i950
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 3.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 1.8/1.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.75 kW/1 HP
- Output current 2.4/2.1 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 1.5 kW/2 HP
- Output current 7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 9.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 5.6/4.8 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 4 kW/5 HP
- Output current 16.5 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 4 kW/5 HP
- Output current 9.5/8.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 5.5 kW/7.5 HP
- Output current 23 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 7.5 kW/10 HP
- Output current 16.5/14 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 11 kW/15 HP
- Output current 23.5/21 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 15 kW/20 HP
- Output current 32/27 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 22 kW/30 HP
- Output current 47/40.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 30 kW/40 HP
- Output current 61/52 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 45 kW/60 HP
- Output current 89/77 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 55 kW/75 HP
- Output current 110/96 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 75 kW/100 HP
- Output current 150/124 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 90 kW/125 HP
- Output current 180/156 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 110 kW/150 HP
- Output current 212/180 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
-
Fault message ID
704676259 0x2A0081A3 Description
Severity/responseiParameters - Restore, watchdog expired
Information
-
Fault message ID
704676260 0x2A0081A4 Description
Severity/responsePROFIsafe - iParCRC error
Information
-
Fault message ID
704676261 0x2A0081A5 Description
Severity/responsePROFIsafe - CRC2 error
Information
-
Fault message ID
704676262 0x2A0081A6 Description
Severity/responseF_WD_Time or F_WD_Time_2 expired
Information
-
Fault message ID
704676263 0x2A0081A7 Description
Severity/responseReserved (PROFIsafe standard)
Information
-
Fault message ID
704676264 0x2A0081A8 Description
CauseFSoE - Invalid slave address
RemedyThe slave address transmitted by the FSoE master differs from the slave address set in the device.
Severity/responseCheck slave address in the FSoE master. Check parameter setting in the device.
Information
-
Fault message ID
704676265 0x2A0081A9 Description
CauseFSoE - Invalid communication parameter length
RemedyThe length of the communication parameter transmitted by the FSoE master differs from the expected length.
Severity/responseCheck setting of the communication parameters.
Information
-
Fault message ID
704676266 0x2A0081AA Description
CauseFSoE - Data exchange left
RemedyDue to an error FSoE has left the data exchange.
Severity/responseCheck FSoE configuration. Reset error.
Information
-
Fault message ID
704680064 0x2A009080 Description
CauseDiscrepancy check or function check error - SD-In1
RemedySignal error at safe input SD-In1.
Severity/responseCheck parameter setting. Check wiring.
Warning
-
Fault message ID
704680065 0x2A009081 Description
CauseDiscrepancy check or function check error - SD-In2
RemedySignal error at safe input SD-In2.
Severity/responseCheck parameter setting. Check wiring.
Warning
-
Fault message ID
704680066 0x2A009082 Description
CauseDiscrepancy check or function check error - SD-In3
RemedySignal error at safe input SD-In3.
Severity/responseCheck parameter setting. Check wiring.
Warning
-
Fault message ID
704680067 0x2A009083 Description
CauseDiscrepancy check or function check error - SD-In4
RemedySignal error at safe input SD-In4.
Severity/responseCheck parameter setting. Check wiring.
Warning
-
Fault message ID
704680068 0x2A009084 Description
CauseDisabled SD-In1 = HIGH
RemedyInitialization error or parameterization error. HIGH level detected at the deactivated safe input.
Severity/responseCheck parameter setting. Check wiring.
Warning
-
Fault message ID
704680069 0x2A009085 Description
CauseDisabled SD-In2 = HIGH
RemedyInitialization error or parameterization error. HIGH level detected at the deactivated safe input.
Severity/responseCheck parameter setting. Check wiring.
Warning
-
Fault message ID
704680070 0x2A009086 Description
CauseDisabled SD-In3 = HIGH
RemedyInitialization error or parameterization error. HIGH level detected at the deactivated safe input.
Severity/responseCheck parameter setting. Check wiring.
Warning
-
Fault message ID
704680071 0x2A009087 Description
CauseDisabled SD-In4 = HIGH
RemedyInitialization error or parameterization error. HIGH level detected at the deactivated safe input.
Severity/responseCheck parameter setting. Check wiring.
Warning
-
Fault message ID
704680072 0x2A009088 Description
CauseSD-Out1 - Channel A remains stuck at HIGH
RemedyChannel A of SD_Out1 cannot be deactivated.
Severity/responseCheck wiring for short circuit.
Warning
-
Fault message ID
704680073 0x2A009089 Description
CauseSD-Out1 - Channel A remains stuck at LOW
RemedyChannel A of SD_Out1 cannot be activated.
Severity/responseCheck wiring. Check supply voltage.
Warning
-
Fault message ID
704680074 0x2A00908A Description
CauseSD-Out1 - Channel B remains stuck at HIGH
RemedyChannel B of SD_Out1 cannot be deactivated.
