i550
- Rated power 0.25 kW/0.33 HP
- Output current 1.7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 120 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.25 kW/0.33 HP
- Output current 1.7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 0.25 kW/0.33 HP
- Output current 1.7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 120 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.37 kW/0.5 HP
- Output current 1.3/1.1 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 0.55 kW/0.75 HP
- Output current 3.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 0.55 kW/0.75 HP
- Output current 3.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 1.8/1.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 120 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.75 kW/1 HP
- Output current 2.4/2.1 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 1.1 kW/1.5 HP
- Output current 6 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 120 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 1.1 kW/1.5 HP
- Output current 6 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 1.1 kW/1.5 HP
- Output current 6 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 1.1 kW/1.5 HP
- Output current 3.2/3 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 1.5 kW/2 HP
- Output current 7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 1.5 kW/2 HP
- Output current 7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 1.5 kW/2 HP
- Output current 3.9/3.5 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 2.2 kW/3 HP
- Output current 9.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 2.2 kW/3 HP
- Output current 9.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 5.6/4.8 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
-
Fault message ID
28833 0x70A1 Description
Keypad displayAnalog output 1 fault
AO1 fault Cause
RemedyOpen circuit or short circuit at analog output 1.
Severity/response- Check wiring of analog output 1.
- Check definition of the output range in 0x2639:001 (P440.01).
Warning
-
Fault message ID
28834 0x70A2 Description
Keypad displayAnalog output 2 fault
AO2 fault Cause
RemedyOpen circuit or short circuit at analog output 2.
Severity/response- Check wiring of analog output 2.
- Check definition of the output range in 0x263A:001 (P441.01).
Warning
-
Fault message ID
28961 0x7121 Description
Keypad displayFault - Pole position identification
Pole pos. error Cause
Remedy- Too many deviations during the pole position identification.
- Compared to the inverter, the rated motor current is too high or too low.
Severity/response- Check setting of the motor data.
- Ensure that the motor is at a standstill during the pole position identification process.
- Ensure that the motor and inverter match each other in terms of power.
Fault (configurable) Setting parameters: 0x2C60
-
Fault message ID
29056 0x7180 Description
Keypad displayMotor overcurrent
Mot max current Cause
RemedyThe motor current has exceeded the warning/ error threshold for the motor current monitoring set in 0x2D46:001 (P353.01).
Severity/response- Check motor load.
- Check drive dimensioning.
- Check warning threshold or error threshold set in 0x2D46:001 (P353.01).
Fault (configurable)
- The event can only be reset after a blocking time. Setting parameters: 0x2D46:002 (P353.02)
-
Fault message ID
29445 0x7305 Description
Keypad displayEncoder open circuit
Encoder error Cause
RemedyThe encoder signal loss monitoring function has detected a failure of the encoder signal.
Severity/response- Check the encoder connection.
- Check encoder cable for wire breakage.
- Check encoder current supply.
Warning (configurable) Setting parameters: 0x2C45 (P342.00)
-
Fault message ID
29573 0x7385 Description
Keypad displayFeedback system: speed limit
F.fdb spd limit Cause
RemedyThe feedback system exceeds the maximum permissible frequency range of the digital inputs.
Severity/responseCheck feedback system.
Warning
-
Fault message ID
30336 0x7680 Description
Keypad displayMemory module is full
EPM full Cause
RemedyThe memory module contains too many parameter settings.
Severity/responseExecute "Save user data" 0x2022:003 (P700.03) device command again. This reinitialises the user memory with the current parameter settings. In this way, parameter settings that are no longer required are automatically deleted.
Warning
- The parameter settings were not saved in the memory module.
-
Fault message ID
30337 0x7681 Description
Keypad displayMemory module not present
EPM not present Cause
RemedyThe inverter memory module was removed.
Severity/response1. Switch off inverter. 2. Plug the memory module into the inverter. 3. Switch the inverter on again. Note: The memory module cannot be replaced during ongoing operation!
