i550
- Rated power 0.25 kW/0.33 HP
- Output current 1.7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 120 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.25 kW/0.33 HP
- Output current 1.7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 0.25 kW/0.33 HP
- Output current 1.7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 120 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.37 kW/0.5 HP
- Output current 1.3/1.1 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 0.55 kW/0.75 HP
- Output current 3.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 0.55 kW/0.75 HP
- Output current 3.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 1.8/1.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 120 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.75 kW/1 HP
- Output current 2.4/2.1 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 1.1 kW/1.5 HP
- Output current 6 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 120 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 1.1 kW/1.5 HP
- Output current 6 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 1.1 kW/1.5 HP
- Output current 6 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 1.1 kW/1.5 HP
- Output current 3.2/3 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 1.5 kW/2 HP
- Output current 7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 1.5 kW/2 HP
- Output current 7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 1.5 kW/2 HP
- Output current 3.9/3.5 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 2.2 kW/3 HP
- Output current 9.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 2.2 kW/3 HP
- Output current 9.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 5.6/4.8 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
-
Fault message ID
33154 0x8182 Description
Keypad displayCAN: bus off
CAN: bus off Cause
RemedyToo many faulty frames have been received.
- Defective cable (e. g. loose contact).
- Two nodes with the same node address.
Severity/response- Check wiring of the network.
- Check bus terminating resistor.
- Set the identical baud rate for each node of the network.
- Assign a unique node address to each node of the network.
- Eliminate EMC interferences.
Trouble (configurable)
- Change to the "Bus-Off" communication status.
-
Fault message ID
33155 0x8183 Description
Keypad displayCAN: warning
CAN bus warning Cause
RemedyToo many faulty frames have been received.
- Defective cable (e. g. loose contact).
- Two nodes with the same node address.
Severity/response- Check wiring of the network.
- Check bus terminating resistor.
- Set the identical baud rate for each node of the network.
- Assign a unique node address to each node of the network.
- Eliminate EMC interferences.
Warning (configurable)
-
Fault message ID
33156 0x8184 Description
Keypad displayCAN: heartbeat time-out consumer 1
CAN heartb. C1 Cause
RemedyWithin the heartbeat time 0x1016:001 (P520.01), no heartbeat telegram was received by node 1 to be monitored.
Severity/response- Check communication with the heartbeat producer.
- Reactivate heartbeat producer.
Fault (configurable)
-
Fault message ID
33157 0x8185 Description
Keypad displayCAN: heartbeat time-out consumer 2
CAN heartb. C2 Cause
RemedyWithin the heartbeat time 0x1016:002 (P520.02), no heartbeat telegram was received by node 2 to be monitored.
Severity/response- Check communication with the heartbeat producer.
- Reactivate heartbeat producer.
Fault (configurable)
-
Fault message ID
33158 0x8186 Description
Keypad displayCAN: heartbeat time-out consumer 3
CAN heartb. C3 Cause
RemedyWithin the heartbeat time 0x1016:003 (P520.03), no heartbeat telegram was received by node 3 to be monitored.
Severity/response- Check communication with the heartbeat producer.
- Reactivate heartbeat producer.
Fault (configurable)
-
Fault message ID
33159 0x8187 Description
Keypad displayCAN: heartbeat time-out consumer 4
CAN heartb. C4 Cause
RemedyWithin the heartbeat time 0x1016:004 (P520.04), no heartbeat telegram was received by node 4 to be monitored.
Severity/response- Check communication with the heartbeat producer.
- Reactivate heartbeat producer.
Fault (configurable)
-
Fault message ID
33168 0x8190 Description
Keypad displayNetwork - Watchdog time-out
Watchdog timeout Cause
RemedyTime-out during cyclic data reception, e.g. due to an interrupted communication link to the master or missing cyclic data.
Severity/response- Check wiring of the network.
- Eliminate EMC interferences.
Trouble (configurable)
-
Fault message ID
33169 0x8191 Description
Keypad displayNetwork - Disruption of cyclic data exchange
Cycl data error Cause
RemedyThe communication partner has interrupted the cyclic data exchange.
Severity/response- Check wiring of the network.
