i950
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 3.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 1.8/1.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 0.75 kW/1 HP
- Output current 2.4/2.1 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 1.5 kW/2 HP
- Output current 7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 9.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 5.6/4.8 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 4 kW/5 HP
- Output current 16.5 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 4 kW/5 HP
- Output current 9.5/8.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 5.5 kW/7.5 HP
- Output current 23 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 230/240 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter not integrated
- Rated power 7.5 kW/10 HP
- Output current 16.5/14 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 11 kW/15 HP
- Output current 23.5/21 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 15 kW/20 HP
- Output current 32/27 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 22 kW/30 HP
- Output current 47/40.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 30 kW/40 HP
- Output current 61/52 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 45 kW/60 HP
- Output current 89/77 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 55 kW/75 HP
- Output current 110/96 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 75 kW/100 HP
- Output current 150/124 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 90 kW/125 HP
- Output current 180/156 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
- Rated power 110 kW/150 HP
- Output current 212/180 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation B
- Product series i950 cabinet
- EMC filter Integrated
-
Fault message ID
0 0x00000000 Description
CauseNo error
RemedyNo error
Severity/responseFor information only. No remedy necessary.
Information
-
Fault message ID
537469777 0x20092351 Description
CauseMotor utilization too high (i²xt)
RemedyMotor thermally overloaded, e.g. by an impermissible continuous current or by frequent or too long acceleration processes.
Severity/responseCheck drive sizing. Check the setting in the warning threshold or error threshold.
Fehler > CiA402 (configurable)
Setting parameters: 0x2D50:001
-
Fault message ID
537469824 0x20092380 Description
CauseTrouble - utilization of the power section (ixt) too high
RemedyPower section overloaded.
Severity/responseCheck drive sizing.
Fault
-
Fault message ID
537469825 0x20092381 Description
CauseWarning - Utilization of the power section (ixt) too high
RemedyPower section overloaded.
Severity/responseCheck drive sizing.
Warning
-
Fault message ID
537469828 0x20092384 Description
CauseUltimate motor current reached
RemedyUltimate motor current reached.
Severity/response- Reduce the maximum current of the inverter. 0x6073
- Optimize the current controller. 0x2942
Fault > CiA402 (configurable)
Setting parameters: 0x2D46:002
-
Fault message ID
537469829 0x20092385 Description
CauseParameterized max. motor current > max. device current
RemedyParameterized max. motor current 0x6073 > max. device current 0x2DDF:002
Severity/responseReduce max. motor current. 0x6073
Warning
-
Fault message ID
537469830 0x20092386 Description
CauseClamp is active
RemedyMax. device current has been reached. (Display in 0x2DDF:002)
Severity/response- Select a flatter speed ramp.
- Reduce the load.
- Set Imax controller more dynamically. 0x2B08
Warning
-
Fault message ID
537469833 0x20092389 Description
CauseWarning - device utilization (ixt) too high
RemedyFrequent and too long acceleration processes with overcurrent.
Severity/responseCheck drive sizing.
Warning
-
Fault message ID
537469835 0x2009238B Description
CauseTrouble - Device utilization (ixt) too high
RemedyFrequent and too long acceleration processes with overcurrent.
Severity/responseCheck drive sizing.
Fault
-
Fault message ID
537473409 0x20093181 Description
CauseMains failure
RemedyThe motor was decelerated to standstill via the mains failure control without an undervoltage fault occurring.
Severity/response- Check mains voltage.
- Check mains settings.
- Check fuses.
Fault
-
Fault message ID
537477762 0x20094282 Description
CauseThermal overload of control unit
Remedy- Control card temperature > 100 °C
- Ambient temperature too high
Severity/response- Provide for better cooling.
- Reduce ambient temperature.
Information
-
Fault message ID
537478016 0x20094380 Description
CauseFault - Motor temperature sensor
RemedyMotor PTC error.
Severity/responseConnect PTC or switch off monitoring.
Warning (configurable)
Setting parameters: 0x2D49:002
-
Fault message ID
537478017 0x20094381 Description
CauseError - Motor temperature monitoring (PTC)
RemedyMotor PTC error.
Severity/responseConnect PTC or switch off monitoring.
Fault > CiA402 (configurable)
Setting parameters: 0x2D48:002
-
Fault message ID
537478018 0x20094382 Description
CauseMotor overtemperature (load encoder/master encoder)
RemedyMotor temperature via load encoder higher than variable temperature limit.
Severity/responseConnect PTC or switch off monitoring. Set a higher warning threshold (0x2D49:003) and/or error threshold (0x2D49:004).
Warning (configurable)
Setting parameters: 0x2D49:002
-
Fault message ID
537478019 0x20094383 Description
CauseMotor temperature sensor error (load encoder/master encoder)
RemedyMotor PTC error.
Severity/responseConnect PTC or switch off monitoring.
Warning (configurable)
Setting parameters: 0x2D49:002
-
Fault message ID
537485328 0x20096010 Description
CauseInternal error
RemedyInternal error
Severity/responseRestart the device. If the error persists, contact the manufacturer.
Warning
-
Fault message ID
537486096 0x20096310 Description
CauseIncorrect parameter set download
RemedyCRC error in the parameter set detected. Vendor, product code or OBD revision are different. The parameter set is unknown.
Severity/responseRecreate parameter set. Repeat parameter set download.
Warning
-
Fault message ID
537486112 0x20096320 Description
CauseParameter error in object
RemedyUnknown index in the parameter set.
Severity/responseRecreate parameter set.
Warning
-
Fault message ID
537489584 0x200970B0 Description
CauseConnected network option is not supported
RemedyThe network option plugged into the inverter is not supported by the firmware.
