per session, max.5
Sampling interval, min.100 ms
Publishing interval, min.200 ms
Number of server methods, max.20
Number of monitored items, recommended max.1 000
Number of server interfaces, max.2
Number of nodes for user-defined server interfaces, max.2 000
Further protocols
MODBUSYes
Communication functions
S7 communication
supportedYes
as serverYes
as clientYes
User data per job, max.See online help (S7 communication, user data size)
Number of connections
overallPG Connections: 4 reserved / 4 max; HMI Connections: 12 reserved / 18 max; S7 Connections: 8 reserved / 14 max; Open User Connections: 8 reserved / 14 max; Web Connections: 2 reserved / 30 max; OPC UA Connections: 0 reserved / 10 max; Total Connections: 34 reserved / 68 max
Test commissioning functions
Status/control
Status/control variableYes
VariablesInputs/outputs, memory bits, DBs, distributed I/Os, timers, counters
Forcing
ForcingYes
Diagnostic buffer
presentYes
Traces
Number of configurable Traces2
Memory size per trace, max.512 kbyte
Interrupts/diagnostics/status information
Diagnostics indication LED
RUN/STOP LEDYes
ERROR LEDYes
MAINT LEDYes
Integrated Functions
Counter
Number of counters6
Counting frequency, max.100 kHz
Frequency measurementYes
controlled positioningYes
Number of position-controlled positioning axes, max.8
Number of positioning axes via pulse-direction interfaceUp to 4 with SB 1222
PID controllerYes
Number of alarm inputs4
Potential separation
Potential separation digital inputs
Potential separation digital inputs500 V AC for 1 minute
between the channels, in groups of1
Potential separation digital outputs
Potential separation digital outputsRelays
between the channelsNo
between the channels, in groups of2
EMC
Interference immunity against discharge of static electricity
Interference immunity against discharge of static electricity acc. to IEC 61000-4-2Yes
Test voltage at air discharge8 kV
Test voltage at contact discharge6 kV
Interference immunity to cable-borne interference
Interference immunity on supply lines acc. to IEC 61000-4-4Yes
Interference immunity on signal cables acc. to IEC 61000-4-4Yes
Interference immunity against voltage surge
Interference immunity on supply lines acc. to IEC 61000-4-5Yes
Interference immunity against conducted variable disturbance induced by high-frequency fields
Interference immunity against high-frequency radiation acc. to IEC 61000-4-6Yes
Emission of radio interference acc. to EN 55 011
Limit class A, for use in industrial areasYes; Group 1
Limit class B, for use in residential areasYes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011
Degree and class of protection
IP degree of protectionIP20
Standards, approvals, certificates
Siemens Eco Profile (SEP)Siemens EcoTech
Ecological footprint
environmental product declarationYes; type II acc. to ISO 14021
Global warming potential
global warming potential, (total) [CO2 eq]76.4 kg
global warming potential, (during production) [CO2 eq]13.8 kg
global warming potential, (during operation) [CO2 eq]63.4 kg
global warming potential, (after end of life cycle) [CO2 eq]-0.89 kg
Ambient conditions
Free fall
Fall height, max.0.3 m; five times, in product package
Ambient temperature during operation
min.-20 °C; = Tmin; Startup @ 0 °C
max.60 °C; Number of simultaneously activated inputs or outputs 4 or 3 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 8 or 6 at 55 °C horizontal or 45 °C vertical
horizontal installation, min.-20 °C; = Tmin (incl. condensation/frost); start-up @ 0 °C
horizontal installation, max.60 °C; = Tmax
vertical installation, min.-20 °C; = Tmin; Startup @ 0 °C
vertical installation, max.50 °C; = Tmax
At cold restart, min.0 °C
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.2 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m); above 2 000 m max. 132 V AC
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Vibrations
Vibration resistance during operation acc. to IEC 60068-2-62 g (m/s²) wall mounting, 1 g (m/s²) DIN rail
Operation, tested according to IEC 60068-2-6Yes
Shock testing
tested according to IEC 60068-2-27Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms
Resistance
Coolants and lubricants
Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Configuration
Programming
Programming language
LADYes
FBDYes
SCLYes
Know-how protection
User program protection/password protectionYes
Copy protectionYes
Block protectionYes
Access protection
protection of confidential configuration dataYes
Protection level: Write protectionYes
Protection level: Read/write protectionYes
Protection level: Complete protectionYes
User administrationYes; device-wide
Number of users42
Number of groups14
Number of roles20
Cycle time monitoring
can be setYes
Dimensions
Width90 mm
Height100 mm
Depth75 mm
Weights
Weight, approx.385 g
Approvals / Certificates