i950
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 3.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 1.8/1.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.75 kW/1 HP
- Output current 2.4/2.1 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 1.5 kW/2 HP
- Output current 7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 9.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 5.6/4.8 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 4 kW/5 HP
- Output current 16.5 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 4 kW/5 HP
- Output current 9.5/8.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 5.5 kW/7.5 HP
- Output current 23 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 7.5 kW/10 HP
- Output current 16.5/14 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 11 kW/15 HP
- Output current 23.5/21 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 15 kW/20 HP
- Output current 32/27 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 22 kW/30 HP
- Output current 47/40.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 30 kW/40 HP
- Output current 61/52 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 45 kW/60 HP
- Output current 89/77 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 55 kW/75 HP
- Output current 110/96 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 75 kW/100 HP
- Output current 150/124 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 90 kW/125 HP
- Output current 180/156 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 110 kW/150 HP
- Output current 212/180 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
-
Fault message ID
805311914 0x300015AA Description
CauseMissing EtherCAT command in Ethernet frame
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311915 0x300015AB Description
CauseMailbox init command timeout
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311916 0x300015AC Description
CauseAt least one EtherCAT slave not in 'Operational'
RemedyMaster is "Operational". At least one slave is not "Operational".
Severity/responseCheck slave status. Check network topology.
Warning
-
Fault message ID
805311917 0x300015AD Description
CauseEtherCAT cable connected
RemedyEtherCAT cable connected
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805311918 0x300015AE Description
CauseEtherCAT cable not connected
RemedyNetwork cabling is faulty.
Severity/responseCheck network cabling.
Warning
-
Fault message ID
805311919 0x300015AF Description
CauseCyclic commands - Time-out
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311920 0x300015B0 Description
CauseRedundant operation - Ethernet cable is missing at 2nd EtherCAT interface
RemedyNetwork cabling is faulty.
Severity/responseCheck network cabling.
Warning
-
Fault message ID
805311921 0x300015B1 Description
CauseAt least one slave is in state 'Error'
RemedyAt least one slave is in the "Error" state.
Severity/responseCheck slave status. Check network topology.
Warning
-
Fault message ID
805311922 0x300015B2 Description
CauseSlave error
RemedyA slave reports an error.
Severity/responseAnalyze detailed error message in the logbook. Check slave status. Check network topology.
Warning
-
Fault message ID
805311923 0x300015B3 Description
CauseCommunication to device interrupted
RemedyThe connection to the slave is interrupted. The slave does not respond. The slave is no longer available.
Severity/responseCheck slave status. Check network topology.
Warning
-
Fault message ID
805311924 0x300015B4 Description
CauseSDO abort
RemedyCoE access denied.
Severity/responseAnalyze detailed error message in the logbook. Check object properties. Check transfer properties.
Warning
-
Fault message ID
805311925 0x300015B5 Description
CauseDC slaves are 'in-sync'
RemedyDC slaves are 'in-sync'
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805311926 0x300015B6 Description
CauseDC slaves are 'out-of-sync'
RemedyThe DC deviation is outside the permissible limits.
Severity/responseCheck slave status. Check slave properties. Check network topology.
Warning
-
Fault message ID
805311927 0x300015B7 Description
CauseDC single latch on slave
RemedyInternal message
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805311928 0x300015B8 Description
CauseMbxTferRcv - file upload failure
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311929 0x300015B9 Description
CauseMbxTferRcv - file download failure
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311930 0x300015BA Description
CauseClient registration lost
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311931 0x300015BB Description
Severity/responseRedundant operation - Ethernet cable connected
Warning
-
Fault message ID
805311932 0x300015BC Description
Severity/responseSoE write error init command mbox
Warning
-
Fault message ID
805311960 0x300015D8 Description
Severity/responseHot Connect - all groups detected
Warning
-
Fault message ID
805311961 0x300015D9 Description
Severity/responseHot Connect - all group errors detected
Warning
-
Fault message ID
805311962 0x300015DA Description
CauseSlave removed from bus
RemedyA slave has been removed from the network topology.
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805311963 0x300015DB Description
CauseSlave added to bus
RemedyA slave has been added to the network topology.
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805311964 0x300015DC Description
CauseTopology was changed
RemedyThe network topology has been changed.
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805311965 0x300015DD Description
CausePort closed
Remedy"Border Close" has been executed on the port.
Severity/responseAnalyze detailed error message in the logbook.
Warning
-
0x28E5
Parameter
SBC Source S-Bus Data type
U8 Default setting
Disabled [0] Attributes
- -
0x28E6:001
Parameter
SBC: Brake mode Data type
U8 Default setting
SBC without STO [1] Attributes
- -
0x28E6:002
Parameter
SBC: Delay SBC Data type
U16 Default setting
0 ms Attributes
- -
0x28E6:003
Parameter
SBC: Delay STO Data type
U16 Default setting
0 ms Attributes
- -
0x28E6:004
Parameter
SBC: Brake open delay Data type
U16 Default setting
0 ms Attributes
- -
0x28E7:001
Parameter
SBC: "SBC active" - Output Data type
U8 Default setting
Disabled [0] Attributes
- -
0x28E7:002
Parameter
SBC: "SBC activated" - Output Data type
U8 Default setting
Disabled [0] Attributes
- -
0x28E8:001
Parameter
Diagnostic: Configuration diagnostic value 1 Data type
U16 Default setting
PDSS - Current monitored speed [1] Attributes
- -
0x28E8:002
Parameter
Diagnostic: Configuration diagnostic value 2 Data type
U16 Default setting
SS1, SS2 - Current speed ramp [2] Attributes
- -
0x28E9:001
Parameter
Diagnostic: Diagnostic value 1 Data type
I16 Default setting
- (Read only) Attributes
- -
0x28E9:002
Parameter
Diagnostic: Diagnostic value 2 Data type
I16 Default setting
- (Read only) Attributes
- -
0x2900:001
Parameter
Speed controller settings: Gain Data type
U32 Default setting
0.00033 Nm/rpm Attributes
- -
0x2900:002
Parameter
Speed controller settings: Reset time Data type
U16 Default setting
17.6 ms Attributes
- -
0x2900:003
Parameter
Speed controller settings: Rate time Data type
U16 Default setting
0.00 ms Attributes
- -
0x2901
Parameter
Speed controller gain adaption Data type
U16 Default setting
100.00 % Attributes
- -
0x2902
Parameter
I component load value Data type
I16 Default setting
0.0 % Attributes
- -
0x2903
Parameter
Speed setpoint filter time Data type
U16 Default setting
0.0 ms Attributes
- -
0x2904
Parameter
Actual speed filter time Data type
U16 Default setting
0.3 ms Attributes
- -
0x2907:001
Parameter
Additional speed limitation Data type
U32 Default setting
0 rpm Attributes
- -
0x2910:001
Parameter
Inertia settings: Motor moment of inertia Data type
U32 Default setting
0.14 kg cm² Attributes
- -
0x2910:002
Parameter
Inertia settings: Scaled load inertia Data type
U32 Default setting
0.00 kg cm² Attributes
- -
0x2910:003
Parameter
Inertia settings: Coupling Data type
U8 Default setting
Stiff [0] Attributes
- -
0x2910:004
Parameter
Inertia settings: Mechanical natural frequency Data type
U16 Default setting
0.0 Hz Attributes
- -
0x2910:005
Parameter
Inertia settings: Load moment of inertia (elastic coupled) Data type
U32 Default setting
0.00 kg cm² Attributes
- -
0x2922:001
Parameter
Following error diagnostics: Following error (interval) - Time Data type
U16 Default setting
1000 ms Attributes
-