6ED1052-1CC08-0BA2

6ED1052-1CC08-0BA2

LOGO! 24CE, modul logic, afișaj, alimentare / I/O: 24 V/24 V/24 V tranzistor, 8 DI (4 AI)/4 DO, memorie 400 de blocuri, extensibil modular, Ethernet, server web integrat, jurnal de date, pagini web definite de utilizator, card microSD standard pentru LOGO! Soft Comfort V8.4 sau mai recent, proiectele mai vechi pot fi executate, conexiune cloud, MQTT în toate unitățile de bază LOGO! 8.4

Categorie de produs
LOGO!
Producător
SIEMENS
Serie de produse
LOGO!
Display
with displayYes
Installation type/mounting
Mountingon 35 mm DIN rail, 4 spacing units wide
Supply voltage
Rated value (DC)
24 V DCYes
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Time of day
Time switching clocks
Number400; Max. 400, function-specific
Power reserve480 h
Digital inputs
Number of digital inputs8; Of which 4 can be used in analog mode (0 to 10 V)
Digital outputs
Number of digital outputs4; Transistor
Short-circuit protectionYes; electrical (1 A)
Output current
for signal "1" permissible range for 0 to 55 °C, max.0.3 A
EMC
Emission of radio interference acc. to EN 55 011
Limit class B, for use in residential areasYes; Radio interference suppression according to EN55011, Limit Value Class B
Standards, approvals, certificates
Siemens Eco Profile (SEP)Siemens EcoTech
CE markYes
CSA approvalYes; covered by UL cert
UL approvalYes
FM approvalYes
developed in accordance with IEC 61131Yes
according to VDE 0631Yes
Marine approvalYes
Ecological footprint
environmental product declarationYes
Global warming potential
global warming potential, (total) [CO2 eq]51.5 kg
global warming potential, (during production) [CO2 eq]9.64 kg
global warming potential, (during operation) [CO2 eq]42.1 kg
global warming potential, (after end of life cycle) [CO2 eq]-0.364 kg
Ambient conditions
Ambient temperature during operation
min.-20 °C; No condensation
max.55 °C
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m)
Dimensions
Width71.5 mm; 4 modular widths (MW)
Height90 mm
Depth60 mm
Approvals / Certificates