i950
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 3.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 1.8/1.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.75 kW/1 HP
- Output current 2.4/2.1 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 1.5 kW/2 HP
- Output current 7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 9.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 5.6/4.8 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 4 kW/5 HP
- Output current 16.5 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 4 kW/5 HP
- Output current 9.5/8.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 5.5 kW/7.5 HP
- Output current 23 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 7.5 kW/10 HP
- Output current 16.5/14 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 11 kW/15 HP
- Output current 23.5/21 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 15 kW/20 HP
- Output current 32/27 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 22 kW/30 HP
- Output current 47/40.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 30 kW/40 HP
- Output current 61/52 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 45 kW/60 HP
- Output current 89/77 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 55 kW/75 HP
- Output current 110/96 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 75 kW/100 HP
- Output current 150/124 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 90 kW/125 HP
- Output current 180/156 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 110 kW/150 HP
- Output current 212/180 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
-
Fault message ID
805311914 0x300015AA Description
CauseMissing EtherCAT command in Ethernet frame
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311915 0x300015AB Description
CauseMailbox init command timeout
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311916 0x300015AC Description
CauseAt least one EtherCAT slave not in 'Operational'
RemedyMaster is "Operational". At least one slave is not "Operational".
Severity/responseCheck slave status. Check network topology.
Warning
-
Fault message ID
805311917 0x300015AD Description
CauseEtherCAT cable connected
RemedyEtherCAT cable connected
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805311918 0x300015AE Description
CauseEtherCAT cable not connected
RemedyNetwork cabling is faulty.
Severity/responseCheck network cabling.
Warning
-
Fault message ID
805311919 0x300015AF Description
CauseCyclic commands - Time-out
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311920 0x300015B0 Description
CauseRedundant operation - Ethernet cable is missing at 2nd EtherCAT interface
RemedyNetwork cabling is faulty.
Severity/responseCheck network cabling.
Warning
-
Fault message ID
805311921 0x300015B1 Description
CauseAt least one slave is in state 'Error'
RemedyAt least one slave is in the "Error" state.
Severity/responseCheck slave status. Check network topology.
Warning
-
Fault message ID
805311922 0x300015B2 Description
CauseSlave error
RemedyA slave reports an error.
Severity/responseAnalyze detailed error message in the logbook. Check slave status. Check network topology.
Warning
-
Fault message ID
805311923 0x300015B3 Description
CauseCommunication to device interrupted
RemedyThe connection to the slave is interrupted. The slave does not respond. The slave is no longer available.
Severity/responseCheck slave status. Check network topology.
Warning
-
Fault message ID
805311924 0x300015B4 Description
CauseSDO abort
RemedyCoE access denied.
Severity/responseAnalyze detailed error message in the logbook. Check object properties. Check transfer properties.
Warning
-
Fault message ID
805311925 0x300015B5 Description
CauseDC slaves are 'in-sync'
RemedyDC slaves are 'in-sync'
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805311926 0x300015B6 Description
CauseDC slaves are 'out-of-sync'
RemedyThe DC deviation is outside the permissible limits.
Severity/responseCheck slave status. Check slave properties. Check network topology.
Warning
-
Fault message ID
805311927 0x300015B7 Description
CauseDC single latch on slave
RemedyInternal message
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805311928 0x300015B8 Description
CauseMbxTferRcv - file upload failure
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311929 0x300015B9 Description
CauseMbxTferRcv - file download failure
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311930 0x300015BA Description
CauseClient registration lost
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311931 0x300015BB Description
Severity/responseRedundant operation - Ethernet cable connected
Warning
-
Fault message ID
805311932 0x300015BC Description
Severity/responseSoE write error init command mbox
Warning
-
Fault message ID
805311960 0x300015D8 Description
Severity/responseHot Connect - all groups detected
Warning
-
Fault message ID
805311961 0x300015D9 Description
Severity/responseHot Connect - all group errors detected
Warning
-
Fault message ID
805311962 0x300015DA Description
CauseSlave removed from bus
RemedyA slave has been removed from the network topology.
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805311963 0x300015DB Description
CauseSlave added to bus
RemedyA slave has been added to the network topology.
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805311964 0x300015DC Description
CauseTopology was changed
RemedyThe network topology has been changed.
Severity/responseFor information only. No remedy necessary.
Warning
-
Fault message ID
805311965 0x300015DD Description
CausePort closed
Remedy"Border Close" has been executed on the port.
Severity/responseAnalyze detailed error message in the logbook.
Warning
-
0x1000
Parameter
Device type Data type
U32 Default setting
- (Read only) Attributes
- -
0x1001
Parameter
Error register Data type
U8 Default setting
- (Read only) Attributes
- -
0x1008
Parameter
Manufacturer device name Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x1009
Parameter
Manufacturer hardware version Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x100A
Parameter
Manufacturer software version Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x1018:001
Parameter
Identity object: Vendor ID Data type
U32 Default setting
- (Read only) Attributes
- -
0x1018:002
Parameter
Identity object: Product Code Data type
U32 Default setting
- (Read only) Attributes
- -
0x1018:003
Parameter
Identity object: Revision number Data type
U32 Default setting
- (Read only) Attributes
- -
0x1018:004
Parameter
Identity object: Serial number Data type
U32 Default setting
- (Read only) Attributes
- -
0x10F1:001
Parameter
Error settings: Local error reaction Data type
U32 Default setting
Device specific state [2] Attributes
- -
0x10F1:002
Parameter
Error settings: Sync error counter limit Data type
U16 Default setting
20 Attributes
- -
0x2000:001
Parameter
Device data: Product code Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2000:002
Parameter
Device data: Serial number Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2000:003
Parameter
Device data: Production date Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2000:004
Parameter
Device data: CU firmware version Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2000:006
Parameter
Device data: CU bootloader version Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2000:008
Parameter
Device data: Object directory version Data type
U32 Default setting
- (Read only) Attributes
- -
0x2000:015
Parameter
Device data: Communication firmware revision number Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2000:019
Parameter
Device data: Safety module version Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2001
Parameter
Device name Data type
STRING[128] Default setting
"Device" Attributes
- -
0x2002:001
Parameter
Device module: Safety module Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2002:006
Parameter
Device module: CU serial number Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2002:007
Parameter
Device module: PU serial number Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2002:010
Parameter
Device module: Type communication module Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x2002:011
Parameter
Device module: Serial number communication module Data type
STRING[50] Default setting
- (Read only) Attributes
-
No results.