- The slave must receive new parameterisation and configuration files by the master, in order to be able to exchange data again.
No response (configurable)
-
Fault message ID
33170 0x8192 Description
Keypad displayNetwork - Initialization error
Net. Init. error Cause
RemedyThe initialisation of the communication stack has been interrupted due to an incorrect address setting or communication configuration.
Severity/responseCheck master/slave configuration and restart the devices.
Trouble (configurable)
-
Fault message ID
33171 0x8193 Description
Keypad displayNetwork - Invalid cyclic process data
Inv. cyclic data Cause
RemedyThe cyclic process data received are invalid.
Severity/responseCheck cyclic process data sent by the master.
Trouble (configurable)
-
Fault message ID
33185 0x81A1 Description
Keypad displayModbus: network time-out
Modbus time-out Cause
RemedyNo valid messages have been received via the Modbus for a longer time than the time-out time set in 0x2858:002 (P515.02).
Severity/response- Check communication with the master.
- Check wiring.
- Check bus termination.
Fault (configurable)
-
Fault message ID
33186 0x81A2 Description
Keypad displayModbus: incorrect request by master
Modbus request Cause
RemedyThe request by the master is invalid, e. g. invalid CRC checksum, non-supported function code, or impermissible data access.
Severity/responseCheck request by the master:
- Value in the valid range?
- Function code valid?
- No impermissible write access? (e. g. with regard to read-only parameters)
Warning The inverter (slave) responds to the master with an error code:
- 0x01 = invalid function code
- 0x02 = invalid data address
- 0x03 = invalid data value
- 0x04 = slave device failure
-
Fault message ID
33200 0x81B0 Description
Keypad displayNetwork communication faulty
Comm. faulty Cause
RemedyIn case of the Ethernet communication interface, an internal software error has occurred.
Severity/response- Switch inverter off and on again.
- In the event of a power failure during a firmware download, it is required to reload the firmware via the USB module and then restart the inverter.
Trouble
-
Fault message ID
33381 0x8265 Description
Keypad displayPOWERLINK: Loss of SoC
POWERLINK SoC Cause
RemedySoC of master was not received.
Severity/responseCheck configuration and system setup.
Trouble (configurable)
-
Fault message ID
33382 0x8266 Description
Keypad displayPOWERLINK: CRC error
POWERLINK CRC Cause
RemedyCRC frame defective.
Severity/responseCheck system setup.
Trouble (configurable)
-
Fault message ID
33414 0x8286 Description
Keypad displayNetwork - PDO mapping error
PDO map error Cause
Remedy- Invalid PDO assignment by the master.
- Internal PDO assignment was changed and does not comply with the configuration available in the master.
Severity/responseCheck data mapping in the master and slave.
Trouble (configurable) Setting parameters: 0x2859:003 (P515.03)
-
Fault message ID
33425 0x8291 Description
Keypad displayCAN: RPDO1 time-out
Timeout RPDO1 Cause
Severity/responseRPDO1 was not received within the time-out period set in 0x1400:005 (P540.05) or with the sync configured.
Fault (configurable)
-
Fault message ID
33426 0x8292 Description
Keypad displayCAN: RPDO2 time-out
Timeout RPDO2 Cause
Severity/responseRPDO2 was not received within the time-out period set in 0x1401:005 (P541.05) or with the sync configured.
Fault (configurable)
-
Fault message ID
33427 0x8293 Description
Keypad displayCAN: RPDO3 time-out
Timeout RPDO3 Cause
Severity/responseRPDO3 was not received within the time-out period set in 0x1402:005 (P542.05) or with the sync configured.
Fault (configurable)
-
Fault message ID
33553 0x8311 Description
Keypad displayTorque limit reached
Torque limit Cause
RemedyMotor has reached the torque limit:
- 0x2949:003 (P337.03): Actual positive torque limit
- 0x2949:004 (P337.04): Actual negative torque limit
Severity/response- Observe load requirements.
- Reduce motor load.
- Check set torque limits and sources for the torque limits.
No response (configurable)
-
Fault message ID
33664 0x8380 Description
Keypad displayFunction not allowed in selected operating mode
Func. n. allowed Cause
RemedyThe selected function is not permissible in the chosen operating mode.
