i950
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 3.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 1.8/1.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.75 kW/1 HP
- Output current 2.4/2.1 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 1.5 kW/2 HP
- Output current 7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 9.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 5.6/4.8 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 4 kW/5 HP
- Output current 16.5 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 4 kW/5 HP
- Output current 9.5/8.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 5.5 kW/7.5 HP
- Output current 23 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 7.5 kW/10 HP
- Output current 16.5/14 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 11 kW/15 HP
- Output current 23.5/21 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 15 kW/20 HP
- Output current 32/27 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 22 kW/30 HP
- Output current 47/40.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 30 kW/40 HP
- Output current 61/52 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 45 kW/60 HP
- Output current 89/77 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 55 kW/75 HP
- Output current 110/96 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 75 kW/100 HP
- Output current 150/124 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 90 kW/125 HP
- Output current 180/156 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 110 kW/150 HP
- Output current 212/180 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
-
Fault message ID
805311914 0x300015AA Description
CauseMissing EtherCAT command in Ethernet frame
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311915 0x300015AB Description
CauseMailbox init command timeout
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311916 0x300015AC Description
CauseAt least one EtherCAT slave not in 'Operational'
RemedyMaster is "Operational". At least one slave is not "Operational".
Severity/responseCheck slave status. Check network topology.
Warning
-
Fault message ID
805311917 0x300015AD Description
CauseEtherCAT cable connected
RemedyEtherCAT cable connected
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805311918 0x300015AE Description
CauseEtherCAT cable not connected
RemedyNetwork cabling is faulty.
Severity/responseCheck network cabling.
Warning
-
Fault message ID
805311919 0x300015AF Description
CauseCyclic commands - Time-out
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311920 0x300015B0 Description
CauseRedundant operation - Ethernet cable is missing at 2nd EtherCAT interface
RemedyNetwork cabling is faulty.
Severity/responseCheck network cabling.
Warning
-
Fault message ID
805311921 0x300015B1 Description
CauseAt least one slave is in state 'Error'
RemedyAt least one slave is in the "Error" state.
Severity/responseCheck slave status. Check network topology.
Warning
-
Fault message ID
805311922 0x300015B2 Description
CauseSlave error
RemedyA slave reports an error.
Severity/responseAnalyze detailed error message in the logbook. Check slave status. Check network topology.
Warning
-
Fault message ID
805311923 0x300015B3 Description
CauseCommunication to device interrupted
RemedyThe connection to the slave is interrupted. The slave does not respond. The slave is no longer available.
Severity/responseCheck slave status. Check network topology.
Warning
-
Fault message ID
805311924 0x300015B4 Description
CauseSDO abort
RemedyCoE access denied.
Severity/responseAnalyze detailed error message in the logbook. Check object properties. Check transfer properties.
Warning
-
Fault message ID
805311925 0x300015B5 Description
CauseDC slaves are 'in-sync'
RemedyDC slaves are 'in-sync'
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805311926 0x300015B6 Description
CauseDC slaves are 'out-of-sync'
RemedyThe DC deviation is outside the permissible limits.
Severity/responseCheck slave status. Check slave properties. Check network topology.
Warning
-
Fault message ID
805311927 0x300015B7 Description
CauseDC single latch on slave
RemedyInternal message
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805311928 0x300015B8 Description
CauseMbxTferRcv - file upload failure
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311929 0x300015B9 Description
CauseMbxTferRcv - file download failure
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311930 0x300015BA Description
CauseClient registration lost
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311931 0x300015BB Description
Severity/responseRedundant operation - Ethernet cable connected
Warning
-
Fault message ID
805311932 0x300015BC Description
Severity/responseSoE write error init command mbox
Warning
-
Fault message ID
805311960 0x300015D8 Description
Severity/responseHot Connect - all groups detected
Warning
-
Fault message ID
805311961 0x300015D9 Description
Severity/responseHot Connect - all group errors detected
Warning
-
Fault message ID
805311962 0x300015DA Description
CauseSlave removed from bus
RemedyA slave has been removed from the network topology.
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805311963 0x300015DB Description
CauseSlave added to bus
RemedyA slave has been added to the network topology.
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805311964 0x300015DC Description
CauseTopology was changed
RemedyThe network topology has been changed.
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805311965 0x300015DD Description
CausePort closed
Remedy"Border Close" has been executed on the port.
Severity/responseAnalyze detailed error message in the logbook.
Warning
-
0x2894:005
Parameter
SS1, SS2: Ramp - Start-offset relative Data type
U8 Default setting
5 % Attributes
- -
0x2894:006
Parameter
SS1, SS2: Ramp - Start-offset absolute Data type
U16 Default setting
0 rpm Attributes
- -
0x2894:007
Parameter
SS1, SS2: Ramp - Currently monitored speed Data type
U16 Default setting
x rpm (Read only) Attributes
- -
0x2894:008
Parameter
SS1, SS2: Ramp - Minimum difference Data type
I16 Default setting
x rpm (Read only) Attributes
- -
0x2895
Parameter
SS1 Source SD-In Data type
U8 Default setting
Disabled [0] Attributes
- -
0x2896
Parameter
SS1 Source S-Bus Data type
U8 Default setting
Disabled [0] Attributes
- -
0x2897:001
Parameter
SS1: Mode Data type
U8 Default setting
STO after stopping time [0] Attributes
- -
0x2897:002
Parameter
SS1: Delay STO after n=0 Data type
U16 Default setting
0 ms Attributes
- -
0x2898
Parameter
SS1 "SS1 active" - Output Data type
U8 Default setting
Disabled [0] Attributes
- -
0x2899
Parameter
SS2 Source SD-In Data type
U8 Default setting
Disabled [0] Attributes
- -
0x289A
Parameter
SS2 Source S-Bus Data type
U8 Default setting
Disabled [0] Attributes
- -
0x289B:001
Parameter
SS2: Mode Data type
U8 Default setting
SOS after stopping time [0] Attributes
- -
0x289C
Parameter
SS2 "SS2 active" - Output Data type
U8 Default setting
Disabled [0] Attributes
- -
0x289D
Parameter
SOS Source SD-In Data type
U8 Default setting
Disabled [0] Attributes
- -
0x289E
Parameter
SOS Source S-Bus Data type
U8 Default setting
Disabled [0] Attributes
- -
0x289F:001
Parameter
SOS: Tolerance window (Delta p=0) Data type
I32 Default setting
8192 incr. Attributes
- -
0x289F:002
Parameter
SOS: Restart Data type
U8 Default setting
Acknowledged restart [0] Attributes
- -
0x289F:003
Parameter
SOS: Maximum change of position Data type
I32 Default setting
x incr. (Read only) Attributes
- -
0x28A0
Parameter
SOS "SOS observed" - Output Data type
U8 Default setting
Disabled [0] Attributes
- -
0x28A1
Parameter
SSE Source SD-In Data type
U8 Default setting
Disabled [0] Attributes
- -
0x28A2
Parameter
SSE Source S-Bus Data type
U8 Default setting
Disabled [0] Attributes
- -
0x28A3:001
Parameter
SSE: Emergency stop function Data type
U8 Default setting
STO [0] Attributes
- -
0x28A4
Parameter
SSE "SSE active" - Output Data type
U8 Default setting
Disabled [0] Attributes
- -
0x28A8
Parameter
OMS Source Data type
U8 Default setting
Disabled [0] Attributes
- -
0x28A9:001
Parameter
OMS: Stop function Data type
U8 Default setting
STO [0] Attributes
-