Fault
- The default setting stored in the inverter firmware has been loaded.
- The error cannot be reset by the user.
-
Fault message ID
30338 0x7682 Description
Keypad displayInvalid user data
EPM invalid data Cause
RemedyThe user parameter settings in the memory module are invalid.
Severity/response1. Execute user parameter settings again. 2. Execute device command "Save user data" 0x2022:003 (P700.03).
Fault
- The user parameter settings are lost.
- The default settings were automatically loaded.
-
Fault message ID
30340 0x7684 Description
Keypad displayData not compl. saved before powerdown
Save incomplete Cause
RemedySaving of the parameter settings was interrupted by an unexpected disconnection.
Severity/response1. Check user parameter settings. (The loaded backup is an older version.) 2. If required, repeat the changes made last. 3. Execute device command "Save user data" 0x2022:003 (P700.03).
Warning
- The user parameter settings were not fully saved.
- At the next switch-on, the data stored are copied to the user memory.
-
Fault message ID
30345 0x7689 Description
Keypad displayMemory module: invalid OEM data
data invalid OEM Cause
RemedyThe OEM memory contains invalid parameter settings or is empty.
Severity/response- Execute device command "Save OEM data" 0x2022:006 (P700.06).
- Thus, the user parameter settings get lost!
Warning
- The user parameter settings were automatically loaded.
-
Fault message ID
30346 0x768A Description
Keypad displayMemory module: wrong type
Wrong EPM Cause
RemedyThe memory module connected is not supported by the inverter.
Severity/response1. Switch off inverter. 2. Replace plugged-in memory module by a memory module that matches the inverter. 3. Switch the inverter on again.
Fault
- The default setting stored in the inverter firmware has been loaded.
- The error cannot be reset by the user.
-
Fault message ID
30352 0x7690 Description
Keypad displayEPM firmware version incompatible
EPM-FW incomp. Cause
RemedyThe parameter settings saved in the memory module are incompatible with the firmware version.
Severity/response1. Execute device command "Load default settings" 0x2022:001 (P700.01). 2. Execute "Save user data" 0x2022:003 (P700.03) or "Save OEM data" 0x2022:006 (P700.06) device command.
Fault
- The data have been loaded into the RAM memory, but they are incompatible.
-
Fault message ID
30353 0x7691 Description
Keypad displayEPM data: firmware type incompatible
EPM: FW incomp. Cause
RemedyThe parameter settings saved in the memory module are incompatible with the firmware type. Example: Memory module of an inverter with an application I/O is used in an inverter with a standard I/O.
Severity/response1. Execute device command "Load default settings" 0x2022:001 (P700.01). 2. Execute "Save user data" 0x2022:003 (P700.03) or "Save OEM data" 0x2022:006 (P700.06) device command.
Fault
- The data have been loaded into the RAM memory, but they are incompatible.
-
Fault message ID
30354 0x7692 Description
Keypad displayEPM data: new firmware type detected
UserCU not match Cause
RemedyThe parameter settings saved in the memory module do not match the inverter hardware.
Severity/response1. Check parameter settings. 2. Reset error. 3. Execute "Save user data" 0x2022:003 (P700.03) or "Save OEM data" 0x2022:006 (P700.06) device command.
Fault
- The data have been loaded into the RAM memory without being modified, and they are compatible.
- The settings loaded must be accepted by the user (see remedy).
-
Fault message ID
30355 0x7693 Description
Keypad displayEPM data: PU size incompatible
EPM PU size inco Cause
RemedyThe parameter settings saved in the memory module are incompatible with the inverter.
Severity/response1. Execute device command "Load default settings" 0x2022:001 (P700.01). 2. Execute "Save user data" 0x2022:003 (P700.03) or "Save OEM data" 0x2022:006 (P700.06) device command.
Fault
- The data have been loaded into the RAM memory, but they are incompatible.
