i950
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 3.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 1.8/1.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.75 kW/1 HP
- Output current 2.4/2.1 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 1.5 kW/2 HP
- Output current 7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 9.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 5.6/4.8 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 4 kW/5 HP
- Output current 16.5 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 4 kW/5 HP
- Output current 9.5/8.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 5.5 kW/7.5 HP
- Output current 23 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 7.5 kW/10 HP
- Output current 16.5/14 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 11 kW/15 HP
- Output current 23.5/21 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 15 kW/20 HP
- Output current 32/27 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 22 kW/30 HP
- Output current 47/40.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 30 kW/40 HP
- Output current 61/52 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 45 kW/60 HP
- Output current 89/77 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 55 kW/75 HP
- Output current 110/96 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 75 kW/100 HP
- Output current 150/124 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 90 kW/125 HP
- Output current 180/156 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 110 kW/150 HP
- Output current 212/180 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
-
Fault message ID
805311369 0x30001389 Description
CauseCTRL - Feature not supported
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311370 0x3000138A Description
CauseCTRL - Invalid index
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311371 0x3000138B Description
CauseISW - Invalid offset
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311373 0x3000138D Description
CauseCTRL - Invalid size
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311374 0x3000138E Description
CauseISW - Invalid data
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311375 0x3000138F Description
CauseISW - Not ready
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311376 0x30001390 Description
CauseCTRL - Busy
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311377 0x30001391 Description
CauseISW - Cannot queue acyclic EtherCAT command
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311378 0x30001392 Description
CauseCFG - No memory left
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311379 0x30001393 Description
CauseCTRL - Invalid parameter
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311380 0x30001394 Description
CauseCTRL - Not found
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311382 0x30001396 Description
CauseISW - Invalid state
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311383 0x30001397 Description
CauseISW - Cannot add slave to timer list
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311384 0x30001398 Description
CauseSLV - Time-out
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311385 0x30001399 Description
CauseISW - Open failed
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311386 0x3000139A Description
CauseLLA - Send failed
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311387 0x3000139B Description
CauseCFG - Error when queuing a mailbox command
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311388 0x3000139C Description
CauseISW - Invalid mailbox command
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311389 0x3000139D Description
CauseISW - Unknown mailbox protocol command
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311390 0x3000139E Description
CauseISW - Access denied
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311394 0x300013A2 Description
CauseCFG - Invalid product key
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311395 0x300013A3 Description
CausePRJ - Wrong format of master XML file
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311396 0x300013A4 Description
CauseCTRL - Function disabled
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311398 0x300013A6 Description
CausePRJ - Mismatch of bus configuration and number of connected slaves
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
805311399 0x300013A7 Description
CausePRJ - Error reading master XML file
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
0xA680:010
Parameter
Systembus input data: Systembus data input 10 Data type
U32 Default setting
0 Attributes
- -
0xA680:011
Parameter
Systembus input data: Systembus data input 11 Data type
U32 Default setting
0 Attributes
- -
0xA680:012
Parameter
Systembus input data: Systembus data input 12 Data type
U32 Default setting
0 Attributes
- -
0xA680:013
Parameter
Systembus input data: Systembus data input 13 Data type
U32 Default setting
0 Attributes
- -
0xA680:014
Parameter
Systembus input data: Systembus data input 14 Data type
U32 Default setting
0 Attributes
- -
0xA680:015
Parameter
Systembus input data: Systembus data input 15 Data type
U32 Default setting
0 Attributes
- -
0xA680:016
Parameter
Systembus input data: Systembus data input 16 Data type
U32 Default setting
0 Attributes
- -
0xE600:001
Parameter
FSoE Slave Frame Elements: Command Data type
U8 Default setting
- (Read only) Attributes
- -
0xE600:002
Parameter
FSoE Slave Frame Elements: Connection ID Data type
U16 Default setting
- (Read only) Attributes
- -
0xE600:003
Parameter
FSoE Slave Frame Elements: CRC_0 Data type
U16 Default setting
- (Read only) Attributes
- -
0xE600:004
Parameter
FSoE Slave Frame Elements: CRC_1 Data type
U16 Default setting
- (Read only) Attributes
- -
0xE600:005
Parameter
FSoE Slave Frame Elements: CRC_2 Data type
U16 Default setting
- (Read only) Attributes
- -
0xE600:006
Parameter
FSoE Slave Frame Elements: CRC_3 Data type
U16 Default setting
- (Read only) Attributes
- -
0xE600:007
Parameter
FSoE Slave Frame Elements: CRC_4 Data type
U16 Default setting
- (Read only) Attributes
- -
0xE600:008
Parameter
FSoE Slave Frame Elements: CRC_5 Data type
U16 Default setting
- (Read only) Attributes
- -
0xE600:009
Parameter
FSoE Slave Frame Elements: CRC_6 Data type
U16 Default setting
- (Read only) Attributes
- -
0xE700:001
Parameter
FSoE Master Frame Elements: Command Data type
U8 Default setting
- (Read only) Attributes
- -
0xE700:002
Parameter
FSoE Master Frame Elements: Connection ID Data type
U16 Default setting
- (Read only) Attributes
- -
0xE700:003
Parameter
FSoE Master Frame Elements: CRC_0 Data type
U16 Default setting
- (Read only) Attributes
- -
0xE700:004
Parameter
FSoE Master Frame Elements: CRC_1 Data type
U16 Default setting
- (Read only) Attributes
- -
0xE901:001
Parameter
FSoE Connection Communication Parameter: Version Data type
STRING[2] Default setting
- (Read only) Attributes
- -
0xE901:002
Parameter
FSoE Connection Communication Parameter: Safety address Data type
U16 Default setting
- (Read only) Attributes
- -
0xE901:003
Parameter
FSoE Connection Communication Parameter: Connection ID Data type
U16 Default setting
- (Read only) Attributes
- -
0xE901:004
Parameter
FSoE Connection Communication Parameter: Watchdog Time Data type
U16 Default setting
- (Read only) Attributes
- -
0xE901:006
Parameter
FSoE Connection Communication Parameter: Connection Type Data type
U16 Default setting
- (Read only) Attributes
-
No results.