i950
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 3.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 1.8/1.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.75 kW/1 HP
- Output current 2.4/2.1 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 1.5 kW/2 HP
- Output current 7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 9.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 5.6/4.8 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 4 kW/5 HP
- Output current 16.5 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 4 kW/5 HP
- Output current 9.5/8.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 5.5 kW/7.5 HP
- Output current 23 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 7.5 kW/10 HP
- Output current 16.5/14 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 11 kW/15 HP
- Output current 23.5/21 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 15 kW/20 HP
- Output current 32/27 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 22 kW/30 HP
- Output current 47/40.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 30 kW/40 HP
- Output current 61/52 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 45 kW/60 HP
- Output current 89/77 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 55 kW/75 HP
- Output current 110/96 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 75 kW/100 HP
- Output current 150/124 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 90 kW/125 HP
- Output current 180/156 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 110 kW/150 HP
- Output current 212/180 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
-
Fault message ID
805311434 0x300013CA Description
CauseCoE - SDO Abort 'Client/server command specifier not valid or unknown (0x05040001)'
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311435 0x300013CB Description
CauseCoE - SDO Abort 'Invalid block size (block mode only) (0x05040002)'
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311436 0x300013CC Description
CauseCoE - SDO Abort 'Invalid sequence number (block mode only) (0x05040003)'
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311437 0x300013CD Description
CauseCoE - SDO Abort 'CRC error (block mode only) (0x05040004)'
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311438 0x300013CE Description
CauseCoE - SDO Abort 'Out of memory (0x05040005)'
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311439 0x300013CF Description
CauseCoE - SDO Abort 'Unsupported access to an object (0x06010000)'
RemedyAccess denied.
Severity/responseCheck access authorization.
Warning
-
Fault message ID
805311440 0x300013D0 Description
CauseCoE - SDO Abort 'Attempt to read a write only object (0x06010001)'
RemedyAccess denied.
Severity/responseCheck access authorization.
Warning
-
Fault message ID
805311441 0x300013D1 Description
CauseCoE - SDO Abort 'Attempt to write a read only object (0x06010002)'
RemedyAccess denied.
Severity/responseCheck access authorization.
Warning
-
Fault message ID
805311442 0x300013D2 Description
CauseCoE - SDO-Abort 'Object does not exist in the object dictionary (0x06020000)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check if object exists.
Warning
-
Fault message ID
805311443 0x300013D3 Description
CauseCoE - SDO Abort 'Object cannot be mapped to the PDO (0x06040041)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check if object exists.
Warning
-
Fault message ID
805311444 0x300013D4 Description
CauseCoE - SDO Abort 'Number and length of objects to be mapped exceed PDO length (0x06040042)'
RemedyAccess denied.
Severity/responseCheck the length of the objects to be mapped.
Warning
-
Fault message ID
805311445 0x300013D5 Description
CauseCoE - SDO Abort 'General parameter incompatibility (0x06040043)'
RemedyAccess denied.
Severity/responseCheck access authorization.
Warning
-
Fault message ID
805311446 0x300013D6 Description
CauseCoE - SDO Abort 'General internal incompatibility in the device (0x06040047)'
RemedyAccess denied.
Severity/responseCheck access authorization.
Warning
-
Fault message ID
805311447 0x300013D7 Description
CauseCoE - SDO Abort 'Access failed due to an hardware error (0x06060000)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check object properties.
Warning
-
Fault message ID
805311448 0x300013D8 Description
CauseCoE - SDO Abort 'Data type or length of service parameters do not match (0x06070010)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check object properties.
Warning
-
Fault message ID
805311449 0x300013D9 Description
CauseCoE - SDO Abort 'Data type does not match, service parameter too high (0x06070012)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check object properties.
Warning
-
Fault message ID
805311450 0x300013DA Description
CauseCoE - SDO Abort 'Data type does not match, service parameter too low (0x06070013)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check object properties.
Warning
-
Fault message ID
805311451 0x300013DB Description
CauseCoE - SDO Abort 'Subindex does not exist (0x06090011)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check object properties.
Warning
-
Fault message ID
805311452 0x300013DC Description
CauseCoE - SDO Abort 'Write access - Parameter value exceeds limits (0x06090030)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check object properties.
Warning
-
Fault message ID
805311453 0x300013DD Description
CauseCoE - SDO Abort 'Write access - Parameter value too high (0x06090031)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check object properties.