-
Fault message ID
30356 0x7694 Description
Keypad displayEPM data: new PU size detected
EPM new PU size Cause
RemedyThe parameter settings saved in the memory module comply with a different hardware. Example: Memory module of an inverter with a power of 3 kW is used in an inverter with a power of 18.5 kW.
Severity/response1. Check parameter settings. 2. Reset error. 3. Execute "Save user data" 0x2022:003 (P700.03) or "Save OEM data" 0x2022:006 (P700.06) device command.
Fault
- The data have been loaded into the RAM memory without being modified, and they are compatible.
- The settings loaded must be accepted by the user (see remedy).
-
Fault message ID
30357 0x7695 Description
Keypad displayInvalid parameter changeover configuration
InvalidChgovrCfg Cause
RemedyOne or more parameters can no longer be used for the "Parameter change-over" function.
Severity/response1. Check error message for parameter change- over in 0x4047:001 (P756.01). 2. Correct the list entry shown in 0x4047:002 (P756.02).
Warning
- The parameter change-over function is deactivated.
-
Fault message ID
30358 0x7696 Description
Keypad displayEPM data: unknown parameter found
Unkn. Par in EPM Cause
RemedyThe memory module contains parameter settings for one or several parameters that are not known to the inverter.
Severity/responseExecute the "Save user data" 0x2022:003 (P700.03) device command. This reinitialises the user memory with the current parameter settings. In this way, parameter settings that are no longer required are automatically deleted.
Information
-
Fault message ID
30359 0x7697 Description
Keypad displayParameter changes lost
Parameter loss Cause
RemedyA voltage failure has occurred and changed parameter settings that had not been saved yet were available.
Severity/response1. Execute parameter settings again. 2. Execute device command "Save user data" 0x2022:003 (P700.03).
Fault
- The parameter settings changed have been lost.
-
Fault message ID
33042 0x8112 Description
Keypad displayNetwork - Time-out explicit message
TO expl. msg Cause
Remedy- Within the time-out period for explicit messages, which has been parameterised by the scanner, no "explicit message" was received.
- The connection to the scanner has been interrupted.
- Failure of an explicit connection.
Severity/response- Check cables and terminals.
- Plug network cables into the Ethernet port.
- Check the requested package interval (RPI) of the explicit connection.
- Increase time limit for explicit messages in the scanner.
Warning (configurable) Setting parameters: 0x2859:006 (P515.06)
-
Fault message ID
33044 0x8114 Description
Keypad displayNetwork - Overall communication time-out
TO overall comm Cause
Remedy- EtherNet/IP: the maximum permissible time- out period for the CIP communication set in 0x23A1:010 (P510.10) has been exceeded.
- Modbus TCP/IP: the maximum permissible time-out period for the TCP communication set in 0x23B1:010 (P510.10) has been exceeded.
Severity/response- Check cables and terminals.
- Connect network cable.
Warning (configurable)
-
Fault message ID
33045 0x8115 Description
Keypad displayTime-out (PAM)
(PAM) Time-out Cause
RemedyThe parameter access monitoring (PAM) function has been activated. For a time longer than the time-out period set in 0x2552:003 (P595.03), no value was entered into the "Keep- alive-Register" 0x2552:002 (P595.02).
Severity/response- Check communication.
- Check settings of the parameter access monitoring (PAM) function.
No response (configurable) Setting parameters: 0x2552:004 (P595.04)
-
Fault message ID
33046 0x8116 Description
Keypad displayModbus TCP master time-out
MBTCP mast t-out Cause
RemedyNo valid messages have been received by the Modbus master for a time longer than the time- out period set in 0x23B6:001 (P514.01).
Severity/responseCheck communication with the master.
Fault (configurable) Setting parameters: 0x2859:008 (P515.08)
-
Fault message ID
33047 0x8117 Description
Keypad displayModbus TCP Keep Alive time-out
MB.Keep Alive TO Cause
RemedyFor a time longer than the time-out period set in 0x23B6:002 (P514.02), no value was entered into the Keep alive register 0x23B6:005 (P514.05).
