i950
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 3.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 1.8/1.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.75 kW/1 HP
- Output current 2.4/2.1 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 1.5 kW/2 HP
- Output current 7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 9.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 5.6/4.8 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 4 kW/5 HP
- Output current 16.5 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 4 kW/5 HP
- Output current 9.5/8.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 5.5 kW/7.5 HP
- Output current 23 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 7.5 kW/10 HP
- Output current 16.5/14 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 11 kW/15 HP
- Output current 23.5/21 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 15 kW/20 HP
- Output current 32/27 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 22 kW/30 HP
- Output current 47/40.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 30 kW/40 HP
- Output current 61/52 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 45 kW/60 HP
- Output current 89/77 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 55 kW/75 HP
- Output current 110/96 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 75 kW/100 HP
- Output current 150/124 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 90 kW/125 HP
- Output current 180/156 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 110 kW/150 HP
- Output current 212/180 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
-
Fault message ID
805312090 0x3000165A Description
CauseWrong response on 'configured fix address request' for slave
RemedyWrong response to the request.
Severity/responseCheck slave status. Check network topology.
Warning
-
Fault message ID
805312091 0x3000165B Description
CauseWrong response on 'alias address' request for slave
RemedyWrong response to the request.
Severity/responseCheck slave status. Check network topology.
Warning
-
Fault message ID
805312092 0x3000165C Description
CauseCannot execute EC_IOCTL_DC_SLV_SYNC_DEVLIMIT_GET
RemedyThe command cannot be executed
Severity/responseAnalyze detailed error message in the logbook.
Warning
-
Fault message ID
805312093 0x3000165D Description
CauseCannot read latch timer
RemedyRead error
Severity/responseAnalyze detailed error message in the logbook.
Warning
-
Fault message ID
805312094 0x3000165E Description
CauseCannot execute EC_IOCTL_DC_SLV_SYNC_RESTART
RemedyThe command cannot be executed
Severity/responseAnalyze detailed error message in the logbook.
Warning
-
Fault message ID
805312097 0x30001661 Description
CauseRAP - Invalid parameter size
RemedyRAP - Invalid parameter size
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805312098 0x30001662 Description
CauseRAP - Marshaling error
RemedyOrder error
Severity/responseAnalyze detailed error message in the logbook.
Warning
-
Fault message ID
805312099 0x30001663 Description
Severity/responseUnable to enqueue (missing calls to ProcessNotificationJobs)
Warning
-
Fault message ID
805312100 0x30001664 Description
CauseNo connection to slaves
RemedyPossibly the network cable is missing.
Severity/responseCheck slave status. Check network topology.
Warning
-
Fault message ID
805312101 0x30001665 Description
CauseecatSetTargetState cannot set EtherCAT master into target state, master is busy (time-out)
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805312102 0x30001666 Description
CauseecatStop() returns 'Busy', retry...
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805312103 0x30001667 Description
CauseMailbox transfer request - Error
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805312104 0x30001668 Description
CauseMailbox transfer
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805312105 0x30001669 Description
CauseWaiting for mailbox transfer from master...
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805312106 0x3000166A Description
CauseMailbox transfer - Fatal time-out error
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805312107 0x3000166B Description
CauseBus cycle and Sync period are different
RemedyIncorrect setting.
Severity/responseCheck bus cycle. Check sync period.
Warning
-
Fault message ID
805312108 0x3000166C Description
CauseError getting the bus scan state
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805312109 0x3000166D Description
CauseWrong response on DC supported request or slave
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805312110 0x3000166E Description
CauseUnable to set 'DC slave sync disable'
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805312111 0x3000166F Description
CauseError when restarting bus scan
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805312112 0x30001670 Description
CauseBus scan timeout
RemedyThe bus scan was aborted due to timeout.
Severity/responseAnalyze detailed error message in the logbook. Check network topology.
Warning
-
Fault message ID
805312568 0x30001838 Description
CauseConfiguration error - Check of VendorID failed
RemedyThe vendor ID could not be checked.
