i950
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 3.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 1.8/1.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.75 kW/1 HP
- Output current 2.4/2.1 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 1.5 kW/2 HP
- Output current 7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 9.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 5.6/4.8 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 4 kW/5 HP
- Output current 16.5 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 4 kW/5 HP
- Output current 9.5/8.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 5.5 kW/7.5 HP
- Output current 23 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 7.5 kW/10 HP
- Output current 16.5/14 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 11 kW/15 HP
- Output current 23.5/21 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 15 kW/20 HP
- Output current 32/27 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 22 kW/30 HP
- Output current 47/40.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 30 kW/40 HP
- Output current 61/52 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 45 kW/60 HP
- Output current 89/77 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 55 kW/75 HP
- Output current 110/96 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 75 kW/100 HP
- Output current 150/124 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 90 kW/125 HP
- Output current 180/156 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 110 kW/150 HP
- Output current 212/180 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
-
Fault message ID
704663684 0x2A005084 Description
CauseIRL - Internal error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663691 0x2A00508B Description
CauseSD-Inx/CLx - Error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663692 0x2A00508C Description
CauseInternal switch-off path - Error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663693 0x2A00508D Description
CauseInternal switch-off path - Test pulse error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663694 0x2A00508E Description
CauseSBC - Test pulse error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663695 0x2A00508F Description
CauseSBC - Remains stuck at LOW
RemedyError in the safe brake control
Severity/responseCheck the supply voltage of the brake. Check the wiring of the brake.
Warning
-
Fault message ID
704663696 0x2A005090 Description
CauseFaulty internal adjustment data
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663828 0x2A005114 Description
CauseReference voltage error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663829 0x2A005115 Description
Cause6 V voltage error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663830 0x2A005116 Description
Cause5 V voltage error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663831 0x2A005117 Description
Cause3.3 V voltage error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704668032 0x2A006180 Description
CauseInternal error - STO activated
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704668037 0x2A006185 Description
CauseCommunication error - Basic device
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704668038 0x2A006186 Description
CauseSynchronization error - Basic device
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Information
-
Fault message ID
704668039 0x2A006187 Description
Severity/responseSBC - Device configuration incompatible
Warning
-
Fault message ID
704668544 0x2A006380 Description
CauseF-parameter error
RemedyError in the PROFIsafe parameter setting The F-PLC is parameterized incorrectly.
Severity/responseCheck PROFIsafe component. Check network cable. Analyze the error history of the higher-level controller.
Information
-
Fault message ID
704668545 0x2A006381 Description
CauseF_Dest_Add unequal F-address
RemedyThe safety address F_Dest_Add in the higher- level controller and the F address in the device are different.
Severity/responseAdapt safety addresses.
Information
-
Fault message ID
704668546 0x2A006382 Description
CauseF_Dest_Add = 0 or FFFFhex
RemedyThe safety address F_Dest_Add in the higher- level controller is invalid.
Severity/responseAdapt safety address.
Information
-
Fault message ID
704668547 0x2A006383 Description
CauseF_Source_Add = 0 or FFFFhex
RemedyThe safety address F_Source_Add in the higher- level controller is invalid.
Severity/responseAdapt safety address.
Information
-
Fault message ID
704668548 0x2A006384 Description
CauseF_WD_Time = 0 ms
RemedyThe monitoring time F_WD_Time in the higher- level controller is invalid.
Severity/responseAdapt parameter setting.
Information
-
Fault message ID
704668549 0x2A006385 Description
CauseF_SIL exceeds technical SIL
RemedyThe SIL parameterized in the higher-level controller is greater than the technically possible SIL of the device.
Severity/responseAdapt parameter setting in the higher-level controller.
Information
-
Fault message ID
704668550 0x2A006386 Description
CauseF_CRC_Length error
RemedyThe data length of the F_CRC in the higher-level controller is faulty.
Severity/responseCheck safety parameter in the higher-level controller.
Information
-
Fault message ID
704668551 0x2A006387 Description
CauseWrong F-parameter version
RemedyThe F parameter version is not supported by the device.
Severity/responseSelect supported F parameter version in the higher-level controller.
Information
-
Fault message ID
704668552 0x2A006388 Description
Severity/responseF_Block_ID not supported
Information
-
Fault message ID
704668553 0x2A006389 Description
CauseSafety parameter set deleted
RemedySafety parameter set deleted
Severity/responseFor information only. No remedy necessary.
Information
-
0x28E5
Parameter
SBC Source S-Bus Data type
U8 Default setting
Disabled [0] Attributes
- -
0x28E6:001
Parameter
SBC: Brake mode Data type
U8 Default setting
SBC without STO [1] Attributes
- -
0x28E6:002
Parameter
SBC: Delay SBC Data type
U16 Default setting
0 ms Attributes
- -
0x28E6:003
Parameter
SBC: Delay STO Data type
U16 Default setting
0 ms Attributes
- -
0x28E6:004
Parameter
SBC: Brake open delay Data type
U16 Default setting
0 ms Attributes
- -
0x28E7:001
Parameter
SBC: "SBC active" - Output Data type
U8 Default setting
Disabled [0] Attributes
- -
0x28E7:002
Parameter
SBC: "SBC activated" - Output Data type
U8 Default setting
Disabled [0] Attributes
- -
0x28E8:001
Parameter
Diagnostic: Configuration diagnostic value 1 Data type
U16 Default setting
PDSS - Current monitored speed [1] Attributes
- -
0x28E8:002
Parameter
Diagnostic: Configuration diagnostic value 2 Data type
U16 Default setting
SS1, SS2 - Current speed ramp [2] Attributes
- -
0x28E9:001
Parameter
Diagnostic: Diagnostic value 1 Data type
I16 Default setting
- (Read only) Attributes
- -
0x28E9:002
Parameter
Diagnostic: Diagnostic value 2 Data type
I16 Default setting
- (Read only) Attributes
- -
0x2900:001
Parameter
Speed controller settings: Gain Data type
U32 Default setting
0.00033 Nm/rpm Attributes
- -
0x2900:002
Parameter
Speed controller settings: Reset time Data type
U16 Default setting
17.6 ms Attributes
- -
0x2900:003
Parameter
Speed controller settings: Rate time Data type
U16 Default setting
0.00 ms Attributes
- -
0x2901
Parameter
Speed controller gain adaption Data type
U16 Default setting
100.00 % Attributes
- -
0x2902
Parameter
I component load value Data type
I16 Default setting
0.0 % Attributes
- -
0x2903
Parameter
Speed setpoint filter time Data type
U16 Default setting
0.0 ms Attributes
- -
0x2904
Parameter
Actual speed filter time Data type
U16 Default setting
0.3 ms Attributes
- -
0x2907:001
Parameter
Additional speed limitation Data type
U32 Default setting
0 rpm Attributes
- -
0x2910:001
Parameter
Inertia settings: Motor moment of inertia Data type
U32 Default setting
0.14 kg cm² Attributes
- -
0x2910:002
Parameter
Inertia settings: Scaled load inertia Data type
U32 Default setting
0.00 kg cm² Attributes
- -
0x2910:003
Parameter
Inertia settings: Coupling Data type
U8 Default setting
Stiff [0] Attributes
- -
0x2910:004
Parameter
Inertia settings: Mechanical natural frequency Data type
U16 Default setting
0.0 Hz Attributes
- -
0x2910:005
Parameter
Inertia settings: Load moment of inertia (elastic coupled) Data type
U32 Default setting
0.00 kg cm² Attributes
- -
0x2922:001
Parameter
Following error diagnostics: Following error (interval) - Time Data type
U16 Default setting
1000 ms Attributes
-
No results.