i550
- Rated power 0.25 kW/0.33 HP
- Output current 1.7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 120 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.25 kW/0.33 HP
- Output current 1.7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 0.25 kW/0.33 HP
- Output current 1.7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 120 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 0.37 kW/0.5 HP
- Output current 2.4 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.37 kW/0.5 HP
- Output current 1.3/1.1 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 0.55 kW/0.75 HP
- Output current 3.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 0.55 kW/0.75 HP
- Output current 3.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.55 kW/0.75 HP
- Output current 1.8/1.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 120 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 0.75 kW/1 HP
- Output current 4.2 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 0.75 kW/1 HP
- Output current 2.4/2.1 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 1.1 kW/1.5 HP
- Output current 6 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 120 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 1.1 kW/1.5 HP
- Output current 6 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 1.1 kW/1.5 HP
- Output current 6 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 1.1 kW/1.5 HP
- Output current 3.2/3 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 1.5 kW/2 HP
- Output current 7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 1.5 kW/2 HP
- Output current 7 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 1.5 kW/2 HP
- Output current 3.9/3.5 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 2.2 kW/3 HP
- Output current 9.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
- Rated power 2.2 kW/3 HP
- Output current 9.6 A
- Output frequency 0-599 Hz
- Rated mains voltage 1/N(3)/PE 230/240 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter not integrated
- Rated power 2.2 kW/3 HP
- Output current 5.6/4.8 A
- Output frequency 0-599 Hz
- Rated mains voltage 3/PE 400/480 V AC
- Motor output Single axis
- Generation A
- Product series i550 cabinet
- EMC filter Integrated
-
Fault message ID
17025 0x4281 Description
Keypad displayHeat sink fan warning
Heatsink fan Cause
RemedyWarning of the heatsink fan.
Severity/responseClean fan and ventilation slots. If required, replace fan. The fans can be unlocked via locking hooks and can then be removed.
Warning
-
Fault message ID
17029 0x4285 Description
Keypad displayPU overtemperature warning
Warn.PU Overtemp Cause
RemedyThe heatsink temperature of the power unit (display in 0x2D84:001 (P117.01)) has exceeded the warning threshold set in 0x2D84:002.
- Ambient temperature too high.
- Fan or ventilation slots are polluted.
- Fan is defective.
Severity/response- Provide for a sufficient cooling of the device.
- Clean fan and ventilation slots.
- If required, replace fan.
Warning
-
Fault message ID
17168 0x4310 Description
Keypad displayMotor overtemperature
Overtemp. motor Cause
RemedyThe motor temperature sensor connected to terminals X109/T1 and X109/T2 measures a too high motor temperature.
- Motor too hot by impermissibly high currents.
- Motor too hot by frequent and too long acceleration processes.
Severity/response- Check drive dimensioning.
- Check motor temperature sensor and wiring.
Fault (configurable)
- The event can only be reset after a blocking time.
-
Fault message ID
20754 0x5112 Description
Keypad displayExternal supply voltage critical
Ext. supply low Cause
RemedyExternal supply voltage failed or too low.
Severity/response- Check optional external 24V voltage supply (terminal X3/24E), if connected.
- Check mains voltage.
Warning
-
Fault message ID
20864 0x5180 Description
Keypad displayOverload 24 V supply
Overload 24V Cause
RemedyOutput current at the 24V output or at the digital outputs too high.
Severity/responseCheck 24V output and digital outputs for earth fault or overload.
Warning
-
Fault message ID
21376 0x5380 Description
Keypad displayOEM hardware incompatible
Incomp. OEM HW Cause
RemedyThe control unit (OEM hardware) is not compatible with the power unit (OEM hardware).
Severity/response- Use compatible hardware.
- Contact the OEM.
Fault
- The inverter is disabled immediately. The motor has no torque (is coasting).
- The event can only be reset by mains switching.
-
Fault message ID
24970 0x618A Description
Keypad displayWarning - Internal fan
Internal fan Cause
RemedyWarning of the internal fan.
Severity/responseCheck/replace internal fan.
Warning
-
Fault message ID
25216 0x6280 Description
Keypad displayTrigger/functions connected incorrectly
P400 config err Cause
RemedyThe assignment directives have not been observed.
- If the "flexible I/O configuration" is active as control source, the "Enable inverter" or "Run" function must be connected to a digital input in order that the motor can be stopped again any time!
- The use of the "Start forward (CW)" and "Start reverse (CCW)" functions excludes the use of the "Run forward (CW)" and "Run reverse (CCW)" functions, and vice versa.
Severity/responseCheck and correct the assignment of the triggers to the functions.
- With keypad or network control, the two "Enable inverter 0x2631:001 (P400.01)" and "Run 0x2631:002 (P400.02)" functions can also be set to "Constant TRUE [1]" to start the motor.
