i950
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 3.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 1.8/1.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.75 kW/1 HP
- Output current 2.4/2.1 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 1.5 kW/2 HP
- Output current 7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 9.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 5.6/4.8 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 4 kW/5 HP
- Output current 16.5 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 4 kW/5 HP
- Output current 9.5/8.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 5.5 kW/7.5 HP
- Output current 23 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 7.5 kW/10 HP
- Output current 16.5/14 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 11 kW/15 HP
- Output current 23.5/21 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 15 kW/20 HP
- Output current 32/27 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 22 kW/30 HP
- Output current 47/40.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 30 kW/40 HP
- Output current 61/52 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 45 kW/60 HP
- Output current 89/77 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 55 kW/75 HP
- Output current 110/96 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 75 kW/100 HP
- Output current 150/124 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 90 kW/125 HP
- Output current 180/156 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 110 kW/150 HP
- Output current 212/180 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
-
Fault message ID
704663684 0x2A005084 Description
CauseIRL - Internal error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663691 0x2A00508B Description
CauseSD-Inx/CLx - Error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663692 0x2A00508C Description
CauseInternal switch-off path - Error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663693 0x2A00508D Description
CauseInternal switch-off path - Test pulse error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663694 0x2A00508E Description
CauseSBC - Test pulse error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663695 0x2A00508F Description
CauseSBC - Remains stuck at LOW
RemedyError in the safe brake control
Severity/responseCheck the supply voltage of the brake. Check the wiring of the brake.
Warning
-
Fault message ID
704663696 0x2A005090 Description
CauseFaulty internal adjustment data
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663828 0x2A005114 Description
CauseReference voltage error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663829 0x2A005115 Description
Cause6 V voltage error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663830 0x2A005116 Description
Cause5 V voltage error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663831 0x2A005117 Description
Cause3.3 V voltage error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704668032 0x2A006180 Description
CauseInternal error - STO activated
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704668037 0x2A006185 Description
CauseCommunication error - Basic device
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704668038 0x2A006186 Description
CauseSynchronization error - Basic device
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Information
-
Fault message ID
704668039 0x2A006187 Description
Severity/responseSBC - Device configuration incompatible
Warning
-
Fault message ID
704668544 0x2A006380 Description
CauseF-parameter error
RemedyError in the PROFIsafe parameter setting The F-PLC is parameterized incorrectly.
Severity/responseCheck PROFIsafe component. Check network cable. Analyze the error history of the higher-level controller.
Information
-
Fault message ID
704668545 0x2A006381 Description
CauseF_Dest_Add unequal F-address
RemedyThe safety address F_Dest_Add in the higher- level controller and the F address in the device are different.
Severity/responseAdapt safety addresses.
Information
-
Fault message ID
704668546 0x2A006382 Description
CauseF_Dest_Add = 0 or FFFFhex
RemedyThe safety address F_Dest_Add in the higher- level controller is invalid.
Severity/responseAdapt safety address.
Information
-
Fault message ID
704668547 0x2A006383 Description
CauseF_Source_Add = 0 or FFFFhex
RemedyThe safety address F_Source_Add in the higher- level controller is invalid.
Severity/responseAdapt safety address.
Information
-
Fault message ID
704668548 0x2A006384 Description
CauseF_WD_Time = 0 ms
RemedyThe monitoring time F_WD_Time in the higher- level controller is invalid.
Severity/responseAdapt parameter setting.
Information
-
Fault message ID
704668549 0x2A006385 Description
CauseF_SIL exceeds technical SIL
RemedyThe SIL parameterized in the higher-level controller is greater than the technically possible SIL of the device.
Severity/responseAdapt parameter setting in the higher-level controller.
Information
-
Fault message ID
704668550 0x2A006386 Description
CauseF_CRC_Length error
RemedyThe data length of the F_CRC in the higher-level controller is faulty.
Severity/responseCheck safety parameter in the higher-level controller.
