i950
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 3.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 1.8/1.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.75 kW/1 HP
- Output current 2.4/2.1 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 1.5 kW/2 HP
- Output current 7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 9.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 5.6/4.8 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 4 kW/5 HP
- Output current 16.5 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 4 kW/5 HP
- Output current 9.5/8.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 5.5 kW/7.5 HP
- Output current 23 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 7.5 kW/10 HP
- Output current 16.5/14 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 11 kW/15 HP
- Output current 23.5/21 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 15 kW/20 HP
- Output current 32/27 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 22 kW/30 HP
- Output current 47/40.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 30 kW/40 HP
- Output current 61/52 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 45 kW/60 HP
- Output current 89/77 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 55 kW/75 HP
- Output current 110/96 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 75 kW/100 HP
- Output current 150/124 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 90 kW/125 HP
- Output current 180/156 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 110 kW/150 HP
- Output current 212/180 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
-
Fault message ID
704663684 0x2A005084 Description
CauseIRL - Internal error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663691 0x2A00508B Description
CauseSD-Inx/CLx - Error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663692 0x2A00508C Description
CauseInternal switch-off path - Error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663693 0x2A00508D Description
CauseInternal switch-off path - Test pulse error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663694 0x2A00508E Description
CauseSBC - Test pulse error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663695 0x2A00508F Description
CauseSBC - Remains stuck at LOW
RemedyError in the safe brake control
Severity/responseCheck the supply voltage of the brake. Check the wiring of the brake.
Warning
-
Fault message ID
704663696 0x2A005090 Description
CauseFaulty internal adjustment data
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663828 0x2A005114 Description
CauseReference voltage error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663829 0x2A005115 Description
Cause6 V voltage error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663830 0x2A005116 Description
Cause5 V voltage error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704663831 0x2A005117 Description
Cause3.3 V voltage error
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704668032 0x2A006180 Description
CauseInternal error - STO activated
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704668037 0x2A006185 Description
CauseCommunication error - Basic device
RemedyInternal error
Severity/responseRestart the device. If the error persists, replace the device.
Warning
-
Fault message ID
704668038 0x2A006186 Description
CauseSynchronization error - Basic device
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Information
-
Fault message ID
704668039 0x2A006187 Description
Severity/responseSBC - Device configuration incompatible
Warning
-
Fault message ID
704668544 0x2A006380 Description
CauseF-parameter error
RemedyError in the PROFIsafe parameter setting The F-PLC is parameterized incorrectly.
Severity/responseCheck PROFIsafe component. Check network cable. Analyze the error history of the higher-level controller.
Information
-
Fault message ID
704668545 0x2A006381 Description
CauseF_Dest_Add unequal F-address
RemedyThe safety address F_Dest_Add in the higher- level controller and the F address in the device are different.
Severity/responseAdapt safety addresses.
Information
-
Fault message ID
704668546 0x2A006382 Description
CauseF_Dest_Add = 0 or FFFFhex
RemedyThe safety address F_Dest_Add in the higher- level controller is invalid.
Severity/responseAdapt safety address.
Information
-
Fault message ID
704668547 0x2A006383 Description
CauseF_Source_Add = 0 or FFFFhex
RemedyThe safety address F_Source_Add in the higher- level controller is invalid.
Severity/responseAdapt safety address.
Information
-
Fault message ID
704668548 0x2A006384 Description
CauseF_WD_Time = 0 ms
RemedyThe monitoring time F_WD_Time in the higher- level controller is invalid.
Severity/responseAdapt parameter setting.
Information
-
Fault message ID
704668549 0x2A006385 Description
CauseF_SIL exceeds technical SIL
RemedyThe SIL parameterized in the higher-level controller is greater than the technically possible SIL of the device.
Severity/responseAdapt parameter setting in the higher-level controller.
Information
-
Fault message ID
704668550 0x2A006386 Description
CauseF_CRC_Length error
RemedyThe data length of the F_CRC in the higher-level controller is faulty.
Severity/responseCheck safety parameter in the higher-level controller.
Information
-
Fault message ID
704668551 0x2A006387 Description
CauseWrong F-parameter version
RemedyThe F parameter version is not supported by the device.
Severity/responseSelect supported F parameter version in the higher-level controller.
Information
-
Fault message ID
704668552 0x2A006388 Description
Severity/responseF_Block_ID not supported
Information
-
Fault message ID
704668553 0x2A006389 Description
CauseSafety parameter set deleted
RemedySafety parameter set deleted
Severity/responseFor information only. No remedy necessary.
Information
-
0x1000
Parameter
Device type Data type
U32 Default setting
- (Read only) Attributes
- -
0x1001
Parameter
Error register Data type
U8 Default setting
- (Read only) Attributes
- -
0x1008
Parameter
Manufacturer device name Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x1009
Parameter
Manufacturer hardware version Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x100A
Parameter
Manufacturer software version Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x1018:001
Parameter
Identity object: Vendor ID Data type
U32 Default setting
- (Read only) Attributes
- -
0x1018:002
Parameter
Identity object: Product Code Data type
U32 Default setting
- (Read only) Attributes
- -
0x1018:003
Parameter
Identity object: Revision number Data type
U32 Default setting
- (Read only) Attributes
- -
0x1018:004
Parameter
Identity object: Serial number Data type
U32 Default setting
- (Read only) Attributes
- -
0x10F1:001
Parameter
Error settings: Local error reaction Data type
U32 Default setting
Device specific state [2] Attributes
- -
0x10F1:002
Parameter
Error settings: Sync error counter limit Data type
U16 Default setting
20 Attributes
- -
0x2000:001
Parameter
Device data: Product code Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2000:002
Parameter
Device data: Serial number Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2000:003
Parameter
Device data: Production date Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2000:004
Parameter
Device data: CU firmware version Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2000:006
Parameter
Device data: CU bootloader version Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2000:008
Parameter
Device data: Object directory version Data type
U32 Default setting
- (Read only) Attributes
- -
0x2000:015
Parameter
Device data: Communication firmware revision number Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2000:019
Parameter
Device data: Safety module version Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2001
Parameter
Device name Data type
STRING[128] Default setting
"Device" Attributes
- -
0x2002:001
Parameter
Device module: Safety module Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2002:006
Parameter
Device module: CU serial number Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2002:007
Parameter
Device module: PU serial number Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2002:010
Parameter
Device module: Type communication module Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2002:011
Parameter
Device module: Serial number communication module Data type
STRING[50] Default setting
- (Read only) Attributes
-
No results.