Trouble
-
Fault message ID
25217 0x6281 Description
Keypad displayUser-defined fault 1
User fault 1 Cause
RemedyFlexible I/O configuration: the "Activate fault 1" function was activated via the trigger selected in 0x2631:043 (P400.43).
Severity/responseEliminate error cause and then reset error.
Fault
-
Fault message ID
25218 0x6282 Description
Keypad displayUser-defined fault 2
User fault 2 Cause
RemedyFlexible I/O configuration: the "Activate fault 2" function was activated via the trigger selected in 0x2631:044 (P400.44).
Severity/responseEliminate error cause and then reset error.
Fault
-
Fault message ID
25232 0x6290 Description
Keypad displayWarning invert rotation
Invert rotation Cause
Remedy- Negative setpoint selection with an active limitation of rotation 0x283A (P304.00).
- The "Reverse rotational direction" 0x2631:013 (P400.13) function was requested with an active limitation of rotation 0x283A (P304.00).
Severity/response- Check setpoint selection and trigger.
- Check setting in 0x283A (P304.00).
Warning
- The motor is brought to a standstill, since a reversal of the rotating direction is not permissible.
-
Fault message ID
25233 0x6291 Description
Keypad displayMaximuml allowed troubles exceeded
Trouble overflow Cause
RemedyThe number of permitted restart attempts after a fault set in 0x2839:003 (P760.03) was exceeded. The fault occurred to frequently and could not be reset.
Severity/responseCheck and the eliminate the fault.
Fault
- The motor remains at a standstill, no automatic restart is executed.
-
Fault message ID
25248 0x62A0 Description
Keypad displayUser-defined fault (LECOM)
UserFault(LECOM) Cause
RemedyThe "Activate fault" function was triggered via bit 10 of the LECOM control word 0x400B:002 (P592.02).
Severity/responseEliminate error cause and then reset error.
Fault
-
Fault message ID
25249 0x62A1 Description
Keypad displayNetwork: user fault 1
Netw.UserFault 1 Cause
RemedyThe "Activate fault 1" function was triggered via the NetWordIN1 data word 0x4008:001 (P590.01).
Severity/responseEliminate error cause and then reset error.
Fault
-
Fault message ID
25250 0x62A2 Description
Keypad displayNetwork: user fault 2
Netw.UserFault 2 Cause
RemedyThe "Activate fault 2" function was triggered via the NetWordIN1 data word 0x4008:001 (P590.01).
Severity/responseEliminate error cause and then reset error.
Fault
-
Fault message ID
25265 0x62B1 Description
Keypad displayNetWordIN1 configuration incorrect
NetWordIN1 error Cause
RemedyTwo bits of the NetWordIN1 data word 0x4008:001 (P590.01) were assigned to the same function.
Severity/responseCheck and correct configuration of the NetWordIN1 data word.
- The functions that are to be triggered via bits 0 ... 15 of the NetWordIN1 data word are defined in 0x400E:001 (P505.01) ... 0x400E:016 (P505.16).
Trouble
-
Fault message ID
25266 0x62B2 Description
Keypad displayChanged device ID not yet active
Dev-ID changed Cause
RemedyThe device ID of the device was changed manually.
Severity/response1. Execute device command "Save user data" 0x2022:003 (P700.03). 2. Switch inverter off and on again.
Fault
-
Fault message ID
25267 0x62B3 Description
Keypad displayDefault settings not yet active
Settings error Cause
RemedyThe “Back-to-Box” system command has been executed. The standard parameter set has been written and saved. Communication is deactivated and the device is in stop status.
Severity/responseSwitch inverter off and on again.
Fault
-
Fault message ID
25505 0x63A1 Description
Keypad displayCU: load error ID tag
CU ID tag error Cause
RemedyCalibration data of the control unit not compatible or faulty.
Severity/response- Update firmware of the inverter to the most recent version.
- If the error persists, the control unit or the device has to be replaced. In this case, please contact the manufacturer.
Fault
- The inverter is disabled immediately. The motor has no torque (is coasting).
- The event can only be reset by mains switching.
-
Fault message ID
25506 0x63A2 Description
Keypad displayPU: load error ID tag
PU ID tag error Cause
RemedyCalibration data of the power unit not compatible or faulty.
Severity/response- Update firmware of the inverter to the most recent version.
- If the error persists, the power unit or the device has to be replaced. In this case, please contact the manufacturer.
Fault
- The inverter is disabled immediately. The motor has no torque (is coasting).
- The event can only be reset by mains switching.
-
Fault message ID
25507 0x63A3 Description
Keypad displayPower unit unknown
PU unknown Cause
RemedyThe power unit installed is not supported by the software.
Severity/responseUpdate firmware of the inverter to the most recent version.
Fault
- The inverter is disabled immediately. The motor has no torque (is coasting).
- The event can only be reset by mains switching.