Severity/responseAnalyze detailed error message in the logbook. Check network topology.
Warning
-
Fault message ID
805312569 0x30001839 Description
CauseConfiguration error - Check of ProductCode failed
RemedyThe product code could not be checked.
Severity/responseAnalyze detailed error message in the logbook. Check network topology.
Warning
-
Fault message ID
805312570 0x3000183A Description
CauseConfiguration error - Check of Revision failed
RemedyThe revision could not be checked.
Severity/responseAnalyze detailed error message in the logbook. Check network topology.
Warning
-
Fault message ID
805312571 0x3000183B Description
CauseConfiguration error - Check of VendorID failed
RemedyThe vendor ID could not be checked.
Severity/responseAnalyze detailed error message in the logbook. Check network topology.
Warning
-
0x28A9:002
Parameter
OMS: Motion function Data type
U8 Default setting
Free mode [11] Attributes
- -
0x28A9:003
Parameter
OMS: Function at low level Data type
U8 Default setting
Normal operation [0] Attributes
- -
0x28AA
Parameter
OMS "OMS active" - Output Data type
U8 Default setting
Disabled [0] Attributes
- -
0x28AB
Parameter
RMS Source Data type
U8 Default setting
Disabled [0] Attributes
- -
0x28AC:001
Parameter
RMS: Stop function Data type
U8 Default setting
STO [0] Attributes
- -
0x28AD
Parameter
RMS "RMS active" - Output Data type
U8 Default setting
Disabled [0] Attributes
- -
0x28AE
Parameter
ES Source Data type
U8 Default setting
Disabled [0] Attributes
- -
0x28AF
Parameter
ES "ES active" - Output Data type
U8 Default setting
Disabled [0] Attributes
- -
0x28B0:001
Parameter
SMS: Maximum speed Nmax Data type
U16 Default setting
0 rpm Attributes
- -
0x28B0:002
Parameter
SMS: Response (n>Nmax) Data type
U8 Default setting
STO [0] Attributes
- -
0x28B1
Parameter
SMS "SMS observed" - Output Data type
U8 Default setting
Disabled [0] Attributes
- -
0x28B2:001
Parameter
SSM: Monitored speed Data type
U16 Default setting
0 rpm Attributes
- -
0x28B3
Parameter
SSM "SSM within limits" - Output Data type
U8 Default setting
Disabled [0] Attributes
- -
0x28B8:001
Parameter
SDI: SDIpos - Source SD-In Data type
U8 Default setting
Disabled [0] Attributes
- -
0x28B8:002
Parameter
SDI: SDIneg - Source SD-In Data type
U8 Default setting
Disabled [0] Attributes
- -
0x28B9:001
Parameter
SDI: SDIpos - Source S-Bus Data type
U8 Default setting
Disabled [0] Attributes
- -
0x28B9:002
Parameter
SDI: SDIneg - Source S-Bus Data type
U8 Default setting
Disabled [0] Attributes
- -
0x28BA:001
Parameter
SDI: Monitoring standard operation Data type
U8 Default setting
Both directions enabled [0] Attributes
- -
0x28BA:002
Parameter
SDI: Delay time Data type
U16 Default setting
0 ms Attributes
- -
0x28BA:003
Parameter
SDI: Tolerance threshold Data type
I32 Default setting
8192 incr. Attributes
- -
0x28BA:004
Parameter
SDI: Error response Data type
U8 Default setting
STO [0] Attributes
- -
0x28BA:005
Parameter
SDI: Maximum change of position Data type
I32 Default setting
x incr. (Read only) Attributes
- -
0x28BB:001
Parameter
SDI: "SDIpos observed" - Output Data type
U8 Default setting
Disabled [0] Attributes
- -
0x28BB:002
Parameter
SDI: "SDIneg observed" - Output Data type
U8 Default setting
Disabled [0] Attributes
- -
0x28BF:001
Parameter
SLS: SLS1 - Internal source Data type
U32 Default setting
Disabled [0] Attributes
-