Warning
-
Fault message ID
805311454 0x300013DE Description
CauseCoE - SDO Abort 'Write access - Parameter value too low (0x06090032)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check object properties.
Warning
-
Fault message ID
805311455 0x300013DF Description
CauseCoE - SDO Abort 'Maximum value less than minimum value (0x06090036)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check object properties.
Warning
-
Fault message ID
805311456 0x300013E0 Description
CauseCoE - SDO Abort 'General error (0x08000000)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check object properties.
Warning
-
Fault message ID
805311457 0x300013E1 Description
CauseCoE - SDO Abort 'Data cannot be transferred/stored in application (0x08000020)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check object properties.
Warning
-
Fault message ID
805311458 0x300013E2 Description
CauseCoE - SDO Abort 'Local control - Data cannot be transferred/stored in application (0x08000021)'
RemedyAccess denied.
Severity/responseCheck access authorization. Check object properties.
Warning
-
0x2822:029
Parameter
Axis commands: Get load encoder/master encoder characteristic (resolver) Data type
U8 Default setting
Off/Ready [0] Attributes
- -
0x2822:030
Parameter
Axis commands: Get load encoder/master encoder information (HIPERFACE®) Data type
U8 Default setting
Off/Ready [0] Attributes
- -
0x2822:037
Parameter
Axis commands: Estimate all motor parameters based on rated data Data type
U8 Default setting
Off/Ready [0] Attributes
- -
0x2822:038
Parameter
Axis commands: HIPERFACE (A): Set position with synchronization Data type
U8 Default setting
Off/Ready [0] Attributes
- -
0x2822:039
Parameter
Axis commands: HIPERFACE (A): Set position with synchronization Data type
U8 Default setting
Off/Ready [0] Attributes
- -
0x2822:042
Parameter
Axis commands: Calculate speed filter time constant Data type
U8 Default setting
Off/Ready [0] Attributes
- -
0x2822:043
Parameter
Axis commands: Load power dependent motor parameters Data type
U8 Default setting
RANLI_C2822_S043_GEN_V00000000 [0] Attributes
- -
0x2822:044
Parameter
Axis commands: Cogging torque compensation Data type
U8 Default setting
RANLI_C2822_S044_GEN_V00000000 [0] Attributes
- -
0x2823
Parameter
Status of axis commands Data type
U8 Default setting
x % (Read only) Attributes
- -
0x2824
Parameter
Control via PDO/Application Data type
U8 Default setting
Keypad [1] Attributes
C -
0x2825
Parameter
Drive mode selection Data type
U8 Default setting
CiA402 operating modes [0] Attributes
C -
0x2826
Parameter
Timeout for error response -> quickstop Data type
U32 Default setting
4 s Attributes
- -
0x282A:001
Parameter
Status words: Cause of disable Data type
U32 Default setting
- (Read only) Attributes
H -
0x282A:004
Parameter
Status words: Extended status word Data type
U16 Default setting
- (Read only) Attributes
H -
0x282C:001
Parameter
I/O diagnostic: Application level of the digital inputs Data type
U32 Default setting
- (Read only) Attributes
H -
0x282C:002
Parameter
I/O diagnostic: Digital output levels Data type
U32 Default setting
- (Read only) Attributes
H -
0x2830
Parameter
Inverter control word Data type
U16 Default setting
0x0000 Attributes
H -
0x2831
Parameter
Inverter status word Data type
U16 Default setting
- (Read only) Attributes
H -
0x2832
Parameter
Identification status Data type
U16 Default setting
- (Read only) Attributes
H -
0x2833
Parameter
Inverter status word 2 Data type
U16 Default setting
- (Read only) Attributes
H -
0x2835:001
Parameter
Manual test mode: Current setpoint Data type
I16 Default setting
0 % Attributes
- -
0x2835:002
Parameter
Manual test mode: Frequency Data type
I16 Default setting
0.0 Hz Attributes
- -
0x2835:003
Parameter
Manual test mode: Starting angle Data type
I16 Default setting
0.0 ° Attributes
- -
0x2836:001
Parameter
Manual control mode: Current setpoint Data type
U16 Default setting
30 % Attributes
- -
0x2836:002
Parameter
Manual control mode: Frequency Data type
I16 Default setting
0.0 Hz Attributes
-