-
Fault message ID
28800 0x7080 Description
Keypad displayAssertion level monitoring (Low/High)
Assertionlevel Cause
RemedyThe last setting of the connection level differs from the saved setting.
Severity/response1. Execute device command "Save user data" 0x2022:003 (P700.03). 2. Switch inverter off and on again.
Fault
-
Fault message ID
28801 0x7081 Description
Keypad displayFault - Analog input 1
fault AI1 Cause
RemedyThe monitoring function of the input signal configured for analog input 1 in 0x2636:008 (P430.08) and 0x2636:009 (P430.09) has been triggered.
Severity/response- Check input signal at analog input 1.
- Check configuration of the monitoring function.
Fault (configurable) Setting parameters: 0x2636:010 (P430.10)
-
Fault message ID
28802 0x7082 Description
Keypad displayAnalog input 2 fault
AI2 fault Cause
RemedyThe monitoring function of the input signal configured for analog input 2 in 0x2637:008 (P431.08) and 0x2637:009 (P431.09) has been triggered.
Severity/response- Check input signal at analog input 2.
- Check configuration of the monitoring function.
Fault (configurable) Setting parameters: 0x2637:010 (P431.10)
-
Fault message ID
28803 0x7083 Description
Keypad displayHTL input fault
HTL input fault Severity/response
No response (configurable) Setting parameters: 0x2641:006 (P416.06)
-
0x1017
Parameter
Producer heartbeat time Data type
U16 Display Code
P522.00 Default setting
0 ms Fieldbus
CANopen -
0x1018:001
Parameter
Identity object: Vendor ID Data type
U32 Default setting
- (Read only) Attributes
- -
0x1018:002
Parameter
Identity object: Product Code Data type
U32 Default setting
- (Read only) Attributes
- -
0x1018:003
Parameter
Identity object: Revision number Data type
U32 Default setting
- (Read only) Attributes
- -
0x1018:004
Parameter
Identity object: Serial number Data type
U32 Default setting
- (Read only) Attributes
- -
0x1029:000
Parameter
Error behavior: Highest sub-index supported Data type
U8 Default setting
- (Read only) Fieldbus
CANopen -
0x1029:001
Parameter
Error behavior: Communication error Data type
U8 Default setting
Status > Pre-operational [0] Fieldbus
CANopen -
0x1030:001
Parameter
NMT_InterfaceGroup_0h_REC: InterfaceIndex_U16 Data type
U16 Default setting
- (Read only) Fieldbus
POWERLINK -
0x1030:002
Parameter
NMT_InterfaceGroup_0h_REC: InterfaceDescription_VSTR Data type
STRING[32] Default setting
- (Read only) Fieldbus
POWERLINK -
0x1030:003
Parameter
NMT_InterfaceGroup_0h_REC: InterfaceType_U8 Data type
U8 Default setting
- (Read only) Fieldbus
POWERLINK -
0x1030:004
Parameter
NMT_InterfaceGroup_0h_REC: InterfaceMtu_U32 Data type
U32 Default setting
- (Read only) Fieldbus
POWERLINK -
0x1030:005
Parameter
NMT_InterfaceGroup_0h_REC: InterfacePhysAddress_ OSTR Data type
OCTET[6] Default setting
- (Read only) Fieldbus
POWERLINK -
0x1030:006
Parameter
NMT_InterfaceGroup_0h_REC: InterfaceName_VSTR Data type
STRING[32] Default setting
- (Read only) Fieldbus
POWERLINK -
0x1030:007
Parameter
NMT_InterfaceGroup_0h_REC: InterfaceOperState_U8 Data type
U8 Default setting
- (Read only) Fieldbus
POWERLINK -
0x1030:008
Parameter
NMT_InterfaceGroup_0h_REC: InterfaceAdminState_U8 Data type
U8 Default setting
0 Fieldbus
POWERLINK -
0x1030:009
Parameter
NMT_InterfaceGroup_0h_REC: Valid_BOOL Data type
U8 Default setting
0 Fieldbus
POWERLINK -
0x10F3:001
Parameter
Diagnosis History: Maximum Messages Data type
U8 Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:002
Parameter
Diagnosis History: Newest Message Data type
U8 Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:003
Parameter
Diagnosis History: Newest Acknowledged Message Data type
U8 Default setting
0 Fieldbus
EtherCAT -
0x10F3:004
Parameter
Diagnosis History: New message available Data type
U8 Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:005
Parameter
Diagnosis History: Flags Data type
U16 Default setting
1 Fieldbus
EtherCAT -
0x10F3:006
Parameter
Diagnosis History: Diagnosis message 0 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:007
Parameter
Diagnosis History: Diagnosis message 1 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:008
Parameter
Diagnosis History: Diagnosis message 2 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT -
0x10F3:009
Parameter
Diagnosis History: Diagnosis message 3 Data type
OCTET[19] Default setting
- (Read only) Fieldbus
EtherCAT
No results.