- Selection of torque mode [-1] in 0x6060 (P301.00) with incompatible motor control in 0x2C00 (P300.00).
- Selection of invalid drive mode [0] in 0x6060 (P301.00).
Severity/response- Note: selection of torque mode [-1] in 0x6060 (P301.00) with incompatible motor control in 0x2C00 (P300.00).
- Check settings of operation modes.
- 0x6060 (P301.00)
Warning
-
Fault message ID
36992 0x9080 Description
Keypad displayKeypad removed
Keypad removed Cause
RemedyThe keypad was removed while the keypad control was activated.
Severity/response- Plug keypad back in or activate another control source.
Fault
-
Fault message ID
65282 0xFF02 Description
Keypad displayFault - Brake resistor overload
BrkResistor OL.F Cause
RemedyThe calculated thermal load of the brake resistor has reached the error threshold set in 0x2550:009 (P707.09). The regenerative energy is too high.
Severity/response- Check drive dimensioning.
- Check settings for the brake energy management. Note: The error status will be reset if the thermal load falls below the error threshold - 20 %.
Fault (configurable)
- The event can only be reset after a blocking time. Setting parameters: 0x2550:011 (P707.11)
-
Fault message ID
65285 0xFF05 Description
Keypad displaySafety option - Internal error
Safety int.Error Cause
RemedyThe safety module or safety circuit of the device was detected as being defective. The integrated safety technology is defective.
Severity/responseHardware error: it is necessary to contact the manufacturer since the device must be replaced. The inverter must be replaced. Note! The user is not allowed to change inverters that come with integrated safety technology.
- The safety module must not be removed.
- The user must not carry out any repairs on the safety module.
- The safety module is not a spare part.
Fault
- The inverter is disabled immediately. The motor has no torque (is coasting).
- The event can only be reset by mains switching.
-
Fault message ID
65286 0xFF06 Description
Keypad displayMotor overspeed
Motor overspeed Cause
RemedyThe motor speed has reached the error threshold for overspeed set in 0x2D44:001 (P350.01).
Severity/responseAdapt the maximum motor speed 0x6080 (P322.00) and the warning threshold or error threshold 0x2D44:001 (P350.01).
Fault (configurable)
- The event can only be reset after a blocking time. Setting parameters: 0x2D44:002 (P350.02)
-
0x10F3:010
Parameter
Diagnosis History: Diagnosis message 4 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:011
Parameter
Diagnosis History: Diagnosis message 5 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:012
Parameter
Diagnosis History: Diagnosis message 6 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:013
Parameter
Diagnosis History: Diagnosis message 7 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:014
Parameter
Diagnosis History: Diagnosis message 8 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:015
Parameter
Diagnosis History: Diagnosis message 9 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:016
Parameter
Diagnosis History: Diagnosis message 10 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:017
Parameter
Diagnosis History: Diagnosis message 11 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:018
Parameter
Diagnosis History: Diagnosis message 12 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:019
Parameter
Diagnosis History: Diagnosis message 13 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:020
Parameter
Diagnosis History: Diagnosis message 14 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:021
Parameter
Diagnosis History: Diagnosis message 15 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:022
Parameter
Diagnosis History: Diagnosis message 16 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:023
Parameter
Diagnosis History: Diagnosis message 17 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:024
Parameter
Diagnosis History: Diagnosis message 18 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:025
Parameter
Diagnosis History: Diagnosis message 19 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:026
Parameter
Diagnosis History: Diagnosis message 20 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:027
Parameter
Diagnosis History: Diagnosis message 21 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:028
Parameter
Diagnosis History: Diagnosis message 22 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:029
Parameter
Diagnosis History: Diagnosis message 23 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:030
Parameter
Diagnosis History: Diagnosis message 24 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:031
Parameter
Diagnosis History: Diagnosis message 25 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:032
Parameter
Diagnosis History: Diagnosis message 26 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:033
Parameter
Diagnosis History: Diagnosis message 27 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:034
Parameter
Diagnosis History: Diagnosis message 28 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT