i950
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 3.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 1.8/1.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.75 kW/1 HP
- Output current 2.4/2.1 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 1.5 kW/2 HP
- Output current 7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 9.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 5.6/4.8 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 4 kW/5 HP
- Output current 16.5 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 4 kW/5 HP
- Output current 9.5/8.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 5.5 kW/7.5 HP
- Output current 23 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 7.5 kW/10 HP
- Output current 16.5/14 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 11 kW/15 HP
- Output current 23.5/21 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 15 kW/20 HP
- Output current 32/27 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 22 kW/30 HP
- Output current 47/40.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 30 kW/40 HP
- Output current 61/52 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 45 kW/60 HP
- Output current 89/77 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 55 kW/75 HP
- Output current 110/96 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 75 kW/100 HP
- Output current 150/124 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 90 kW/125 HP
- Output current 180/156 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 110 kW/150 HP
- Output current 212/180 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
-
Fault message ID
805312618 0x3000186A Description
CauseMaster - Stopping failed
RemedyMaster cannot be stopped.
Severity/responseSee related entries in the logbook.
Warning
-
Fault message ID
805312619 0x3000186B Description
CauseMaster - Stopping failed, cannot set Slaves 'Pre-Operational'
RemedySlave error
Severity/responseSee related entries in the logbook.
Warning
-
Fault message ID
805312628 0x30001874 Description
CauseMaster - Shutdown failed
RemedyMaster - Shutdown failed
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805312638 0x3000187E Description
CauseRemote API Server - Start failed
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805312648 0x30001888 Description
CauseStart Download Service
RemedyStart Download Service
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805312649 0x30001889 Description
CauseDownload Service done
RemedyDownload Service done
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805312668 0x3000189C Description
CauseMMC - Internal error
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805312669 0x3000189D Description
CauseMMC - 'Modular Machine Configuration' is active
RemedyMMC - "Modular Machine Configuration" is active.
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805312670 0x3000189E Description
CauseMMC - Service started
RemedyMMC - Service started
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805312671 0x3000189F Description
CauseMMC - Service stopped
RemedyMMC - Service stopped
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805312672 0x300018A0 Description
CauseMMC - Error in configuration files
RemedyMMC configuration file is faulty.
Severity/responseCheck MMC configuration file.
Warning
-
Fault message ID
805312673 0x300018A1 Description
CauseMMC - File does not exist
RemedyMMC - File does not exist
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805312674 0x300018A2 Description
CauseMMC - Parsing error
RemedyMMC configuration file is faulty.
Severity/responseCheck MMC configuration file.
Warning
-
Fault message ID
805312675 0x300018A3 Description
CauseMMC - parsing of file successful
RemedyMMC - parsing of file successful
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805312676 0x300018A4 Description
CauseMMC - Devices not sorted in ascending order or devices missing
RemedyMMC configuration file is faulty.
Severity/responseCheck MMC configuration file.
Warning
-
Fault message ID
805312677 0x300018A5 Description
CauseMMC - Number of devices in device tree differs
RemedyMMC configuration file is faulty.
Severity/responseCheck MMC configuration file. Check network topology.
Warning
-
Fault message ID
805312678 0x300018A6 Description
CauseMMC - Device type mismatch for Alias Address
RemedyMMC configuration file is faulty.
Severity/responseCheck MMC configuration file. Analyze detailed error message in the logbook.
Warning
-
Fault message ID
805312679 0x300018A7 Description
CauseMMC - Invalid Alias Address
RemedyIncorrect alias address.
Severity/responseCheck SSA addresses of the slaves. Analyze detailed error message in the logbook.
Warning
-
Fault message ID
805312680 0x300018A8 Description
CauseMMC - Duplicated Alias Address
RemedyDouble alias address.
Severity/responseCheck SSA addresses of the slaves. Analyze detailed error message in the logbook.
Warning
-
Fault message ID
805312681 0x300018A9 Description
CauseMMC - No configuration checks
RemedyMMC - No configuration checks
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805312682 0x300018AA Description
CauseMMC - Invalid configuration
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805312683 0x300018AB Description
CauseMMC - Mandatory slave missing
RemedyMMC configuration file is faulty. Network topology is faulty.
Severity/responseCheck MMC configuration file. Check network topology.
Warning
-
Fault message ID
805312684 0x300018AC Description
CauseMMC - Optional slave is present, but not allowed
RemedyMMC configuration file is faulty. Network topology is faulty.
Severity/responseCheck MMC configuration file. Check network topology.
