i950
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 3.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 1.8/1.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.75 kW/1 HP
- Output current 2.4/2.1 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 1.5 kW/2 HP
- Output current 7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 9.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 5.6/4.8 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 4 kW/5 HP
- Output current 16.5 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 4 kW/5 HP
- Output current 9.5/8.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 5.5 kW/7.5 HP
- Output current 23 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 7.5 kW/10 HP
- Output current 16.5/14 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 11 kW/15 HP
- Output current 23.5/21 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 15 kW/20 HP
- Output current 32/27 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 22 kW/30 HP
- Output current 47/40.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 30 kW/40 HP
- Output current 61/52 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 45 kW/60 HP
- Output current 89/77 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 55 kW/75 HP
- Output current 110/96 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 75 kW/100 HP
- Output current 150/124 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 90 kW/125 HP
- Output current 180/156 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 110 kW/150 HP
- Output current 212/180 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
-
Fault message ID
805311434 0x300013CA Description
CauseCoE - SDO Abort 'Client/server command specifier not valid or unknown (0x05040001)'
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311435 0x300013CB Description
CauseCoE - SDO Abort 'Invalid block size (block mode only) (0x05040002)'
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311436 0x300013CC Description
CauseCoE - SDO Abort 'Invalid sequence number (block mode only) (0x05040003)'
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311437 0x300013CD Description
CauseCoE - SDO Abort 'CRC error (block mode only) (0x05040004)'
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311438 0x300013CE Description
CauseCoE - SDO Abort 'Out of memory (0x05040005)'
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311439 0x300013CF Description
CauseCoE - SDO Abort 'Unsupported access to an object (0x06010000)'
RemedyAccess denied.
Severity/responseCheck access authorization.
Warning
-
Fault message ID
805311440 0x300013D0 Description
CauseCoE - SDO Abort 'Attempt to read a write only object (0x06010001)'
RemedyAccess denied.
Severity/responseCheck access authorization.
Warning
-
Fault message ID
805311441 0x300013D1 Description
CauseCoE - SDO Abort 'Attempt to write a read only object (0x06010002)'
RemedyAccess denied.
Severity/responseCheck access authorization.
Warning
-
Fault message ID
805311442 0x300013D2 Description
CauseCoE - SDO-Abort 'Object does not exist in the object dictionary (0x06020000)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check if object exists.
Warning
-
Fault message ID
805311443 0x300013D3 Description
CauseCoE - SDO Abort 'Object cannot be mapped to the PDO (0x06040041)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check if object exists.
Warning
-
Fault message ID
805311444 0x300013D4 Description
CauseCoE - SDO Abort 'Number and length of objects to be mapped exceed PDO length (0x06040042)'
RemedyAccess denied.
Severity/responseCheck the length of the objects to be mapped.
Warning
-
Fault message ID
805311445 0x300013D5 Description
CauseCoE - SDO Abort 'General parameter incompatibility (0x06040043)'
RemedyAccess denied.
Severity/responseCheck access authorization.
Warning
-
Fault message ID
805311446 0x300013D6 Description
CauseCoE - SDO Abort 'General internal incompatibility in the device (0x06040047)'
RemedyAccess denied.
Severity/responseCheck access authorization.
Warning
-
Fault message ID
805311447 0x300013D7 Description
CauseCoE - SDO Abort 'Access failed due to an hardware error (0x06060000)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check object properties.
Warning
-
Fault message ID
805311448 0x300013D8 Description
CauseCoE - SDO Abort 'Data type or length of service parameters do not match (0x06070010)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check object properties.
Warning
-
Fault message ID
805311449 0x300013D9 Description
CauseCoE - SDO Abort 'Data type does not match, service parameter too high (0x06070012)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check object properties.
Warning
-
Fault message ID
805311450 0x300013DA Description
CauseCoE - SDO Abort 'Data type does not match, service parameter too low (0x06070013)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check object properties.
Warning
-
Fault message ID
805311451 0x300013DB Description
CauseCoE - SDO Abort 'Subindex does not exist (0x06090011)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check object properties.
Warning
-
Fault message ID
805311452 0x300013DC Description
CauseCoE - SDO Abort 'Write access - Parameter value exceeds limits (0x06090030)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check object properties.
