i950
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 3.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 1.8/1.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.75 kW/1 HP
- Output current 2.4/2.1 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 1.5 kW/2 HP
- Output current 7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 9.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 5.6/4.8 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 4 kW/5 HP
- Output current 16.5 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 4 kW/5 HP
- Output current 9.5/8.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 5.5 kW/7.5 HP
- Output current 23 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 7.5 kW/10 HP
- Output current 16.5/14 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 11 kW/15 HP
- Output current 23.5/21 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 15 kW/20 HP
- Output current 32/27 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 22 kW/30 HP
- Output current 47/40.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 30 kW/40 HP
- Output current 61/52 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 45 kW/60 HP
- Output current 89/77 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 55 kW/75 HP
- Output current 110/96 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 75 kW/100 HP
- Output current 150/124 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 90 kW/125 HP
- Output current 180/156 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 110 kW/150 HP
- Output current 212/180 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
-
Fault message ID
805312618 0x3000186A Description
CauseMaster - Stopping failed
RemedyMaster cannot be stopped.
Severity/responseSee related entries in the logbook.
Warning
-
Fault message ID
805312619 0x3000186B Description
CauseMaster - Stopping failed, cannot set Slaves 'Pre-Operational'
RemedySlave error
Severity/responseSee related entries in the logbook.
Warning
-
Fault message ID
805312628 0x30001874 Description
CauseMaster - Shutdown failed
RemedyMaster - Shutdown failed
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805312638 0x3000187E Description
CauseRemote API Server - Start failed
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805312648 0x30001888 Description
CauseStart Download Service
RemedyStart Download Service
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805312649 0x30001889 Description
CauseDownload Service done
RemedyDownload Service done
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805312668 0x3000189C Description
CauseMMC - Internal error
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805312669 0x3000189D Description
CauseMMC - 'Modular Machine Configuration' is active
RemedyMMC - "Modular Machine Configuration" is active.
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805312670 0x3000189E Description
CauseMMC - Service started
RemedyMMC - Service started
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805312671 0x3000189F Description
CauseMMC - Service stopped
RemedyMMC - Service stopped
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805312672 0x300018A0 Description
CauseMMC - Error in configuration files
RemedyMMC configuration file is faulty.
Severity/responseCheck MMC configuration file.
Warning
-
Fault message ID
805312673 0x300018A1 Description
CauseMMC - File does not exist
RemedyMMC - File does not exist
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805312674 0x300018A2 Description
CauseMMC - Parsing error
RemedyMMC configuration file is faulty.
Severity/responseCheck MMC configuration file.
Warning
-
Fault message ID
805312675 0x300018A3 Description
CauseMMC - parsing of file successful
RemedyMMC - parsing of file successful
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805312676 0x300018A4 Description
CauseMMC - Devices not sorted in ascending order or devices missing
RemedyMMC configuration file is faulty.
Severity/responseCheck MMC configuration file.
Warning
-
Fault message ID
805312677 0x300018A5 Description
CauseMMC - Number of devices in device tree differs
RemedyMMC configuration file is faulty.
Severity/responseCheck MMC configuration file. Check network topology.
Warning
-
Fault message ID
805312678 0x300018A6 Description
CauseMMC - Device type mismatch for Alias Address
RemedyMMC configuration file is faulty.
Severity/responseCheck MMC configuration file. Analyze detailed error message in the logbook.
Warning
-
Fault message ID
805312679 0x300018A7 Description
CauseMMC - Invalid Alias Address
RemedyIncorrect alias address.
Severity/responseCheck SSA addresses of the slaves. Analyze detailed error message in the logbook.
Warning
-
Fault message ID
805312680 0x300018A8 Description
CauseMMC - Duplicated Alias Address
RemedyDouble alias address.
Severity/responseCheck SSA addresses of the slaves. Analyze detailed error message in the logbook.
Warning
-
Fault message ID
805312681 0x300018A9 Description
CauseMMC - No configuration checks
RemedyMMC - No configuration checks
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805312682 0x300018AA Description
CauseMMC - Invalid configuration
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805312683 0x300018AB Description
CauseMMC - Mandatory slave missing
RemedyMMC configuration file is faulty. Network topology is faulty.