Warning
-
Fault message ID
805312685 0x300018AD Description
CauseMMC - No valid service active
RemedyMMC - No valid service active
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805312686 0x300018AE Description
CauseMMC - Address assignment error, less slaves connected than configured
RemedyMMC configuration file is faulty. Network topology is faulty.
Severity/responseAnalyze detailed error message in the logbook. Check MMC configuration file. Check network topology.
Warning
-
0x2C04:015
Parameter
d-axis Lss saturation characteristic: y15 = L15 (x = 87.50 %) Data type
U16 Default setting
41 % Attributes
- -
0x2C04:016
Parameter
d-axis Lss saturation characteristic: y16 = L16 (x = 93.25 %) Data type
U16 Default setting
41 % Attributes
- -
0x2C04:017
Parameter
d-axis Lss saturation characteristic: y17 = L17 (x = 100.00 %) Data type
U16 Default setting
41 % Attributes
- -
0x2C04:018
Parameter
d-axis Lss saturation characteristic: Activation Lss saturation characteristic Data type
U16 Default setting
Adjustment on [1] Attributes
- -
0x2C04:019
Parameter
d-axis Lss saturation characteristic: Cross saturation factor Data type
U16 Default setting
0 % Attributes
- -
0x2C05
Parameter
Reference for current grid points (x) Lss saturation characteristic Data type
U16 Default setting
5.4 A Attributes
- -
0x2C06:001
Parameter
Grid points for magnet characteristic (current): x1 = i01/iN Data type
U16 Default setting
0 % Attributes
- -
0x2C06:002
Parameter
Grid points for magnet characteristic (current): y1 = kT01/kTN Data type
U16 Default setting
100 % Attributes
- -
0x2C06:003
Parameter
Grid points for magnet characteristic (current): x2 = i02/iN Data type
U16 Default setting
100 % Attributes
- -
0x2C06:004
Parameter
Grid points for magnet characteristic (current): y2 = kT02/kTN Data type
U16 Default setting
100 % Attributes
- -
0x2C06:005
Parameter
Grid points for magnet characteristic (current): x3 = i03/iN Data type
U16 Default setting
200 % Attributes
- -
0x2C06:006
Parameter
Grid points for magnet characteristic (current): y3 = kT03/kTN Data type
U16 Default setting
100 % Attributes
- -
0x2C06:007
Parameter
Grid points for magnet characteristic (current): x4 = i04/iN Data type
U16 Default setting
415 % Attributes
- -
0x2C06:008
Parameter
Grid points for magnet characteristic (current): y4 = kT04/kTN Data type
U16 Default setting
72 % Attributes
- -
0x2C07:001
Parameter
Inductance grid points (y) Lh saturation characteristic: y1 = L01 (x = 0.00 %) Data type
U16 Default setting
118 % Attributes
- -
0x2C07:002
Parameter
Inductance grid points (y) Lh saturation characteristic: y2 = L02 (x = 6.25 %) Data type
U16 Default setting
118 % Attributes
- -
0x2C07:003
Parameter
Inductance grid points (y) Lh saturation characteristic: y3 = L03 (x = 12.50 %) Data type
U16 Default setting
118 % Attributes
- -
0x2C07:004
Parameter
Inductance grid points (y) Lh saturation characteristic: y4 = L04 (x = 18.75 %) Data type
U16 Default setting
117 % Attributes
- -
0x2C07:005
Parameter
Inductance grid points (y) Lh saturation characteristic: y5 = L05 (x = 25.00 %) Data type
U16 Default setting
116 % Attributes
- -
0x2C07:006
Parameter
Inductance grid points (y) Lh saturation characteristic: y6 = L06 (x = 31.25 %) Data type
U16 Default setting
114 % Attributes
- -
0x2C07:007
Parameter
Inductance grid points (y) Lh saturation characteristic: y7 = L07 (x = 37.50 %) Data type
U16 Default setting
111 % Attributes
- -
0x2C07:008
Parameter
Inductance grid points (y) Lh saturation characteristic: y8 = L08 (x = 43.75 %) Data type
U16 Default setting
107 % Attributes
- -
0x2C07:009
Parameter
Inductance grid points (y) Lh saturation characteristic: y9 = L09 (x = 50.00 %) Data type
U16 Default setting
100 % Attributes
- -
0x2C07:010
Parameter
Inductance grid points (y) Lh saturation characteristic: y10 = L10 (x = 56.25 %) Data type
U16 Default setting
93 % Attributes
- -
0x2C07:011
Parameter
Inductance grid points (y) Lh saturation characteristic: y11 = L11 (x = 62.50 %) Data type
U16 Default setting
86 % Attributes
-