Severity/responseUpdate the firmware to a version that supports the network option. Use the network option supported by the current firmware version.
Fault
-
Fault message ID
537490179 0x20097303 Description
CauseFault - Motor feedback
RemedyDefective encoder cable. Defective encoder.
Severity/responseCheck encoder cable. Check encoder. Switch off monitoring if no encoder is used.
Fault > CiA402 (configurable)
Setting parameters: 0x2C45
-
Fault message ID
537490180 0x20097304 Description
CauseError - Load encoder/master encoder
RemedyDefective encoder cable. Defective encoder.
Severity/responseCheck encoder cable. Check encoder. Switch off monitoring if no encoder is used.
Fault > CiA402 (configurable)
Setting parameters: 0x2C55
-
Fault message ID
537490304 0x20097380 Description
CauseMotor encoder - Communication error
RemedyThe communication to an encoder is disturbed.
Severity/responseCheck the supply voltage of the encoder. (0x2C42:002) Check encoder cable.
Fault > CiA402 (configurable)
Setting parameters: 0x2C41:004
-
Fault message ID
537490305 0x20097381 Description
CauseMotor encoder - wrong absolute value because motor speed is too high
RemedyThe absolute encoder position cannot be accepted as the motor rotates too fast.
Severity/responseLet the motor coast.
Fault > CiA402 (configurable)
Setting parameters: 0x2C41:004
-
Fault message ID
537490306 0x20097382 Description
CauseLoad encoder/master encoder - Communication error
RemedyThe communication to an encoder is disturbed.
Severity/responseCheck the supply voltage of the encoder. (0x2C42:002) Check encoder cable.
Fault > CiA402 (configurable)
Setting parameters: 0x2C51:004
-
Fault message ID
537490307 0x20097383 Description
CauseLoad encoder/master encoder - wrong absolute value because motor speed is too high
RemedyThe absolute encoder position cannot be accepted as the motor rotates too fast.
Severity/responseLet the motor coast.
Fault > CiA402 (configurable)
Setting parameters: 0x2C51:004
-
0x2871:034
Parameter
Safety interface bits: SLS2 observed Data type
BOOLEAN Default setting
- (Read only) Attributes
- -
0x2871:035
Parameter
Safety interface bits: SLS3 observed Data type
BOOLEAN Default setting
- (Read only) Attributes
- -
0x2871:036
Parameter
Safety interface bits: SLS4 observed Data type
BOOLEAN Default setting
- (Read only) Attributes
- -
0x2871:037
Parameter
Safety interface bits: SMS observed Data type
BOOLEAN Default setting
- (Read only) Attributes
- -
0x2871:038
Parameter
Safety interface bits: SSM within limits Data type
BOOLEAN Default setting
- (Read only) Attributes
- -
0x2871:039
Parameter
Safety interface bits: SDIpos observed Data type
BOOLEAN Default setting
- (Read only) Attributes
- -
0x2871:040
Parameter
Safety interface bits: SDIneg observed Data type
BOOLEAN Default setting
- (Read only) Attributes
- -
0x2871:041
Parameter
Safety interface bits: SLP1 observed Data type
BOOLEAN Default setting
- (Read only) Attributes
- -
0x2871:042
Parameter
Safety interface bits: SLP2 observed Data type
BOOLEAN Default setting
- (Read only) Attributes
- -
0x2871:043
Parameter
Safety interface bits: SLP3 observed Data type
BOOLEAN Default setting
- (Read only) Attributes
- -
0x2871:044
Parameter
Safety interface bits: SLP4 observed Data type
BOOLEAN Default setting
- (Read only) Attributes
- -
0x2871:045
Parameter
Safety interface bits: SCA1 within limits Data type
BOOLEAN Default setting
- (Read only) Attributes
- -
0x2871:046
Parameter
Safety interface bits: SCA2 within limits Data type
BOOLEAN Default setting
- (Read only) Attributes
- -
0x2871:047
Parameter
Safety interface bits: SCA3 within limits Data type
BOOLEAN Default setting
- (Read only) Attributes
- -
0x2871:048
Parameter
Safety interface bits: SCA4 within limits Data type
BOOLEAN Default setting
- (Read only) Attributes
- -
0x2871:049
Parameter
Safety interface bits: PDSSpos observed Data type
BOOLEAN Default setting
- (Read only) Attributes
- -
0x2871:050
Parameter
Safety interface bits: PDSSneg observed Data type
BOOLEAN Default setting
- (Read only) Attributes
- -
0x2871:051
Parameter
Safety interface bits: SOS observed Data type
BOOLEAN Default setting
- (Read only) Attributes
- -
0x2871:052
Parameter
Safety interface bits: SBC activated Data type
BOOLEAN Default setting
- (Read only) Attributes
- -
0x2871:053
Parameter
Safety interface bits: SHom active Data type
BOOLEAN Default setting
- (Read only) Attributes
- -
0x2871:054
Parameter
Safety interface bits: SHom available Data type
BOOLEAN Default setting
- (Read only) Attributes
- -
0x2871:055
Parameter
Safety interface bits: Safe speed OK Data type
BOOLEAN Default setting
- (Read only) Attributes
- -
0x2871:056
Parameter
Safety interface bits: n=0 Data type
BOOLEAN Default setting
- (Read only) Attributes
- -
0x2871:057
Parameter
Safety interface bits: Positive direction Data type
BOOLEAN Default setting
- (Read only) Attributes
- -
0x2871:058
Parameter
Safety interface bits: Slip > 25% Data type
BOOLEAN Default setting
- (Read only) Attributes
-
No results.