Information
-
Fault message ID
704668551 0x2A006387 Description
CauseWrong F-parameter version
RemedyThe F parameter version is not supported by the device.
Severity/responseSelect supported F parameter version in the higher-level controller.
Information
-
Fault message ID
704668552 0x2A006388 Description
Severity/responseF_Block_ID not supported
Information
-
Fault message ID
704668553 0x2A006389 Description
CauseSafety parameter set deleted
RemedySafety parameter set deleted
Severity/responseFor information only. No remedy necessary.
Information
-
0x2304:021
Parameter
CANopen settings: Communication error Data type
U8 Default setting
Status -> Pre-operational [0] Attributes
- -
0x2304:031
Parameter
CANopen settings: COB-ID client -> server (rx) Data type
U32 Default setting
0x80000641 Attributes
H -
0x2304:032
Parameter
CANopen settings: COB-ID server -> client (tx) Data type
U32 Default setting
0x800005C1 Attributes
H -
0x2304:033
Parameter
CANopen settings: SDO client - Node-ID Data type
U8 Default setting
1 Attributes
- -
0x2304:041
Parameter
CANopen settings: RPDO1 - COB-ID Data type
U32 Default setting
0x00000201 Attributes
H -
0x2304:042
Parameter
CANopen settings: RPDO1 - Transmission type Data type
U8 Default setting
255 Attributes
- -
0x2304:045
Parameter
CANopen settings: RPDO1 - Event timer Data type
U16 Default setting
100 ms Attributes
- -
0x2304:051
Parameter
CANopen settings: RPDO2 - COB-ID Data type
U32 Default setting
0x80000301 Attributes
H -
0x2304:052
Parameter
CANopen settings: RPDO2 - Transmission type Data type
U8 Default setting
255 Attributes
- -
0x2304:055
Parameter
CANopen settings: RPDO2 - Event timer Data type
U16 Default setting
100 ms Attributes
- -
0x2304:061
Parameter
CANopen settings: RPDO3 - COB-ID Data type
U32 Default setting
0x80000401 Attributes
H -
0x2304:062
Parameter
CANopen settings: RPDO3 - Transmission type Data type
U8 Default setting
255 Attributes
- -
0x2304:065
Parameter
CANopen settings: RPDO3 - Event timer Data type
U16 Default setting
100 ms Attributes
- -
0x2304:071
Parameter
CANopen settings: RPDO4 - COB-ID Data type
U32 Default setting
0x80000501 Attributes
H -
0x2304:072
Parameter
CANopen settings: RPDO4 - Transmission type Data type
U8 Default setting
255 Attributes
- -
0x2304:075
Parameter
CANopen settings: RPDO4 - Event timer Data type
U16 Default setting
100 ms Attributes
- -
0x2304:081
Parameter
CANopen settings: TPDO1 - COB-ID Data type
U32 Default setting
0x40000181 Attributes
H -
0x2304:082
Parameter
CANopen settings: TPDO1 - Transmission type Data type
U8 Default setting
255 Attributes
- -
0x2304:083
Parameter
CANopen settings: TPDO1 - Inhibit time Data type
U16 Default setting
0.0 ms Attributes
- -
0x2304:085
Parameter
CANopen settings: TPDO1 - Event timer Data type
U16 Default setting
20 ms Attributes
- -
0x2304:091
Parameter
CANopen settings: TPDO2 - COB-ID Data type
U32 Default setting
0xC0000281 Attributes
H -
0x2304:092
Parameter
CANopen settings: TPDO2 - Transmission type Data type
U8 Default setting
255 Attributes
- -
0x2304:093
Parameter
CANopen settings: TPDO2 - Inhibit time Data type
U16 Default setting
0.0 ms Attributes
- -
0x2304:095
Parameter
CANopen settings: TPDO2 - Event timer Data type
U16 Default setting
0 ms Attributes
- -
0x2304:101
Parameter
CANopen settings: TPDO3 - COB-ID Data type
U32 Default setting
0xC0000381 Attributes
H