Warning
-
Fault message ID
805311453 0x300013DD Description
CauseCoE - SDO Abort 'Write access - Parameter value too high (0x06090031)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check object properties.
Warning
-
Fault message ID
805311454 0x300013DE Description
CauseCoE - SDO Abort 'Write access - Parameter value too low (0x06090032)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check object properties.
Warning
-
Fault message ID
805311455 0x300013DF Description
CauseCoE - SDO Abort 'Maximum value less than minimum value (0x06090036)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check object properties.
Warning
-
Fault message ID
805311456 0x300013E0 Description
CauseCoE - SDO Abort 'General error (0x08000000)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check object properties.
Warning
-
Fault message ID
805311457 0x300013E1 Description
CauseCoE - SDO Abort 'Data cannot be transferred/stored in application (0x08000020)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check object properties.
Warning
-
Fault message ID
805311458 0x300013E2 Description
CauseCoE - SDO Abort 'Local control - Data cannot be transferred/stored in application (0x08000021)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check object properties.
Warning
-
0x2980
Parameter
Position controller gain Data type
U32 Default setting
28.40 1/s Attributes
- -
0x2981
Parameter
Position controller gain adaption Data type
U16 Default setting
100.00 % Attributes
- -
0x2982
Parameter
Position controller output signal limitation Data type
U32 Default setting
480000.00 rpm Attributes
- -
0x2983
Parameter
Actual position start value Data type
I32 Default setting
0 Attributes
- -
0x2984
Parameter
Mode for setting the actual position Data type
U8 Default setting
Absolute [0] Attributes
- -
0x2986
Parameter
Resulting gain adaption Data type
U32 Default setting
x.xx % (Read only) Attributes
- -
0x29C0:001
Parameter
Field controller settings: Gain Data type
U32 Default setting
165.84 A/Vs Attributes
- -
0x29C0:002
Parameter
Field controller settings: Reset time Data type
U16 Default setting
15.1 ms Attributes
- -
0x29E0:001
Parameter
Field weakening controller settings: Gain (ASM) Data type
U32 Default setting
0.000 Vs/V Attributes
- -
0x29E0:002
Parameter
Field weakening controller settings: Reset time (ASM) Data type
U32 Default setting
2000.0 ms Attributes
- -
0x29E1
Parameter
Field weakening controller Field limitation Data type
U16 Default setting
100.00 % Attributes
- -
0x29E2
Parameter
DC-bus filter time Data type
U16 Default setting
25.0 ms Attributes
- -
0x29E3
Parameter
Motor voltage filter time Data type
U16 Default setting
25.0 ms Attributes
- -
0x29E4
Parameter
Voltage reserve range Data type
U8 Default setting
5 % Attributes
- -
0x2B00
Parameter
V/f characteristic shape Data type
U8 Default setting
Linear [0] Attributes
C -
0x2B01:001
Parameter
V/f shape data: Base voltage Data type
U16 Default setting
225 V Attributes
- -
0x2B01:002
Parameter
V/f shape data: Base frequency Data type
U16 Default setting
270 Hz Attributes
- -
0x2B02:001
Parameter
Frequency grid points (x) user V/f characteristic: x1 = f01 Data type
I16 Default setting
-50 Hz Attributes
- -
0x2B02:002
Parameter
Frequency grid points (x) user V/f characteristic: x2 = f02 Data type
I16 Default setting
-40 Hz Attributes
- -
0x2B02:003
Parameter
Frequency grid points (x) user V/f characteristic: x3 = f03 Data type
I16 Default setting
-30 Hz Attributes
- -
0x2B02:004
Parameter
Frequency grid points (x) user V/f characteristic: x4 = f04 Data type
I16 Default setting
-20 Hz Attributes
- -
0x2B02:005
Parameter
Frequency grid points (x) user V/f characteristic: x5 = f05 Data type
I16 Default setting
-10 Hz Attributes
- -
0x2B02:006
Parameter
Frequency grid points (x) user V/f characteristic: x6 = f06 Data type
I16 Default setting
0 Hz Attributes
- -
0x2B02:007
Parameter
Frequency grid points (x) user V/f characteristic: x7 = f07 Data type
I16 Default setting
10 Hz Attributes
- -
0x2B02:008
Parameter
Frequency grid points (x) user V/f characteristic: x8 = f08 Data type
I16 Default setting
20 Hz Attributes
-