Severity/responseCheck wiring for short circuit.
Warning
-
Fault message ID
704680075 0x2A00908B Description
CauseSD-Out1 - Channel B remains stuck at LOW
RemedyChannel B of SD_Out1 cannot be activated.
Severity/responseCheck wiring. Check supply voltage.
Warning
-
Fault message ID
704680076 0x2A00908C Description
CauseSD-In1 - Channel A remains stuck at HIGH
RemedyChannel A of SD_In1 cannot be deactivated.
Severity/responseCheck wiring for short circuit. Check configuration of the safe input.
Warning
-
Fault message ID
704680077 0x2A00908D Description
CauseSD-In1 - Channel B remains stuck at HIGH
RemedyChannel B of SD_In1 cannot be deactivated.
Severity/responseCheck wiring for short circuit. Check configuration of the safe input.
Warning
-
Fault message ID
704680078 0x2A00908E Description
CauseSD-In2 - Channel A remains stuck at HIGH
RemedyChannel A of SD_In2 cannot be deactivated.
Severity/responseCheck wiring for short circuit. Check configuration of the safe input.
Warning
-
Fault message ID
704680079 0x2A00908F Description
CauseSD-In2 - Channel B remains stuck at HIGH
RemedyChannel B of SD_In2 cannot be deactivated.
Severity/responseCheck wiring for short circuit. Check configuration of the safe input.
Warning
-
Fault message ID
704680080 0x2A009090 Description
CauseSD-In3 - Channel A remains stuck at HIGH
RemedyChannel A of SD_In3 cannot be deactivated.
Severity/responseCheck wiring for short circuit. Check configuration of the safe input.
Warning
-
0x2360
Parameter
EtherCAT communication Data type
U8 Default setting
No action/no error [0] Attributes
- -
0x2362:007
Parameter
Active EtherCAT settings: Tx length Data type
U16 Default setting
- (Read only) Attributes
- -
0x2362:008
Parameter
Active EtherCAT settings: Rx length Data type
U16 Default setting
- (Read only) Attributes
- -
0x2368
Parameter
EtherCAT status Data type
U16 Default setting
- (Read only) Attributes
- -
0x2369
Parameter
EtherCAT error Data type
U16 Default setting
- (Read only) Attributes
H -
0x2371:009
Parameter
onboard EtherCAT: Interface mode Data type
U8 Default setting
Slave [0] Attributes
C -
0x2372:009
Parameter
onboard EtherCAT - Information: Active interface mode Data type
U8 Default setting
- (Read only) Attributes
- -
0x2378
Parameter
onboard EtherCAT - status Data type
U16 Default setting
- (Read only) Attributes
- -
0x2379
Parameter
onboard EtherCAT - Error Data type
U16 Default setting
- (Read only) Attributes
- -
0x2380
Parameter
PROFINET communication Data type
U8 Default setting
No action/no error [0] Attributes
- -
0x2381:001
Parameter
PROFINET settings: IP address Data type
U32 Default setting
0.0.0.0 Attributes
E -
0x2381:002
Parameter
PROFINET settings: Subnet Data type
U32 Default setting
0.0.0.0 Attributes
E -
0x2381:003
Parameter
PROFINET settings: Gateway Data type
U32 Default setting
0.0.0.0 Attributes
E -
0x2381:004
Parameter
PROFINET settings: Station name Data type
STRING[240] Attributes
- -
0x2381:005
Parameter
PROFINET settings: I&M1 System designation Data type
STRING[32] Attributes
- -
0x2381:006
Parameter
PROFINET settings: I&M1 Installation site Data type
STRING[22] Attributes
- -
0x2381:007
Parameter
PROFINET settings: I&M2 Installation date Data type
STRING[16] Attributes
- -
0x2381:008
Parameter
PROFINET settings: I&M3 additional information Data type
STRING[54] Attributes
- -
0x2381:009
Parameter
PROFINET settings: I&M4 signature code Data type
OCTET[54] Default setting
"00000000000000000000000000000000 000000000000000000000000000000000 000000000000000000000000000000000 0000000000" Attributes
- -
0x2382:001
Parameter
Active PROFINET settings: IP address Data type
U32 Default setting
- (Read only) Attributes
E -
0x2382:002
Parameter
Active PROFINET settings: Subnet Data type
U32 Default setting
- (Read only) Attributes
E -
0x2382:003
Parameter
Active PROFINET settings: Gateway Data type
U32 Default setting
- (Read only) Attributes
E -
0x2382:004
Parameter
Active PROFINET settings: Station name Data type
STRING[240] Default setting
- (Read only) Attributes
- -
0x2382:005
Parameter
Active PROFINET settings: MAC Address Data type
OCTET[6] Default setting
- (Read only) Attributes
- -
0x2388
Parameter
PROFINET status Data type
U16 Default setting
- (Read only) Attributes
H
No results.