Severity/responseCheck communication with the master.
Fault (configurable) Setting parameters: 0x2859:009 (P515.09)
-
0x1000
Parameter
Device type Data type
U32 Default setting
- (Read only) Attributes
- -
0x1001
Parameter
Error register Data type
U8 Default setting
- (Read only) Attributes
- -
0x1003:001
Parameter
ERR_History_ADOM: ErrorEntry_DOM 1 Data type
U32 Default setting
- (Read only) Fieldbus
POWERLINK -
0x1003:002
Parameter
ERR_History_ADOM: ErrorEntry_DOM 2 Data type
U32 Default setting
- (Read only) Fieldbus
POWERLINK -
0x1003:003
Parameter
ERR_History_ADOM: ErrorEntry_DOM 3 Data type
U32 Default setting
- (Read only) Fieldbus
POWERLINK -
0x1003:004
Parameter
ERR_History_ADOM: ErrorEntry_DOM 4 Data type
U32 Default setting
- (Read only) Fieldbus
POWERLINK -
0x1003:005
Parameter
ERR_History_ADOM: ErrorEntry_DOM 5 Data type
U32 Default setting
- (Read only) Fieldbus
POWERLINK -
0x1003:006
Parameter
ERR_History_ADOM: ErrorEntry_DOM 6 Data type
U32 Default setting
- (Read only) Fieldbus
POWERLINK -
0x1003:007
Parameter
ERR_History_ADOM: ErrorEntry_DOM 7 Data type
U32 Default setting
- (Read only) Fieldbus
POWERLINK -
0x1003:008
Parameter
ERR_History_ADOM: ErrorEntry_DOM 8 Data type
U32 Default setting
- (Read only) Fieldbus
POWERLINK -
0x1003:009
Parameter
ERR_History_ADOM: ErrorEntry_DOM 9 Data type
U32 Default setting
- (Read only) Fieldbus
POWERLINK -
0x1003:010
Parameter
ERR_History_ADOM: ErrorEntry_DOM 10 Data type
U32 Default setting
- (Read only) Fieldbus
POWERLINK -
0x1005
Parameter
COB-ID SYNC Data type
U32 Default setting
0x00000080 Fieldbus
CANopen -
0x1006
Parameter
NMT_CycleLen_U32 Data type
U32 Default setting
0 Fieldbus
POWERLINK -
0x1006
Parameter
Communication cyclic period Data type
U32 Default setting
0 µs Fieldbus
CANopen -
0x1008
Parameter
Manufacturer device name Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x1009
Parameter
Manufacturer hardware version Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x100A
Parameter
Manufacturer software version Data type
STRING[50] Default setting
- (Read only) Attributes
- -
0x1014
Parameter
COB-ID Emergency telegram (EMCY) Data type
U32 Default setting
- (Read only) Fieldbus
CANopen -
0x1015
Parameter
Inhibit time EMCY Data type
U16 Default setting
0.0 ms Fieldbus
CANopen -
0x1016:000
Parameter
Consumer heartbeat time: Highest sub-index supported Data type
U8 Display Code
P520.00 Default setting
- (Read only) Fieldbus
CANopen -
0x1016:001
Parameter
Consumer heartbeat time: Consumer heartbeat time 1 Data type
U32 Display Code
P520.01 Default setting
0x00000000 Fieldbus
CANopen -
0x1016:002
Parameter
Consumer heartbeat time: Consumer heartbeat time 2 Data type
U32 Display Code
P520.02 Default setting
0x00000000 Fieldbus
CANopen -
0x1016:003
Parameter
Consumer heartbeat time: Consumer heartbeat time 3 Data type
U32 Display Code
P520.03 Default setting
0x00000000 Fieldbus
CANopen -
0x1016:004
Parameter
Consumer heartbeat time: Consumer heartbeat time 4 Data type
U32 Display Code
P520.04 Default setting
0x00000000 Fieldbus
CANopen
No results.