Severity/responseCheck MMC configuration file. Check network topology.
Warning
-
Fault message ID
805312684 0x300018AC Description
CauseMMC - Optional slave is present, but not allowed
RemedyMMC configuration file is faulty. Network topology is faulty.
Severity/responseCheck MMC configuration file. Check network topology.
Warning
-
Fault message ID
805312685 0x300018AD Description
CauseMMC - No valid service active
RemedyMMC - No valid service active
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805312686 0x300018AE Description
CauseMMC - Address assignment error, less slaves connected than configured
RemedyMMC configuration file is faulty. Network topology is faulty.
Severity/responseAnalyze detailed error message in the logbook. Check MMC configuration file. Check network topology.
Warning
-
0x243C:001
Parameter
Device: Ethernet commands: Device: Start firmware update Data type
U8 Default setting
Off / ready [0] Attributes
C -
0x2450
Parameter
Engineering port control Data type
U8 Default setting
No action/No error [0] Attributes
- -
0x2451:001
Parameter
Engineering port settings: IP address Data type
U32 Default setting
0.0.0.0 Attributes
E -
0x2451:002
Parameter
Engineering port settings: Subnet Data type
U32 Default setting
0.0.0.0 Attributes
E -
0x2451:003
Parameter
Engineering port settings: Gateway Data type
U32 Default setting
0.0.0.0 Attributes
E -
0x2451:004
Parameter
Engineering port settings: DHCP Data type
U8 Default setting
Enabled [1] Attributes
- -
0x2451:007
Parameter
Engineering port settings: DNS server address Data type
U32 Default setting
0.0.0.0 Attributes
E -
0x2452:001
Parameter
Active engineering port settings: IP address Data type
U32 Default setting
- (Read only) Attributes
E -
0x2452:002
Parameter
Active engineering port settings: Subnet Data type
U32 Default setting
- (Read only) Attributes
E -
0x2452:003
Parameter
Active engineering port settings: Gateway Data type
U32 Default setting
- (Read only) Attributes
E -
0x2452:004
Parameter
Active engineering port settings: DHCP Data type
U8 Default setting
- (Read only) Attributes
- -
0x2452:005
Parameter
Active engineering port settings: MAC address Data type
OCTET[6] Default setting
- (Read only) Attributes
- -
0x2452:006
Parameter
Active engineering port settings: Link status Data type
U8 Default setting
- (Read only) Attributes
- -
0x2452:007
Parameter
Active engineering port settings: DNS server address Data type
U32 Default setting
- (Read only) Attributes
E -
0x245A:001
Parameter
NTP server addresses: Activate NTP server addresses Data type
U8 Default setting
No action/no error [0] Attributes
- -
0x245A:002
Parameter
NTP server addresses: NTP server address 1 Data type
U32 Default setting
0.0.0.0 Attributes
E -
0x245A:003
Parameter
NTP server addresses: NTP server address 2 Data type
U32 Default setting
0.0.0.0 Attributes
E -
0x245A:004
Parameter
NTP server addresses: NTP server address 3 Data type
U32 Default setting
0.0.0.0 Attributes
E -
0x245A:005
Parameter
NTP server addresses: NTP server address 4 Data type
U32 Default setting
0.0.0.0 Attributes
E -
0x245A:006
Parameter
NTP server addresses: NTP server name 1 Data type
STRING[253] Attributes
- -
0x245A:007
Parameter
NTP server addresses: NTP server name 2 Data type
STRING[253] Attributes
- -
0x245A:008
Parameter
NTP server addresses: NTP server name 3 Data type
STRING[253] Attributes
- -
0x245A:009
Parameter
NTP server addresses: NTP server name 4 Data type
STRING[253] Attributes
- -
0x245B:001
Parameter
System time: Setting method Data type
U8 Default setting
NTP server [0] Attributes
- -
0x245B:002
Parameter
System time: Current time Data type
U64 Default setting
ns Attributes
T
No results.